Page 1

DIRIS A10

Multifunction meters

NEW

Modular multi function meter ‹ Function The DIRIS A10 is a multi function meter for measuring electrical values in low voltage networks in modular format. It allows all electrical parameters to be displayed and the measurement, energy metering and communication functions to be used. In addition, the DIRIS A10 has a function for correcting errors in CT connections. It also allows variations in temperature to be detected thanks to its internal temperature measurement function.

‹ Conformity to standards • IEC 62053-22 class 0.5S • IEC 62053-23 class 2 • IEC 61557-12

site_321_a

Multi-function meter • Current - instantaneous: I1, I2, I3, In - maximum average: I1, I2, I3, In • Voltages & frequency - instantaneous: U1, U2, U3, U12, U23, U31, F • Power - instantaneous: 3P, ΣP, 3Q, ΣQ, 3S, ΣS - maximum average: ΣP, ΣQ, ΣS • Power factor - instantaneous: 3PF, ΣPF • Internal temperature

DIRIS A10

RS485

DIRIS A10

485 232

PC PLC

Metering • Active energy: + kWh • Reactive energy: + kvarh • Hours:

Main meter panel

Currents per phase curve

CONTROL VISION software

diris_808_c_1_gb_cat

diris_791_b_1_cat

‹ Applications

Events Alarms on all electrical values

Harmonic analysis • Total harmonic distortion (level 51) - Currents: thd I1, thd I2, thd I3 - Phase-to-neutral voltage: thd U1, thd U2, thd U3 - Phase to phase voltage: thd U12, thd U23, thd U31

Communications (1) RS485 (JBUS/MODBUS) digital

Dual tariff function Selection of one out of 2 billing tariffs

Input • Remote control

Output • Remote comand of apparatus • Alarm report • Pulse report

(1) Available as an option (see the following pages).

366

General Catalogue 2011-2012 SOCOMEC


Multifunction meters

DIRIS A10

diris_791x_b_1_cat

‹ Front panel

2 3 4 5 6 7

1. Backlit LCD screen. 2. Direct access key for currents (instant and maximum) and current THD. 3. Direct access key for voltages, frequency and voltage THD. 4. Direct access key for active, reactive and apparent power (instantaneous and max. values) and power factor. 5. Direct access key for energies and hour meter. 6. Pushbutton for currents, temperatures and CT setup wiring correction. 7. Metrological LED.

1

‹ Case 64 44

72

DIRIS A 10 TEST

45

90

diris_809_a_1_x_cat

I V F P PF E

OK

°C

PROG

C=0,1Wh/imp

Type Number of optional modules Dimensions W x H x D Case protection index Front protection rating Display type Voltage and other connection section Connection cross-section of others Weight

Modular 4 72 x 90 x 64 mm 30 52 LCD 4 mm2 2.5 mm2 205 g (4825 0010) - 215 g (4825 0011)

‹ Electrical characteristics

Current measurement on high-impedance inputs (TRMS)

Energy accuracy

Via CT primary Via CT secondary Measurement range Input consumption Measurement updating period Accuracy Sustained overload intermittent overload

Active (according to IEC 62053-22) Reactive (according to IEC 62053-23)

9 999 A 5A 0 … 11 kA 0.6 VA 1s 0.2 % 6A 10 In for 1 s

class 0.5 S class 2

Auxiliary power supply

Alternating voltage AC tolerance Frequency Consumption

220 … 277 VAC ± 15 % 50 / 60 Hz < 3 VA

Voltage measurements (TRMS)

Direct measurement between phases Direct measurement between phase and neutral Input consumption Measurement updating period Accuracy Sustained overload

50 … 500 VAC 28 … 289 VAC ≤ 0.1 VA 1s 0.2 % 800 VAC

1s 0.5 %

Operating conditions

Frequency measurement

Measurement range Measurement updating period Accuracy

45 … 65 Hz 1s 0.1 %

SOCOMEC General Catalogue 2011-2012

1 20 / 30 VDC - 0.5 A - 10 VA ≤ 108

Communication

Link Type Protocol JBUS/MODBUS® speed

Power factor measurement

Measurement updating period Accuracy

Number Type Max. number of operations

1s 0.5 %

Power measurement

Measurement updating period Accuracy

Digital output (pulses or on/off)

Operating temperature Storage temperature Relative humidity

RS485 2 … 3 half duplex wires JBUS/MODBUS® in RTU mode 1400 … 38400 bauds

- 10 … + 55 °C - 20 … + 70 °C 85 %

367


â&#x20AC;š DIRIS A10 - Connection Low voltage balanced network Recommandation: - For IT earthing systems, it is recommended that the CT secondary is not connected to earth. - When disconnecting the DIRIS, the secondaries of each current transformer must be short-circuited. This operation can be carried out automatically from a product in the SOCOMEC catalogue, PTI: consult us. - It is recommended that the earthing point for the DIRIS A10 and the current transformer secondaries should not earthed at the same time.

3/4 wires with 1 CT

Single phase 1 = Fus. 0.5 A gG / 0.5 A class CC

1 = Fus. 0.5 A gG / 0.5 A class CC

N L1 L2 L3

P1 S1

1 = Fus. 0.5 A gG / 0.5 A class CC

P1 S1

P1

L1 N

S2

S1

1

1

1

V1 V2 V3 VN

S1 S2 S1 S2 S1 S2 I1

I2

I3

V1 V2 V3 VN

diris_812_a_1_gb_cat

1

S2

diris_811_a_1_gb_cat

diris_810_a_1_gb_cat

1

Two phase

S1 S2 S1 S2 S1 S2 I1

I2

I3

L1 L2

S2

1

V1 V2 V3 VN

S1 S2 S1 S2 S1 S2 I1

I2

I3

Low voltage unbalanced network

3/4 wires with 3 CTs

3 wires with 2 CTs 1 = Fus. 0.5 A gG / 0.5 A class CC

1 = Fus. 0.5 A gG / 0.5 A class CC

S2

S1

P1

S1

P1

1

L1 L2 L3

P1 S1

1

1

1

I3

V1 V2 V3 VN

diris_815_a_1_gb_cat

I2

diris_814_a_1_gb_cat

diris_813_a_1_gb_cat

S1 S2 S1 S2 S1 S2 I1

S1

S2

S2

S1

1

V1 V2 V3 VN

P1

L1 L2 L3

S2

S2

S1

1

1 = Fus. 0.5 A gG / 0.5 A class CC P1

N L1 L2 L3

P1

1

3 wires with 2 CTs

S1 S2 S1 S2 S1 S2 I1

I2

I3

Use of 2 CTs reduces by 0.5% the accuracy of the phase, whose current is worked out by vector calculation.

