INSPECTION REPORT

For the Property at:

777 NORTH WAHOO CIRCLE PANAMA CITY, FL 32401

Prepared for: SCOTT BUFFALO Inspection Date: Monday, October 12, 2015 Prepared by: Randall Rands

Inspections by Randall LLC 102 Heron turn Panama City Beach, FL 32407 850 714 1955 inspectionsbyrandall.com randall@inspectionsbyrandall.com

Detailed property inspection reports - for information and your safety


January 27, 2016 Dear Scott Buffalo, RE: Report No. 1027 777 North Wahoo Circle Panama City, FL 32401 Thanks very much for choosing Inspections by Randall LLC to perform your home inspection. The inspection itself and the attached report comply with the requirements of the Standards of Practice of our national Association. This document defines the scope of a home inspection. Clients sometimes assume that a home inspection will include many things that are beyond the scope. We encourage you to read the Standards of Practice so that you clearly understand what things are included in the home inspection and report. The report has been prepared for the exclusive use of our client. No use by third parties is intended. We will not be responsible to any parties for the contents of the report, other than the party named herein . The report is effectively a snapshot of the house, recording the conditions on a given date and time. Home inspectors cannot predict future behavior, and as such, we cannot be responsible for things that occur after the inspection. If conditions change, we are available to revisit the property and update our report. The report itself is copyrighted, and may not be used in whole or in part without our express written permission. Again, thanks very much for choosing us to perform your home inspection. Sincerely, Randall Rands on behalf of Inspections by Randall LLC

Inspections by Randall LLC 102 Heron turn Panama City Beach, FL 32407 850 714 1955 inspectionsbyrandall.com randall@inspectionsbyrandall.com


Report No. 1027

SUMMARY 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

This Summary outlines potentially significant issues from a cost or safety standpoint. This section is provided as a courtesy and cannot be considered a substitute for reading the entire report. Please read the complete document. Priority Maintenance Items

Roofing OPTIONAL \ Roofing Condition: Other 3 inch plumbing vent near Valley does not appear to be extended above roof the required distance. Recommend further evaluation by licensed plumber

1. Other

2. Other

Electrical General Exterior outlet is not GFCI protected. Recommend further evaluation by licensed electrician. Location: South First Floor Porch

Providing great property inspections for every client every time

Page 1 of 59


Report No. 1027

SUMMARY 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

3. OPTIONAL \ Electrical Condition: Outlet in Kitchen wall, left of the stove, tests as open ground. Recommend further evaluation by licensed electrician. Location: Kitchen

4.

5. Providing great property inspections for every client every time

Page 2 of 59


Report No. 1027

SUMMARY 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

DISTRIBUTION SYSTEM \ Wiring - damaged or exposed Condition: Exposed in attics Electrical wiring and box in attic is not secured and wires are not covered. Wiring for air handler is loose. Recommend further evaluation by licensed electrician. Implication(s): Electric shock

6. Exposed in attics

7. wires for air handler

DISTRIBUTION SYSTEM \ Outlets (receptacles) Condition: Inoperative No power at this outlet in the master bedroom closet. Implication(s): Equipment inoperative Location: Second Floor

Providing great property inspections for every client every time

Page 3 of 59


Report No. 1027

SUMMARY 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

8. Inoperative DISTRIBUTION SYSTEM \ Smoke detectors Condition: This smoke detector is in the stairwell outside the upstairs bedroom, several feet down from the ceiling. Recommend further evaluation by a licensed electrician. Location: Second Floor Staircase

9. Wall smoke detector

10. Wall smoke detector

Providing great property inspections for every client every time

Page 4 of 59


Report No. 1027

SUMMARY 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Insulation and Ventilation ATTIC/ROOF \ Insulation Condition: Gaps or voids Recommend further evaluation by insulation contractor Implication(s): Reduced comfort | Increased heating and cooling costs Location: Attic

11. Gaps or voids

12. Gaps or voids

13. Gaps or voids

14. Gaps or voids

ATTIC/ROOF \ Roof vents Condition: Inadequate There are not any soffit vents. The roof ridge vent is not open below for ventilation, the gable vents over the two story portion are small. Implication(s): Chance of condensation damage to finishes and/or structure

