T2 Pluggable Surge Protection Devices with maximum discharge surge current of 40kA. References : 23201, 23202, 23203. For the primary protection of networks phase and 3-phases power supply network installations located in sites with high keraunic level or as a supplement to a type 1 SPD. • • • • •

Type 2 SPD with Imax 40 kA / Un=400V Nominal current In 15kA Level of protection Up 2kV Remote and optical fault indicator contact EN 61643-11 / IEC 61643-1

TECHNICAL DATA References

23201

23202

23203

Type of network

TT-TN-IT 3*L +N

TT-TN-IT 3*L

TT-TN-IT L+N

Nominal voltage Un (VAC)

400

400

400

Temporary overvoltage withstand UT

Uc

Uc

Uc

Max. discharge surge current lmax (8/20μs)

40 kA

Nominal current In (8/20μs)

15 kA

Level of protection Up (In)

2 kV

2 kV

Residual voltage Ures at5kA

1,5kV

2 kV

Leakage current lpe

< 1 mA

Follow current quenching capacity N-PE

0 mA

Time response (ns)

< 25

Max. required backup fuse

max.125 A gG/gL

Short circuit current Icc

25 kA at50Hz

Conductor cross section L; N; PE

4-35 mm² (stranded : 25 mm² max.)

Remote indicator contact Conductor cross section

1.5 mm² (stranded,solid)

Ambient temperature (operation)

-20°C / +80° C

Degree of protection / Mounting type

IP20 / Rail din

Replacement plug

Reference 23208

A France Protection product

FRANCE PARATONNERRES   ­­­    ZA de Clocher 23000 Guéret  ­­­  FRANCE Tel : 33 555 523 933    ­­­   Fax : 33 555 819 982 web : http:// www.france­paratonnerres.com ­­­ e­mail : rx@france­paratonnerres.com


T2 Pluggable Surge Protection Devices with maximum discharge surge current of 40kA. References : 23204, 23205, 23206. For the primary protection of networks phase and 3-phases power supply network installations located in sites with high keraunic level or as a supplement to a type 1 SPD. • • • • •

Type 2 SPD with Imax 40 kA / Un=230V Nominal current In 15kA Level of protection Up 1,4kV Remote and optical fault indicator contact EN 61643-11 / IEC 61643-1

TECHNICAL DATA References

23204

23205

23206

Type of network

TT-TN 3*L +N

TT-TN 3*L

TT-TN L+N

Nominal voltage Un (VAC)

230

230

230

Temporary overvoltage withstand UT

> 400 VAC

> 400 VAC

> 400 VAC

Max. discharge surge current lmax (8/20μs)

40 kA

Nominal current In (8/20μs)

15 kA

Level of protection Up (In)

1,4 kV

1,4 kV

1,4 kV

Residual voltage Ures at 5kA

1,05kV

Leakage current lpe

< 1 mA

Follow current quenching capacity N-PE

0 mA

Time response (ns)

< 25

Max. required backup fuse

max.125 A gG/gL

Short circuit current Icc

25 kA at50Hz

Conductor cross section L; N; PE

4-35 mm² (stranded : 25 mm² max.)

Remote indicator contact Conductor cross section

1.5 mm² (stranded,solid)

Ambient temperature (operation)

-20°C / +80° C

Degree of protection / Mounting type

IP20 / Rail din

Replacement plug

Reference 23207

A France Protection product

FRANCE PARATONNERRES   ­­­    ZA de Clocher 23000 Guéret  ­­­  FRANCE Tel : 33 555 523 933    ­­­   Fax : 33 555 819 982 web : http:// www.france­paratonnerres.com ­­­ e­mail : rx@france­paratonnerres.com


T2 Pluggable Surge Protection Devices with maximum discharge surge current of 40kA. References : 23209, 23210. For the primary protection (common mode and differential) of networks phase and 3-phases power supply network installations located in sites with high keraunic level or as a supplement to a type 1 SPD. • • • • •

Type 2 SPD with Imax 40 kA / Un=230V Nominal current In 20kA Level of protection Up 1,5kV Optical fault indicator contact EN 61643-11 / IEC 61643-1

TECHNICAL DATA References

23209

23210

Type of network

TT-TNS 3*L +N

TT-TNS L+N

Nominal voltage Un (VAC)

230

230

Temporary overvoltage withstand UT

> 400 VAC

> 400 VAC

Max. discharge surge current lmax (8/20μs)

40 kA

Nominal current In (8/20μs)

20 kA

20 kA

Level of protection Up (In)

1,5 kV

1,5 kV

Residual voltage Ures at5kA

1,05kV

Leakage current lpe

< 1 mA

Follow current quenching capacity N-PE

0 mA

Time response (ns)

< 25

Max. required backup fuse

max.125 A gG/gL

Short circuit current Icc

25 kA at50Hz

Conductor cross section L; N; PE

4-35 mm² (stranded : 25 mm² max.)