1

1

V1 V2 V3 VN

S1 S2 S1 S2 S1 S2 I1

I2

I3

Use of 2 CTs reduces by 0.5% the accuracy of the phase, whose current is worked out by vector calculation.

Additional information AC & DC auxiliary power supply

Communication via RS485 link

220/ 277 VAC (IEC)

0V RS485

+

diris_821_a_1_x_cat

diris_820_a_1_x_cat

LIYCY-CY

20

22 AUX

It is recommended that the auxiliary power supply be protected by the use of 500 mA gG fuses.

368

General Catalogue 2011-2012 SOCOMEC


Multifunction meters

DIRIS A10

diris_816_a_1_x_cat

‹ Terminals

12

14

16

2

20

V1

V2

V3

VN

A

22 U

X

1

3

5

7

9

18

11

S1 S2 S1 S2 S1 S2 I1

I2

I3

DIRIS A10

S1 - S2: current inputs. AUX: auxiliary power supply Us. V1, V2, V3 & VN: voltage inputs.

0V + RS485 DIRIS A10

RS485 link.

Input

4

6

OUT 1 DIRIS A10

4 - 6: output n°1

diris_818_a_1_x_cat

1 3 15 17

Output

diris_819_b_1_x_cat

diris_816_a_1_x_cat

Communication (option)

8 10 IN 1 DIRIS A10

8 - 10: input n°1

diris_791_b_1_cat

‹ References

Basic device Description DIRIS A10 (grey colour available on request) DIRIS A10 with JBUS/MODBUS communication via RS485 (grey colour available on request)

Description of accessories Fuse combination switches for the protection of voltage inputs (type RM) 3 poles Fuse combination switches for the protection of the auxiliary supply (type RM) 1 pole + neutral Fuses type gG 10x38 0.5 A Current transformers range

DIRIS A10 Reference 4825 0010 4825 0011

To be ordered by multiple 4 6 10

Reference 5601 0018 5601 0017 6012 0000 See page 334

Services and Technical assistance Our expertise extends to a complete offer of services like commissioning installation audit, training, maintenance and project engineering.

SOCOMEC General Catalogue 2011-2012

369


DIRIS A20

Multifunction meters

diris_750_a_1_cat

NEW

‹ Function DIRIS A20 are measurement units which ensure the user has access to all the measurements required for successfully carrying out energy efficiency projects and ensuring the electrical distribution is monitored. All this information can be used and analysed remotely using the CONTROL VISION software.

‹ Conformity to standards • IEC 61557-12 • IEC 62053-22 class 0.5S • IEC 62053-23 class 2

370

diris_576_d_1_gb_cat

Monitoring and managing energy for low voltage electrical installations

Multi-function meter • Current - instantaneous: I1, I2, I3, In - maximum average: I1, I2, I3, In • Voltages & RS485 DIRIS A20 DIRIS A20 frequency - instantaneous: 485 Main meter panel 232 U1, U2, U3, U12, PLC U23, U31, F • Power - instantaneous: 3P, PC Currents per phase ΣP, 3Q, ΣQ, 3S, ΣS curve - maximum average: ΣP, ΣQ, ΣS • Power factor CONTROL VISION software - instantaneous: 3PF, ΣPF Events(1) Metering Alarms on all electrical • Active energy: + kWh values • Reactive energy: + kvarh • Hours: Communications(1) RS485 (JBUS/MODBUS) Harmonic analysis digital • Total harmonic distortion (level 51) Output(1) - Currents: thd I1, thd I2, • Remote comand of thd I3 apparatus - Phase-to-neutral voltage: • Alarm report thd U1, thd U2, thd U3 • Pulse report - Phase to phase voltage: as an option thd U12, thd U23, thd U31 (1) Available (see the following pages).

appli_387_a

‹ Applications

General Catalogue 2011-2012 SOCOMEC


Multifunction meters

DIRIS A20 ‹ Front panel

diris_743x_a_2_cat

1. Backlit LCD screen. 2. Direct access key for currents (instantaneous and max. values), current THD and set up wiring correction. 3. Direct access key for voltages, frequency and voltage THD. 4. Pushbutton for active, reactive, and apparent power (instantaneous and max. values) and power factor. 5. Direct access key for energies and hour meter.

1

2

3

4

5

‹ Case 92

diris_577_c_1_x_cat

96

DIR IS

92

A2 0

I 5

/TES T

V

F

4

P

PF

OK

+ 0.8 - 0.0

E

60

+ 0.8 - 0.0

Type Dimensions W x H x D Case protection index Front protection rating Display type Terminal blocks type Voltage and other connection section Current connection section Weight

Panel mounting 96 x 96 x 60 mm IP30 IP52 LCD fixed or pull-out 0.2 … 2.5 mm2 0.5 … 6 mm2 400 g

20

PR OG

96

‹ Plug-in modules 1 output assignable to: • Pulses: configurable (type, weight, time) in kWh or kvarh • Monitoring: 3I, In, 3V, 3U, F, ΣP, ΣQ, ΣS, ΣPFL/C, THD 3I, THD 3V, THD 3U and timer • Control of apparatus

diris_773_a_1_cat

diris_445_a_1_cat

1 Output

diris_447_a_1_cat

Communication RS485 link with JBUS / MODBUS protocol (speed up to 38400 bauds)

‹ Accessories

SOCOMEC General Catalogue 2011-2012

Mounting kit for 144 x 96 mm cut out plate

diris_718_b_1_cat

IP65 protection

diris_720_a_2_cat

trafo_077_b_2_cat

trafo_024_a_2_cat

Current transformer (see page 334)

371


‹ DIRIS A20 - Electrical characteristics

Current measurement on high-impedance inputs (TRMS) Via CT primary 9 999 A Via CT secondary 5A Measurement range 0 … 11 kA Input consumption 0.6 VA Measurement updating period 1s Accuracy 0.2 % Sustained overload 6A Intermittent overload 10 In for 1 s Voltage measurements (TRMS) Direct measurement between phases Direct measurement between phase and neutral Input consumption Measurement updating period Accuracy Sustained overload