Providing great property inspections for every client every time

Page 5 of 59


Report No. 1027

SUMMARY 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

15. Small gable vent ATTIC/ROOF \ Hatch Condition: Not insulated and not weatherstripped Implication(s): Reduced comfort | Increased heating and cooling costs | Chance of condensation damage to finishes and/or structure

Providing great property inspections for every client every time

Page 6 of 59


Report No. 1027

SUMMARY 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

FOUNDATION \ Interior insulation Condition: None No Insulation under floor Implication(s): Increased heating costs

16. No Insulation under floor

Providing great property inspections for every client every time

Page 7 of 59


Report No. 1027

SUMMARY 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Plumbing FIXTURES AND FAUCETS \ Toilet Condition: Loose Secondary bathroom toilet is not fastened tight to the floor, rocks back and forth. Studs are to long to allow plastic caps to be fastened. Recommend further evaluation by licensed plumber Implication(s): Sewage entering the building | Chance of water damage to contents, finishes and/or structure Location: Bathroom

Providing great property inspections for every client every time

Page 8 of 59


Report No. 1027

SUMMARY 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

17. Loose

18. Loose

This concludes the Summary section. The remainder of the report describes each of the home's systems and also details any recommendations we have for improvements. Limitations that restricted our inspection are included as well. The suggested time frames for completing recommendations are based on the limited information available during a pre-purchase home inspection. These may have to be adjusted based on the findings of specialists. Home Improvement - ballpark costs

Providing great property inspections for every client every time

Page 9 of 59


Report No. 1027

ROOFING 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description General:

Plumbing vents are new

19.

20.

General: Continuous ridge vent - but there does not appear to be any openings in the roof sheathing to allow this ridge vent to vent hot air from the attic.

21. Sloped roofing material: Asphalt shingles

Providing great property inspections for every client every time

Page 10 of 59


Report No. 1027

ROOFING 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Roofing is new - one layer over the existing wood roof sheathing

22. Asphalt shingles Sloped roof flashing material: Probability of leakage:

23. Asphalt shingles Metal

Low

Recommendations OPTIONAL \ Roofing 1. Condition: Other 3 inch plumbing vent near Valley does not appear to be extended above roof the required distance. Recommend further evaluation by licensed plumber

Providing great property inspections for every client every time

Page 11 of 59


Report No. 1027

ROOFING 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

24. Other

25. Other

Providing great property inspections for every client every time

Page 12 of 59


Report No. 1027

EXTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description General:

east elevation

26. General:

south elevation

27. General:

west elevation

Providing great property inspections for every client every time

Page 13 of 59


Report No. 1027

EXTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

28. General:

29. General:

north elevation

30. phone and cable lines do not appear to be connected to residence. access to panel restricted by new conduit

Providing great property inspections for every client every time

Page 14 of 59


Report No. 1027

EXTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

31.

32.

General: Large Pine tree on North side of residence, at this time does not appear to be affecting foundation, recommend continuing observation of tree roots causing foundation problems in the future.

33.

34.

Providing great property inspections for every client every time

Page 15 of 59


Report No. 1027

EXTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Gutter & downspout material: No gutters or downspouts

35. No gutters or downspouts Lot slope: Away from building

36. Away from building

37. Away from building

Wall surfaces: Vinyl siding

Providing great property inspections for every client every time

Page 16 of 59


Report No. 1027

EXTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

38. Vinyl siding Soffit and fascia:

soffit is vinyl, fascia and trim are aluminum

Driveway: Gravel

39. Gravel

40. Gravel

Providing great property inspections for every client every time

Page 17 of 59


Report No. 1027

EXTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Walkway: Gravel

41. Gravel Porch: Pressure treated wood Area underneath this wood porch is a concrete slab.

Providing great property inspections for every client every time

Page 18 of 59


Report No. 1027

EXTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

42. Pressure treated wood Exterior steps: Pressure-treated wood

43. Pressure-treated wood

Providing great property inspections for every client every time

Page 19 of 59


Report No. 1027

EXTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Fence: Wood Appears to be sturdy when pushed.