Ambient temperature (operation)

-20°C / +80° C

Degree of protection / Mounting type

IP20 /Rail din

Replacement plug

Reference 23211 (L) Reference 23207 (N)

A France Protection product

FRANCE PARATONNERRES   ­­­    ZA de Clocher 23000 Guéret  ­­­  FRANCE Tel : 33 555 523 933    ­­­   Fax : 33 555 819 982 web : http:// www.france­paratonnerres.com ­­­ e­mail : rx@france­paratonnerres.com


T2 Compact pluggable Surge Protection Device with maximum discharge surge current of 40kA. Reference : 23212. For the primary protection (common mode and differential) of networks phase and 3-phases power supply network installations located in sites with high keraunic level or as a supplement to a type 1 SPD. • • • • •

Type 2 SPD with Imax 40 kA / Un=230V Nominal current In 15kA Level of protection Up 1,5kV/1,2kV Optical fault indicator contact EN 61643-11 / IEC 61643-1

TECHNICAL DATA References

23212

Type of network

TT-TNS L+N

Nominal voltage Un (VAC)

230

Temporary overvoltage withstand UT

> 400 VAC

Max. discharge surge current lmax (8/20μs)

40 kA

Nominal current In (8/20μs)

20 kA

Level of protection Up (In) (L-N / N-PE)

1,5 kV / 1,2 kV

Residual voltage Ures at5kA (L-N / N-PE)

1,1kV / 0,2kV

Leakage current lpe

< 1 mA

Follow current quenching capacity N-PE

100 A

Time response (ns)

< 100

Max. required backup fuse

max.100 A gG/gL

Short circuit currente Icc

10kA at50Hz

Conductor cross section L- N / N-PE

4-6 mm² / 4-25 mm²

Ambient temperature (operation)

-20°C / +80° C

Degree of protection / Mounting type

IP20 / Rail din

Replacement plug

Reference 23213

A France Protection product

FRANCE PARATONNERRES   ­­­    ZA de Clocher 23000 Guéret  ­­­  FRANCE Tel : 33 555 523 933    ­­­   Fax : 33 555 819 982 web : http:// www.france­paratonnerres.com ­­­ e­mail : rx@france­paratonnerres.com


T2 Pluggable Surge Protective Devices with maximum discharge surge current of 15kA. References : 23214, 23215, 23216, 23217, 23218, 23219. For the primary protection of networks phase and 3-phases power supply network installations located in sites with high keraunic level or as a supplement to a type 1 SPD. • • • • •

Type 2 SPD with Imax 15 kA / Un=230V Nominal current In 5kA Level of protection Up 1,2kV Remote and optical fault indicator contact EN 61643-11 / IEC 61643-1

TECHNICAL DATA References

23214 & 23215

23216 & 23217

23218 & 23219

Type of network

TT-TN L+N

TT-TN 3*L

TT-TN 3*L+N

Nominal voltage Un (VAC)

230

Temporary overvoltage withstand UT

> 400 VAC

Max. discharge surge current lmax (8/20μs)

15 kA

Nominal current In (8/20μs)

5 kA

5 kA

5 kA

Level of protection Up (In)

1,2 kV

1,2 kV

1,2 kV

Residual voltage Ures at 4kA

1,1kV

Leakage current lpe

< 1 mA

Follow current quenching capacity N-PE

0 mA

Time response (ns)

< 25

Max. required backup fuse

max.63 A gG/gL

Short circuit current Icc

25 kA at50Hz

Conductor cross section L; N; PE

4-35 mm² (stranded : 25 mm² max.)

Remote indicator contact Conductor cross section

1.5 mm² (stranded, solid)

Ambient temperature (operation)

-20°C / +80° C

Degree of protection / Mounting type

IP20 / Rail din

Replacement plug

Reference 23220

A France Protection product

FRANCE PARATONNERRES   ­­­    ZA de Clocher 23000 Guéret  ­­­  FRANCE Tel : 33 555 523 933    ­­­   Fax : 33 555 819 982 web : http:// www.france­paratonnerres.com ­­­ e­mail : rx@france­paratonnerres.com

TVSS Nivel 2  

tipo de tvss

Read more
Read more
Similar to
Popular now
Just for you