50 … 500 VAC 28 … 289 VAC ≤ 0.1 VA 1s 0.2 % 800 VAC

Power measurement Measurement updating period Accuracy

1s 0.5 %

Power factor measurement Measurement updating period Accuracy

1s 0.5 %

Frequency measurement Measurement range Measurement updating period Accuracy

45 … 65 Hz 1s 0.1 %

Energy accuracy Active (according to IEC 62053-22) Reactive (according to IEC 62053-23)

class 0.5 S class 2

Auxiliary power supply Alternating voltage AC tolerance Direct voltage DC tolerance Frequency Consumption

110 … 400 VAC ± 10 % 120 … 350 VDC ± 20 % 50 / 60 Hz 10 VA

Pulse or alarm output Number Type Max. number of operations

1 100 VDC - 0.5 A - 10 VA ≤ 108

Communication Link Type Protocol JBUS/MODBUS® speed

RS485 2 … 3 half duplex wires JBUS/MODBUS® in RTU mode 1400 … 38400 bauds

Operating conditions Operating temperature Storage temperature Relative humidity

- 10 … + 55 °C - 20 … + 85 °C 95 %

‹ Terminals

diris_578_a_1_x_cat

S1 - S2: current inputs.

V1

V2

V3

VN

A U X

I1

I2

I3

AUX: auxiliary power supply Us. V1, V2, V3 & VN: voltage inputs.

DIRIS A20

Output or alarm module

Communication module

0V -

+

1

diris_580_b_1_x_cat

diris_579_a_1_x_cat

S1 S2 S1 S2 S1 S2

0n RS485

R = 120

DIRIS A20

RS485 link. R = 120 Ω: internal resistance for the RS485 link.

1 8 19 OUT 1

DIRIS A20

18 - 19: output n°1

‹ Connection Recommendation: - For IT earthing systems, it is recommended that the CT secondary is not connected to earth. - When disconnecting the DIRIS, the secondaries of each current transformer must be short-circuited. This operation can be carried out automatically from a product in the SOCOMEC catalogue, PTI: consult us.

Low voltage balanced network 3/4 wires with 1 CT

Single phase

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class

S1

1

V1 V2 V3 VN

P1

L1 N

S2

S1

1

1

S1 S2 S1 S2 S1 S2 I1

I2

I3

V1 V2 V3 VN

S1 S2 S1 S2 S1 S2 I1

I2

I3

diris_394_d_1_gb_cat

1

S2

P1

diris_393_d_1_gb_cat

diris_392_d_1_gb_cat

1

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class

N L1 L2 L3

P1 S1

Two phase

L1 L2

S2

1

V1 V2 V3 VN

S1 S2 S1 S2 S1 S2 I1

I2

I3

Use of 1 CT reduces by 0.5% the accuracy of the phases, the current of which is worked out by vector calculation.

372

General Catalogue 2011-2012 SOCOMEC


Multifunction meters

DIRIS A20

Low voltage unbalanced network 3/4 wires with 3 CTs

3 wires with 2 CTs 1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class

N L L L

P1 S2 P1

P1

1

1

V1 V2 V3 VN

S1 S2 S1 S2 S1 S2 I1

I2

S1

L1 L2 L3

P1 S1

S2

S2

S1

I3

diris_396_d_1_gb_cat

diris_395_d_1_gb_cat

1

S2

S1

P1

L1 L2 L3

S2

S1

1

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class

P1

1

1

V1 V2 V3 VN

1

S1 S2 S1 S2 S1 S2 I1

I2

I3

Use of 2 CTs reduces by 0.5% the accuracy of the phase, whose current is worked out by vector calculation.

diris_397_d_1_gb_cat

S1

3 wires with 2 CTs

1

1

V1 V2 V3 VN

S1 S2 S1 S2 S1 S2 I1

I2

I3

Use of 2 CTs reduces by 0.5% the accuracy of the phase, whose current is worked out by vector calculation.

Additional information AC & DC auxiliary power supply

Communication via RS485 link

110 / 400 VAC (IEC) 120 / 350 VDC (IEC)

0V -

+ ON

RS485

diris_501_d_1_gb_cat

diris_398_c_1_x_cat

LIYCY-CY

A U X

It is recommended that the auxiliary power supply be protected by the use of 500 mA gG fuses.

diris_750_a_1_cat

‹ References

Basic device Auxiliary power supply Us 110 … 400 VAC / 180 … 350 VDC

DIRIS A20 Reference 4825 0200

Options Plug-in modules 1 output RS485 JBUS / MODBUS® communication

Reference 4825 0080 4825 0082

Accessories Description of accessories IP65 protection Panel mounting kit for a 144 x 96 mm cutout Fuse combination switches for the protection of voltage inputs (type RM) 3 poles Fuse combination switches for the protection of the auxiliary supply (type RM) 1 pole + neutral Fuses type gG 10x38 0.5 A Current transformers range

To be ordered by multiple 1 1 4 6 10

Reference 4825 0089 4825 0088 5601 0018 5601 0017 6012 0000 See page 334

Services and Technical assistance Our expertise extends to a complete offer of services like commissioning installation audit, training, maintenance and project engineering.

SOCOMEC General Catalogue 2011-2012

373


DIRIS A40 / A41

Multifunction meters

NEW

 Applications

Ethernet

DIRIS A41

DIRIS A40

diris_744_a_1_cat

DIRIS A40

DIRIS A40

RS485

 Function The DIRIS A40 and A41 are multifunction meters which ensure the user has access to all the measurements required for energy efficiency projects and monitoring of electrical distribution. All this information can be used and analysed remotely using the CONTROL VISION software.