44. Wood

45. Wood

Providing great property inspections for every client every time

Page 20 of 59


Report No. 1027

STRUCTURE 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Configuration: Crawl space Raised wood floor with crawl space at one story area. Slab-on-grade Slab on grade at two story area Foundation material: Brick

46. Brick Floor construction:

47. Brick Wood joists, with Wood beams rest on brick piers

48. Floor construction:

Providing great property inspections for every client every time

Page 21 of 59


Report No. 1027

STRUCTURE 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Subfloor - plank

49. Subfloor - plank Exterior wall construction:

Wood frame

Roof and ceiling framing: Rafters/roof joists

50. Rafters/roof joists

51. Rafters/roof joists

Plank sheathing 1 x 6 boards

Providing great property inspections for every client every time

Page 22 of 59


Report No. 1027

STRUCTURE 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

52. Plank sheathing

Providing great property inspections for every client every time

Page 23 of 59


Report No. 1027

ELECTRICAL 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description General:

Abandoned wires and PVC pipes under the house from the older electrical and plumbing.

53. General:

54. New IC can lights, installed but insulation was not put back in place after installation

55. Service entrance cable and location:

Underground - not visible

Service size: 200 Amps (240 Volts)

Providing great property inspections for every client every time

Page 24 of 59


Report No. 1027

ELECTRICAL 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

56. 200 Amps (240 Volts)

57. 200 Amps (240 Volts)

58. 200 Amps (240 Volts) Main disconnect/service box rating: 200 Amps

Providing great property inspections for every client every time

Page 25 of 59


Report No. 1027

ELECTRICAL 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

59. 200 Amps Main disconnect/service box type and location: Breakers -exterior wall Exterior main electrical panel

60. Breakers -exterior wall

61. Breakers -exterior wall

Providing great property inspections for every client every time

Page 26 of 59


Report No. 1027

ELECTRICAL 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Number of circuits installed:

2

System grounding material and type: Copper - ground rods

62. Copper - ground rods

63. Copper - ground rods

Distribution panel rating: 200 Amps

Providing great property inspections for every client every time

Page 27 of 59


Report No. 1027

ELECTRICAL 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

64. 200 Amps

65. Electrical Permit Sticker

Auxiliary panel (subpanel) rating:

200 Amps

Auxiliary panel (subpanel) type and location: Breakers - utility room

66. Breakers - utility room

67. Breakers - utility room

Providing great property inspections for every client every time

Page 28 of 59


Report No. 1027

ELECTRICAL 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Distribution wire material and type:

Copper - non-metallic sheathed

Type and number of outlets (receptacles): Grounded - upgraded All the outlets appear to be upgraded as part of the recent remodel. Circuit interrupters: Ground Fault (GFCI) & Arc Fault (AFCI): Smoke detectors:

GFCI - kitchen

Present

Recommendations General 2. Exterior outlet is not GFCI protected. Recommend further evaluation by licensed electrician. Location: South First Floor Porch

68. OPTIONAL \ Electrical 3. Condition: Outlet in Kitchen wall, left of the stove, tests as open ground. Recommend further evaluation by licensed electrician. Location: Kitchen

Providing great property inspections for every client every time

Page 29 of 59


Report No. 1027

ELECTRICAL 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

69.

70.

DISTRIBUTION SYSTEM \ Wiring - damaged or exposed 4. Condition: Exposed in attics Electrical wiring and box in attic is not secured and wires are not covered. Wiring for air handler is loose. Recommend further evaluation by licensed electrician. Implication(s): Electric shock

71. Exposed in attics

72. wires for air handler

DISTRIBUTION SYSTEM \ Outlets (receptacles) 5. Condition: Inoperative No power at this outlet in the master bedroom closet.

Providing great property inspections for every client every time

Page 30 of 59


Report No. 1027

ELECTRICAL 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Implication(s): Equipment inoperative Location: Second Floor

73. Inoperative DISTRIBUTION SYSTEM \ Smoke detectors 6. Condition: This smoke detector is in the stairwell outside the upstairs bedroom, several feet down from the ceiling. Recommend further evaluation by a licensed electrician. Location: Second Floor Staircase

Providing great property inspections for every client every time

Page 31 of 59


Report No. 1027

ELECTRICAL 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

74. Wall smoke detector

75. Wall smoke detector

Providing great property inspections for every client every time

Page 32 of 59


Report No. 1027

HEATING 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Fuel/energy source: System type:

Electricity

Heat pump

Furnace manufacturer: Heat distribution: Efficiency:

York

Ducts and registers

High-efficiency

Approximate age:

2 years

Limitations Warm weather:

Prevented testing in heating mode

Providing great property inspections for every client every time

Page 33 of 59


Report No. 1027

COOLING & HEAT PUMP 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description General:

refrigerant lines and condensation drain Northside

76. General:

Electrical disconnect Northside

77. General:

condensation line with disconnect in electrical box Southside unit

Providing great property inspections for every client every time

Page 34 of 59


Report No. 1027

COOLING & HEAT PUMP 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

78. General:

79.