 Conformity to standards • IEC 61557-12 • IEC 62053-22 class 0.5S • IEC 62053-23 class 2

2

diris_581_e_1_gb_cat

Monitoring and managing energy for high/low voltage electrical installations

CONTROL VISION software

Currents per phase curve

PLC

Multi measurement • Current - instantaneous: I1, I2, I3, In, Isystem - average/maximum average: I1, I2, I3, In • Voltages & frequency - instantaneous: U1, U2, U3, U12, U23, U31, F, Vsystem, Usystem - average/maximum average: U1, U2, U3, U12, U23, U31, F • Power - instantaneous: 3P, ΣP, 3Q, ΣQ, 3S, ΣS - average/maximum average: ΣP, ΣQ, ΣS - predictive: (ΣP), (ΣQ), (ΣS) • Power factor - instantaneous: 3PF, ΣPF - average/maximum average: ΣPF • Temperatures(1) - internal - external via 3 PT100 sensors Metering • Active energy:+/- kWh • Reactive energy:+/- kvarh • Apparent energy:kVAh • Hours: Harmonic analysis • Harmonic distortion rate - Currents: thd I1, thd I2, thd I3, thd In - Phase-to-neutral voltage: thd U1, thd U2, thd U3 - Phase to phase voltage: thd U12, thd U23, thd U31

• Individual up to level 63 - Currents: HI1, HI2, HI3, HIn - Phase-to-neutral voltage: HU1, HU2, HU3, - Phase to phase voltage: HU12, HU23, HU31 Load curves(1) • Active and reactive power: ΣP+/-; ΣQ+/• Voltages & frequency: U1, U2, U3, U12, U23, U31, F Events(1) • Alarms on all electrical values. Communications(1) • Analogues 0/4- 20 mA • Digital RS485 (Jbus/Modbus & Profibus-DP) • Ethernet (modbus/TCP or Jbus/ Modbus RTU over TCP and Web server) • Ethernet with RS485 gateway Jbus/Modbus RTU over TCP Inputs / Outputs(1) • Pulse metering • Remote control/command • Alarm report • Pulse report (1) Available as an option (see the following pages).

General Catalogue 2012-2013 SOCOMEC

appli_384_b

Main meter panel

PC


Multifunction meters

DIRIS A40 / A41 ÂÂ Front panel

diris_744x_a_1_cat

1. Backlit LCD screen. 2. Pushbutton for currents and setup wiring correction 3. Pushbutton for voltages and frequency. 4. Pushbutton for active, reactive, and apparent power and power factor. 5. Pushbutton for maximum and average current and power values. 6. Pushbutton for harmonics values. 7. Pushbutton for pulse, hours and electrical energy meters.

1

2 3

4

5

6

7 Pulse outputs diris_445_a_1_cat

ÂÂPlug-in modules

2 configurable pulse outputs (type, weight and run) on ± kWh, ±kvarh and kVAh

diris_447_a_1_cat

JBUS / MODBUS® communication RS485 link with JBUS / MODBUS® protocol (speed up to 38400 bauds).

PROFIBUS® DP communication SUB-D9 link with PROFIBUS® DP protocol (speed up to 12 Mbauds).

Ethernet communication • Ethernet link with MODBUS/TCP or JBUS/MODBUS RTU over TCP • Embedded Ethernet Webserver software

diris_776_a_1_cat

diris_777_a_1_cat

diris_773_a

diris_775_a_1_cat

DIRIS® A40

Ethernet communication with RS485 JBUS/MODBUS gateway • Ethernet link with MODBUS/TCP or JBUS/MODBUS RTU over TCP • Connection of 1 to 247 RS485 JBUS/MODBUS slaves • Embedded Ethernet Webserver software

DIRIS® A41

diris_448_a_1_cat

Analogue outputs A maximum of 2 modules may be connected, that is 4 analogue outputs. 2 outputs assignable to: 3I, In, 3V, 3U, F, ±ΣP, ±ΣQ, ΣS, ΣPFL/C, I sys, Vsys, Usys, Ppred, Q pred, Spred, internal T°C, T°C 1, T°C 2, T°C 3 and to 17 VDC power supply

diris_774_a

diris_449_a_1_cat

2 inputs - 2 outputs A maximum of 3 modules may be connected, giving 6 inputs. 2 outputs assignable to: - monitoring: 3I, In, 3V, 3U, F, ±ΣP, ±ΣQ, SS, ΣPFL/C, THD 3I, THD In, THD 3V, THD 3U, Ppred, Qpred, Spred, internal T°C, T°C 1, T°C2, T°C3 and hour meter, - remote control, - timed remote control.

diris_682_a_1_cat

Memory • Storing up to a maximum of 62 days of P+, P-, Q+, Q- with an internal or external synchronisation signal of 5, 8, 10, 15, 20, 30 and 60 minutes. • Storing of 10 hour-dated last alarms. • Storing of the last minimum and maximum instantaneous values for 3U, 3V, 3I, In, F, ΣP±, ΣQ±, ΣS, THD 3U, THD 3V, THD, 3U, THD, 3V, THD, 3I, THD In. • Storing of 3U, 3V and F average values based on synchronisation function (maximum 60 days).

diris_747_a_2_cat

Temperature

SOCOMEC General Catalogue 2012-2013

Temperature indication • Internal • External sensor PT 100 (T°C 1) • External sensor PT 100 (T°C 2) • External sensor PT 100 (T°C 3)

3


ÂÂDIRIS A40 / A41 - Accessories Current transformer

IP65 protection

Mounting kit for 144 x 96 mm cut out plate

diris_718_b_1_cat

trafo_024_a_2_cat

trafo_077_b_2_cat

diris_720_a_2_cat

(see page 334)

ÂÂTerminals DIRIS A40

diris_569_a_1_x_cat

S1 - S2: current inputs

V1

V2

V3

VN

A U X

S1 S2 S1 S2 S1 S2 I1

I2

AUX: auxiliary power supply Us V1- V2 - V3 - VN: voltage inputs

I3

DIRIS A40

DIRIS A41

V2

V3

VN

S1 S2 S1 S2 S1 S2 S1 S2 I1

I2

I3

AUX: auxiliary power supply Us V1- V2 - V3 - VN: voltage inputs

IN

DIRIS A41

0V -

+

1 0n R = 120

RS485

DIRIS A40 / A41

Pulse output module

1

2

OUT 1

3

Analogue output module

4 diris_573_a_1_x_cat

Communication module

diris_571_a_1_x_cat

A U X

diris_572_a_1_x_cat

diris_570_a_1_x_cat

S1 - S2: current inputs

V1

OUT 2

DIRIS A40 / A41

5

6

7

8

+ - + 0/4-20 mA 0/4-20 mA OUT 1 OUT 2

DIRIS A40 / A41

1 - 2: pulse output n°1. 3 - 4: pulse output n°2.

5 - 6: analogue output n°1. 7 - 8: analogue output n°2.

2 inputs / 2 outputs module

Memory module

Temperature module

diris_574_b_1_x_cat

OUT 1 A-Cd

OUT 2 A-Cd

1 3 14 15 16 -

+

-

IN 1

+

IN 2

19 20 21 22 23 24 25 26

17 18 +

-

diris_753_a_1_gb_cat

9 10 11 12

diris_683_a_1_x_cat

RS485 link. R = 120 Ω: internal resistance for the RS485 link.

IN synchro

DIRIS A40 / A41

17 - 18: synchronisation input.

9 - 10: relay output n°1. 11 - 12: relay output n°2. 13 - 14: opto input n°1. 15 - 16: opto input n°2.

sensor 2

27 28 29 30 sensor 3

DIRIS A40/A41 Sensor 1 19: Red 20: Red 21: White 22: White

DIRIS A40 / A41

Ethernet Module

sensor 1

Sensor 2 23: Red 24: Red 25: White 26: White

Sensor 3 27: Red 28: Red 29: White 30: White

Ethernet module + RS485 JBUS /

4

10 BASE T 100 BASE T RJ45

DIRIS A40/A41

diris_751_b_1_gb_cat

diris_752_a_1_x_cat

MODBUS gateway

10 BASE T 100 BASE T RJ45

0V -

+

RS485 gateway

DIRIS A40/A41

General Catalogue 2012-2013 SOCOMEC


Multifunction meters

DIRIS A40 / A41 ÂÂElectrical characteristics

Current measurement on insulated inputs (TRMS) Via CT primary 10 000 A Via CT secondary 1 or 5 A Measurement range 0 … 11 kA Input consumption ≤ 0.1 VA Measurement updating period 1s Accuracy 0.2 % Sustained overload 6A intermittent overload 10 In for 1 s

2 inputs / 2 outputs module: Outputs (alarms / control) Number of relays 2(1) Type 250 VAC - 5 A - 1150 VA 2 inputs / 2 outputs module: Phototransistor inputs Number 2(1) Power supply 10 … 30 VDC Minimal signal width 10 ms Minimum length between 2 impulses 18 ms Type phototransistor

Voltage measurements (TRMS) Direct measurement between phases Direct measurement between phase and neutral VT primary VT secondary Frequency Input consumption Measurement updating period Accuracy Sustained overload

50 … 700 VAC 28 … 404 VAC 500 000 VAC 60, 100, 110, 173, 190 VAC 50 / 60 Hz ≤ 0.1 VA 1s 0.2 % 760 VAC

Current-voltage product Limitation for 1A CT Limitation for 5A CT

10 000 000 10 000 000

Power measurement Measurement updating period Accuracy

1s 0.5 %

Power factor measurement Measurement updating period Accuracy

1s 0.5 %

PROFIBUS-DP communication module Link SUB-D9 Protocol PROFIBUS® DP 9.8 kbauds … 12 Mbauds PROFIBUS® speed

Frequency measurement Measurement range Measurement updating period Accuracy

45 … 65 Hz 1s 0.1 %

Ethernet Communication Module Connectique RJ45 Speed 10 base T / 100 base T Protocol MODBUS TCP or JBUS/MODBUS RTU over TCP

Energy accuracy Active (according to IEC 62053-22) Reactive (according to IEC 62053-23)

class 0.5 S class 2

Auxiliary power supply Alternating voltage AC tolerance Direct voltage DC tolerance Frequency Consumption

110 … 400 VAC ± 10 % 120 … 350 VDC / 12 … 48 VDC ± 20 % / - 6 … + 20 % 50 / 60 Hz ≤ 10 VA

Module temperature (inputs) Type Connection Dynamic Accuracy Maximum length

PT100 2, 3 or 4 wires - 20°C ... 150°C +/- 1 digit 300 cm

Operating conditions Operating temperature Storage temperature Relative humidity

- 10 … + 55 °C - 20 … + 85 °C 95 %

Pulse outputs module Number of relays Type Max. number of operations

2 100 VDC - 0.5 A - 10 VA ≤ 108

Analogue output module Number of outputs Type Scale Load resistance Maximum current

2(2) insulated 0 / 4 … 20 mA 600 Ω 30 mA

JBUS / MODBUS communication module Link RS485 Type 2 … 3 half duplex wires Protocol JBUS/MODBUS® in RTU mode ® 1400 … 38400 bauds JBUS/MODBUS speed

(1) Max. 3 modules / Diris. (2) Max. 2 modules / DIRIS.

ÂÂ Case 92

diris_582_d_1_x_cat

96

DIR IS

Type Dimensions W x H x D Case protection index Front protection rating Display type Terminal blocks type Voltage and other connection section Current connection section Weight

+ 0.8 - 0.0

92

A4

0

60

Panel mounting 96 x 96 x 60 mm IP30 IP52 LCD fixed or pull-out 0.2 … 2.5 mm2 0.5 … 6 mm2 400 g

+ 0.8 - 0.0

35

96

SOCOMEC General Catalogue 2012-2013

5


ÂÂDIRIS A40 / A41 - Connections Recommendation: when disconnecting the DIRIS, the secondaries of each current transformer must be short-circuited. This operation can be carried out automatically by a product in the SOCOMEC catalogue, PTI: consult us. In TNC neutral system it is recommanded to use functional earth module.

Low voltage balanced network for DIRIS A40 3/4 wires with 1 CT

Single phase

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class P1 L1 S1 S2 N

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class N P1 L1 S1 S2 L2 L3

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class P1 L1 S1 S2 L2

1

1

S1 S2 S1 S2 S1 S2

V1 V2 V3 VN

I1

I2

I3

1

V1 V2 V3 VN

S1 S2 S1 S2 S1 S2 I1

I2

I3

diris_394_d_1_gb_cat

1

diris_393_d_1_gb_cat

diris_392_d_1_gb_cat

1

Two phase

1

V1 V2 V3 VN

S1 S2 S1 S2 S1 S2 I1

I2

I3

Use of 1 CT reduces by 0.5% the accuracy of the phases, the current of which is worked out by vector calculation.