Interior air handler in laundry room

80.

Providing great property inspections for every client every time

Page 35 of 59


Report No. 1027

COOLING & HEAT PUMP 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

81. General:

83.

82. Interior air handler in one story portion is located in the attic.

84.

Providing great property inspections for every client every time

Page 36 of 59


Report No. 1027

COOLING & HEAT PUMP 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

85. Heat pump type: Air source Smaller York heat pump on south side of building serves the one story area.

86. 13 SEER rating

87. Air source

Providing great property inspections for every client every time

Page 37 of 59


Report No. 1027

COOLING & HEAT PUMP 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

88. Built in March of 2013 Air source Larger exterior compressor on north side of residence serves the two story portion of residence.

89. Air source

90. Air source

Providing great property inspections for every client every time

Page 38 of 59


Report No. 1027

COOLING & HEAT PUMP 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Manufacturer:

York unit on North side of residence

91. Compressor approximate age: 2 years Both units were manufactured in 2013 Failure probability:

Low

Supply temperature:

53 degree temperature was being supplied by both units.

Return temperature:

68 degrees return at two story area, and 70 degrees at one story area of residence.

Temperature difference:

15 to 17 degrees temperature difference

Temperature difference:

This suggests good performance.

Providing great property inspections for every client every time

Page 39 of 59


Report No. 1027

INSULATION AND VENTILATION 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Attic/roof insulation material: Glass fiber R13 unfaced batts

92. Glass fiber Attic/roof ventilation:

None found

Attic/roof air/vapor barrier:

None found

Crawlspace ventilation: Wall Vents Minimal

Limitations Inspection prevented by no access to:

Wall space

Recommendations ATTIC/ROOF \ Insulation 7. Condition: Gaps or voids Recommend further evaluation by insulation contractor Implication(s): Reduced comfort | Increased heating and cooling costs Location: Attic

Providing great property inspections for every client every time

Page 40 of 59


Report No. 1027

INSULATION AND VENTILATION 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

93. Gaps or voids

94. Gaps or voids

95. Gaps or voids

96. Gaps or voids

ATTIC/ROOF \ Roof vents 8. Condition: Inadequate There are not any soffit vents. The roof ridge vent is not open below for ventilation, the gable vents over the two story portion are small. Implication(s): Chance of condensation damage to finishes and/or structure

Providing great property inspections for every client every time

Page 41 of 59


Report No. 1027

INSULATION AND VENTILATION 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

97. Small gable vent ATTIC/ROOF \ Hatch 9. Condition: Not insulated and not weatherstripped Implication(s): Reduced comfort | Increased heating and cooling costs | Chance of condensation damage to finishes and/or structure

Providing great property inspections for every client every time

Page 42 of 59


Report No. 1027

INSULATION AND VENTILATION 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

FOUNDATION \ Interior insulation 10. Condition: None No Insulation under floor Implication(s): Increased heating costs

98. No Insulation under floor

Providing great property inspections for every client every time

Page 43 of 59


Report No. 1027

PLUMBING 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Water supply source:

Public

Service piping into building: Supply piping in building:

Galvanized steel

CPVC (Chlorinated PolyVinylChloride)

Main water shut off valve at the: East Overgrown with weeds and sand and could not get cover off

99. East Water flow and pressure:

blank note

Water flow and pressure:

Functional

Water heater fuel/energy source: Water heater type:

Conventional

Water heater manufacturer: Tank capacity:

Electric

Bradford White

50 gallons

Water heater approximate age: Waste disposal system:

1 year

Public

Exterior hose bibb: Present Located on north side near dryer exhaust

Providing great property inspections for every client every time

Page 44 of 59


Report No. 1027

PLUMBING 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

100. Present

Limitations Items excluded from a building inspection:

Water quality

Water heater relief valves are not tested

Recommendations OPTIONAL \ Plumbing 11. Condition: Shower goose neck is loose where it is coming out of wall, has excessive side to side movement when pushed. Tile also is cracked at the goose neck Location: First Floor Bathroom