Low voltage unbalanced network for DIRIS A40 3/4 wires with 3 CTs

3 wires with 2 CTs

1

1

V1 V2 V3 VN

diris_396_d_1_gb_cat

diris_395_d_1_gb_cat

1

S1 S2 S1 S2 S1 S2 I1

I2

I3

1

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class P1 L1 S1 P1 L2 S1 S2 L3

1

1

V1 V2 V3 VN

S1 S2 S1 S2 S1 S2 I1

I2

I3

diris_397_d_1_gb_cat

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class N P1 L1 S1 S2 L2 P1 L3 S1 S2 1

3 wires with 2 CTs

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class P1 L1 S2 S1 L2 P1 L3 S2 S1

Use of 2 CTs reduces by 0.5% the accuracy of the phase, whose current is worked out by vector calculation.

1

1

V1 V2 V3 VN

S1 S2 S1 S2 S1 S2 I1

I2

I3

Use of 2 CTs reduces by 0.5% the accuracy of the phase, whose current is worked out by vector calculation.

Low voltage unbalanced network for DIRIS A41 4 wires with 4 CTs

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class P1 N P1 S1 L1 S1 S2 L2 P1 L3 S2 S1

diris_575_b_1_gb_cat

1

1

1

V1 V2 V3 VN S1 S2 S1 S2 S1 S2 S1 S2 I1

I2

I3

IN

Additional information Communication via RS485 link

Voltage transformer for HV networks

AC & DC auxiliary power supply

L1 L2 L3

110 / 400 VAC (IEC) 120 / 350 VDC (IEC)

+ ON

RS485

V1 V2 V3 N

diris_400_g_1_gb_cat

0V -

diris_399_b_1_x_cat

diris_398_c_1_x_cat

LIYCY-CY

A U X

It is recommended that the auxiliary power supply be protected by the use of 500 mA gG fuses.

6

General Catalogue 2012-2013 SOCOMEC


Multifunction meters

DIRIS A40 / A41

diris_744_a_1_cat

 References

Basic device Auxiliary power supply Us 110 ... 400 VAC / 120 ... 350 VDC 12 ... 48 VDC

DIRIS A40 Reference 4825 0201 4825 1201

DIRIS A41 with CT on the neutral Reference 4825 0202 4825 1202

Reference 4825 0090 4825 0092 4825 0093 4825 0094 4825 0205 4825 0097 4825 0203 4825 0204 4825 0206 4825 0087

Reference 4825 0090 4825 0092 4825 0093 4825 0094 4825 0205 4825 0097 4825 0203 4825 0204 4825 0206 4825 0087

Options Plug-in modules(1) Pulse outputs Sub D9 JBUS/MODBUS® communication Analogue outputs 2 inputs / 2 outputs RS485 PROFIBUS®DP communication Memory Ethernet communication (embedded Ethernet Webserver software) Ethernet communication + RS485 gateway JBUS/MODBUS (embedded Ethernet Webserver software) Temperature inputs Functional Earth Accessories Description of accessories IP65 protection Panel mounting kit for a 144 x 96 mm cutout Fuse combination switches for the protection of voltage inputs (type RM) 3 poles Fuse combination switches for the protection of the auxiliary supply (type RM) 1 pole + neutral Fuses type gG 10x38 0.5 A Current transformers range

To be ordered in multiples of 1 1 4 6 10

Reference 4825 0089 4825 0088 5601 0018 5601 0017 6012 0000 See page 334

To be ordered in multiples of 1 1 4 6 10

Reference 4825 0089 4825 0088 5601 0018 5601 0017 6012 0000 See page 334

(1) Ease of integration for additional functions (maximum 4 on A40 and 3 on A41).

Services and Technical assistance Our expertise extends to a complete offer of services like commissioning installation audit, training, maintenance and project engineering.

 Ethernet Webserver

The Webserver is a software, based on HTML pages, that is embedded in the optional Ethernet module of the DIRIS. Access is available using an internet browser and entering the IP address of the DIRIS. It enables viewing the main electrical values, diagnostic analysis, device monitoring and setting the main parameters of the DIRIS multifunction meter.

diris_869_a_1_gb_cat

Panels for viewing all average and instantaneous electrical values.

Viewing of average and instantaneous energy consumptions.

Device setting

Alarms

diris_868_a_1_gb_cat

Use

Power and Energy

diris_870_a_1_gb_cat

diris_776_a_1_cat

diris_867_a_1_gb_cat

Instantaneous report of measurements

The last 10 alarms are date and time registered. Duration and limit reached (low limit value / high limit value), as well as the related output alarm number are also displayed. Data can be extracted in *.csv format.

SOCOMEC General Catalogue 2012-2013

7


DIRIS A60

Multifunction meters

NEW

 Applications

Ethernet

DIRIS A60

DIRIS A40

DIRIS A40

DIRIS A40

RS485

Main meter panel

Events monitoring and managing energy for high/low voltage electrical installations  Function DIRIS A60 is a measurement station which takes over all the functions of DIRIS A40 and which is enhanced by a history of harmful events for installation. A graphic representation of these harmful events is associated and provided to the user. All this information can be used and analysed remotely using free quality measurement software that can be downloaded on the site www.socomec.com.

 Conformity to standards • IEC 61557-12 • IEC 62053-22 class 0.5 S • IEC 62053-23 class 2

2

CONTROL VISION software

In addition to the functions of the DIRIS A40, the DIRIS A60 also: • shows the current and voltage unbalance • shows the tangent phi • stores the load curves (50 days ith an interval of 10 minutes) for: - Active, reactive and apparent power: ΣP+/-; ΣQ+/-, ΣS • detects and stores the last 40 events concerning: - overvoltage - voltage dips - cut-offs - overcurrent For each stored event, the DIRIS A60 records the relevant RMS 1/2 interval curves for the voltages V1, V2, V3, U12, U23, U31 and the currents I1, I2, I3, In, giving a total of 400 curves. Other functions: Multi-function meter • Current - instantaneous: I1, I2, I3, In, Isystem, - average/maximum average: I1, I2, I3, In, - unbalance: I unb. • Voltages & frequency - instantaneous: U1, U2, U3, U12, U23, U31, F, Vsystem, Usystem - average/maximum average: U1, U2, U3, U12, U23, U31, F - unbalance: U unb. • Power - instantaneous: 3P, ΣP, 3Q, ΣQ, 3S, ΣS - maximum average: ΣP, ΣQ, ΣS - predictive: ΣP, ΣQ, ΣS. • Power factor - FP, ΣFP • Instantaneous total tangent phi • Instantaneous, averaged, max averaged disbalance

Currents per phase curve

PLC

• Temperatures(1) - internal - external via 3 PT100 sensors Metering • Active energy: +/- kWh • Reactive energy: +/- kvarh • Apparent energy: kVAh • Hours: Harmonic analysis (level 63) • Harmonic distortion rate - Currents: thd I1, thd I2, thd I3, thd In - Phase-to-neutral voltage: thd U1, thd U2, thd U3 - Phase to phase voltage: thd U12, thd U23, thd U31 • Individual - Currents: HI1, HI2, HI3, HIn - Phase-to-neutral voltage: HU1, HU2, HU3, - Phase to phase voltage: HU12, HU23, HU31 Events(1) • Alarms on all electrical values Communications(1) • Analogues 0/4- 20 mA • Digital RS485 (Jbus/Modbus & Profibus-DP) • Ethernet (modbus/TCP or Jbus/ Modbus RTU over TCP and Web server) • Ethernet with RS485 gateway Jbus/Modbus RTU over TCP Inputs / Outputs(1) • Pulse metering • Remote control/command • Alarm report • Pulse report (1) Available as an option (see the following pages).

General Catalogue 2012-2013 SOCOMEC

appli_386_a

diris_826_b_1_gb_cat

diris_824_a_1_cat

PC


Multifunction meters

DIRIS A60

diris_824x_a_1_cat

ÂÂFront panel 1. Backlit LCD screen. 2. Pushbutton for currents, temperatures and CT setup wiring correction. 3. Pushbutton for voltages and frequency. 4. Pushbutton for active, reactive, and apparent power and power factor. 5. Pushbutton for maximum and average current and power values. 6. Pushbutton for harmonics values. 7. Pushbutton for energies and hour run meter. 1

2

3

4

5

6

7

ÂÂPlug-in modules

diris_447_a_1_cat

diris_445_a_1_cat

Pulse outputs • 2 configurable pulse outputs (type, weight and run) on ± kWh, ±kvarh and kVAh

JBUS / MODBUS® communication • RS485 link with JBUS / MODBUS® protocol (speed up to 38400 bauds).

diris_776_a_1_cat

diris_834_a

diris_777_a_1_cat

DIRIS® A60

diris_775_a_1_cat

PROFIBUS® DP communication • RS485 link with PROFIBUS® DP protocol (speed up to 12 Mbauds).

Ethernet communication • Ethernet link with MODBUS/TCP or JBUS/MODBUS RTU over TCP • Embedded Ethernet Webserver software

Ethernet communication with RS485 JBUS/MODBUS gateway • Ethernet link with MODBUS/TCP or JBUS/MODBUS RTU over TCP • Connection of 1 to 247 RS485 JBUS/MODBUS slaves

diris_448_a_1_cat

Analogue outputs • A maximum of 2 modules may be connected, that is 4 analogue outputs. 2 outputs assignable to: 3I, In, 3V, 3U, F, ± ΣP, ± ΣQ, ΣS, ΣPFL/C, I sys, Vsys, Usys, Ppred, Q pred, Spred, T°C internal, T°C 1, T°C 2, T°C3 and to 17 VDC power supply.

diris_449_a_1_cat

2 inputs - 2 outputs • A maximum of 3 modules may be connected, giving 6 inputs. 2 outputs assignable to: - monitoring: 3I, In, 3V, 3U, F, ± ΣP, ± ΣQ, ΣS, ΣPFL/C, THD 3I, THD In, THD 3V, THD 3U, Ppred, Qpred, Spred, T°C internal, T°C 1, T°C2, T°C3 and hour meter, - remote control, - timed remote control, - 2 inputs for pulses metering.

diris_747_a_2_cat

Temperature

SOCOMEC General Catalogue 2012-2013

• Temperature indication: - Internal - External sensor PT 100 (T°C 1) - External sensor PT 100 (T°C 2) - External sensor PT 100 (T°C 3)

3


ÂÂDIRIS A60 - Accessories Current transformer

IP65 protection

Mounting kit for kit 144 x 96 mm cut out plate

diris_718_b_1_cat

diris_720_a_2_cat

trafo_077_b_2_cat

trafo_024_a_2_cat

Current transformer (see page 334)

ÂÂTerminals DIRIS A60

V2

V3

VN

AUX: auxiliary power supply Us V1- V2 - V3 - VN: voltage inputs

I3

RS485

1

9 10 11 12

0n R = 120

OUT 1 A-Cd

DIRIS A40 / A41

Pulse output module

1

2

3

OUT 2 A-Cd

1 3 14 15 16 -

+

-

IN 1

+

+

RS485 gateway

DIRIS A40/A41

Ethernet Module

4

10 BASE T 100 BASE T RJ45

DIRIS A40/A41

OUT 2

19 20 21 22 23 24 25 26

1 - 2: pulse output n°1. 3 - 4: pulse output n°2.

Analogue output module

6

RJ45

0V -

DIRIS A40 / A41

9 - 10: relay output n°1. 11 - 12: relay output n°2. 13 - 14: opto input n°1. 15 - 16: opto input n°2.

DIRIS A40 / A41

5

10 BASE T 100 BASE T

IN 2

Temperature module OUT 1

diris_751_b_1_gb_cat

+

Ethernet module + RS485 JBUS / MODBUS gateway

diris_752_a_1_x_cat

0V -

2 inputs / 2 outputs module

diris_574_b_1_x_cat

diris_571_a_1_x_cat

I2

DIRIS A40

RS485 link. R = 120 Ω: internal resistance for the RS485 link.

diris_572_a_1_x_cat

S1 S2 S1 S2 S1 S2 I1

Communication module

diris_573_a_1_x_cat

A U X

7

diris_753_a_1_gb_cat

diris_569_a_1_x_cat

S1 - S2: current inputs

V1

sensor 1

sensor 2

27 28 29 30 sensor 3

DIRIS A40/A41

8

+ - + 0/4-20 mA 0/4-20 mA OUT 1 OUT 2

DIRIS A40 / A41

5 - 6: analogue output n°1. 7 - 8: analogue output n°2.