Providing great property inspections for every client every time

Page 45 of 59


Report No. 1027

PLUMBING 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

101. FIXTURES AND FAUCETS \ Toilet 12. Condition: Loose Secondary bathroom toilet is not fastened tight to the floor, rocks back and forth. Studs are to long to allow plastic caps to be fastened. Recommend further evaluation by licensed plumber Implication(s): Sewage entering the building | Chance of water damage to contents, finishes and/or structure Location: Bathroom

Providing great property inspections for every client every time

Page 46 of 59


Report No. 1027

PLUMBING 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

102. Loose

103. Loose

Providing great property inspections for every client every time

Page 47 of 59


Report No. 1027

INTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Major floor finishes: Hardwood

104. Wood

105. Wood

Ceramic

106. Ceramic

Providing great property inspections for every client every time

Page 48 of 59


Report No. 1027

INTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Tile

107. Ceramic

108. Tile

109. Ceramic Major wall finishes:

Gypsum board

Providing great property inspections for every client every time

Page 49 of 59


Report No. 1027

INTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Major ceiling finishes: Windows:

Gypsum board

Simonton brand double hung

110. Windows: Single/double hung Double hung with insulated glass

111. Double hung sticker Glazing:

112. Double hung

Double

Providing great property inspections for every client every time

Page 50 of 59


Report No. 1027

INTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Exterior doors - type/material:

Wood

Doors: Inspected Doors in the one story portion are the original solid core doors. Oven type:

Conventional

Oven fuel:

Electricity

Range fuel: Electricity

113. Electricity Appliances: Refrigerator

Providing great property inspections for every client every time

Page 51 of 59


Report No. 1027

INTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

114. Refrigerator

115. Refrigerator

Dishwasher

116. Dishwasher

117. Dishwasher

Waste disposal Insinkerator Badger 5. Appears to be a new garbage disposal but cannot test it since the circuit breaker is off recommend further evaluation

Providing great property inspections for every client every time

Page 52 of 59


Report No. 1027

INTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

118. Waste disposal Microwave oven Microwave oven with interior vent Laundry facilities: Washer No washer present but hot cold water and drain installed

Providing great property inspections for every client every time

Page 53 of 59


Report No. 1027

INTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

119. Washer Laundry tub

120. Laundry tub Dryer No dryer present but electrical outlet nd exhaust vent re installed

Providing great property inspections for every client every time

Page 54 of 59


Report No. 1027

INTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

121. Dryer Vented to outside

122. Vented to outside Kitchen ventilation:

123. Vented to outside

Recirculating type

Providing great property inspections for every client every time

Page 55 of 59


Report No. 1027

INTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Bathroom ventilation: Exhaust fan Vents to exterior soffit

124. Exhaust fan Laundry room ventilation:

Window in laundry room serves as the required ventilation

Laundry room ventilation:

Clothes dryer vented to exterior

Counters and cabinets:

Granite

Providing great property inspections for every client every time

Page 56 of 59


Report No. 1027

INTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

125.

126.

Inventory Water Heater: Bradford White

127. Bradford White

128. Bradford White

Providing great property inspections for every client every time

Page 57 of 59


Report No. 1027

INTERIOR 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

129. Top of tank

130. Drain for pan

END OF REPORT

Providing great property inspections for every client every time

Page 58 of 59


Report No. 1027

REFERENCE LIBRARY 777 North Wahoo Circle, Panama City, FL SUMMARY

ROOFING

EXTERIOR

inspectionsbyrandall.com

October 12, 2015

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

The links below connect you to a series of documents that will help you understand your home and how it works. These are in addition to links attached to specific items in the report. Click on any link to read about that system.

01. ROOFING, FLASHINGS AND CHIMNEYS 02. EXTERIOR 03. STRUCTURE 04. ELECTRICAL 05. HEATING 06. COOLING/HEAT PUMPS 07. INSULATION 08. PLUMBING 09. INTERIOR 10. APPLIANCES 11. LIFE CYCLES AND COSTS 12. SUPPLEMENTARY Asbestos Radon Urea Formaldehyde Foam Insulation (UFFI) Lead Carbon Monoxide Mold Household Pests Termites and Carpenter Ants

13. HOME SET-UP AND MAINTENANCE 14. MORE ABOUT HOME INSPECTIONS

Providing great property inspections for every client every time

Page 59 of 59