4

General Catalogue 2012-2013 SOCOMEC


Multifunction meters

DIRIS A60 ÂÂElectrical characteristics

Current measurement on insulated inputs (TRMS) Via CT primary 10 000 A Via CT secondary 1 or 5 Measurement range 0 … 11 kA Input consumption ≤ 0.1 VA Measurement updating period 1s Accuracy 0.2 % Sustained overload 6A intermittent overload 10 In for 1 s Voltage measurements (TRMS) Direct measurement between phases Direct measurement between phase and neutral VT primary VT secondary Frequency Input consumption Measurement updating period Accuracy Sustained overload

2 inputs / 2 outputs module: Outputs (alarms / control) Number of relays 2(1) Type 250 VAC - 5 A - 1150 VA 2 inputs / 2 outputs module: Phototransistor inputs Number 2(1) Power supply 10 … 30 VDC Minimal signal width 10 ms Minimum length between 2 impulses 18 ms Type phototransistor

50 … 700 VAC 28 … 404 VAC 500 000 VAC 60, 100, 110, 173, 190 VAC 50 / 60 Hz ≤ 0.1 VA 1s 0.2 % 760 VAC

Pulse outputs module Number of relays Type Max. number of operations

2 100 VDC - 0.5 A - 10 VA ≤ 108

Analogue output module Number of outputs Type Scale Load resistance Maximum current

2(2) insulated 0 / 4 … 20 mA 600 Ω 30 mA

Current-voltage product Limitation for 1A CT Limitation for 5A CT

10 000 000 10 000 000

Power measurement Measurement updating period Accuracy

1s 0.5 %

Power factor measurement Measurement updating period Accuracy

1s 0.5 %

PROFIBUS-DP communication module Link SUB-D9 Protocol PROFIBUS® DP 9.8 kbauds … 12 Mbauds PROFIBUS® speed

Frequency measurement Measurement range Measurement updating period Accuracy

45 … 65 Hz 1s 0.1 %

Ethernet Communication Module Connectique RJ45 Speed 10 base T / 100 base T Protocol MODBUS TCP or JBUS/MODBUS RTU over TCP

Energy accuracy Active (according to IEC 62053-22) Reactive (according to IEC 62053-23)

class 0.5 S class 2

Auxiliary power supply Alternating voltage AC tolerance Direct voltage DC tolerance Frequency Consumption

110 … 400 VAC ± 10 % 120 … 350 VDC ± 20 % 50 / 60 Hz ≤ 10 VA

Temperature inputs Type Connection Dynamic Accuracy Maximum length

PT100 2, 3 or 4 wires - 20°C ... 150°C +/- 1 digit 300 cm

Operating conditions Operating temperature Storage temperature Relative humidity

- 10 … + 55 °C - 20 … + 85 °C 95 %

JBUS / MODBUS communication module Link RS485 Type 2 … 3 half duplex wires Protocol JBUS/MODBUS® in RTU mode ® 1400 … 38400 bauds JBUS/MODBUS speed

(1) Max. 3 modules / DIRIS. (2) Max. 2 modules / DIRIS.

ÂÂCase

92

diris_582_d_1_x_cat

96

DIR IS

Type Dimensions W x H x D Case protection index Front protection rating Display type Terminal blocks type Voltage and other connection section Current connection section Weight

+ 0.8 - 0.0

92

A4 0

60

Panel mounting 96 x 96 x 60 mm IP30 IP52 LCD fixed or pull-out 0.2 … 2.5 mm2 0.5 … 6 mm2 400 g

+ 0.8 - 0.0

35

96

SOCOMEC General Catalogue 2012-2013

5


 DIRIS A60 - Connection Recommandation: when disconnecting the DIRIS, the secondaries of each current transformer must be short-circuited. This operation can be carried out automatically by a product in the SOCOMEC catalogue, PTI: consult us. Low voltage balanced network for DIRIS A60 3/4 wires with 1 CT

Single phase

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class N P1 L1 S1 S2 L2 L3

1

1

1

S1 S2 S1 S2 S1 S2

V1 V2 V3 VN

I1

I2

I3

V1 V2 V3 VN

S1 S2 S1 S2 S1 S2 I1

I2

I3

diris_394_d_1_gb_cat

1

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class P1 L1 S1 S2 L2

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class P1 L1 S1 S2 N

diris_393_d_1_gb_cat

diris_392_d_1_gb_cat

1

Two phase

1 S1 S2 S1 S2 S1 S2

V1 V2 V3 VN

I1

I2

I3

Use of 1 CT reduces by 0.5% the accuracy of the phases, the current of which is worked out by vector calculation.

Low voltage unbalanced network for DIRIS A60 3/4 wires with 3 CTs

3 wires with 2 CTs

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class N P1 L1 S1 S2 L2 P1 L3 S1 S2

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class P1 L1 S2 S1 L2 P1 L3 S2 S1 1

1

V1 V2 V3 VN

S1 S2 S1 S2 S1 S2 I1

I2

I3

1

1 = Fus. 0.5 A gG / BS88 2 A gG / 0.5 A CC Class P1 L1 S1 P1 L2 S1 S2 L3

1

1

V1 V2 V3 VN

S1 S2 S1 S2 S1 S2 I1

I2

I3

diris_397_d_1_gb_cat

1

diris_396_d_1_gb_cat

diris_395_d_1_gb_cat

1

3 wires with 2 CTs

Use of 2 CTs reduces by 0.5% the accuracy of the phase, whose current is worked out by vector calculation.

1

1

V1 V2 V3 VN

S1 S2 S1 S2 S1 S2 I1

I2

I3

Use of 2 CTs reduces by 0.5% the accuracy of the phase, whose current is worked out by vector calculation.

Additional information Communication via RS485 link

Connection of voltage transformer for HV networks

AC & DC auxiliary power supply

L1 L2 L3

110 / 400 VAC (IEC) 120 / 350 VDC (IEC)

+ ON

RS485

V1 V2 V3 N

diris_400_g_1_gb_cat

0V -

diris_399_b_1_x_cat

diris_398_c_1_x_cat

LIYCY-CY

A U X

It is recommended that the auxiliary power supply be protected by the use of 500 mA gG fuses.

 Software Visualize the SAG, SWELL, CUT-OFF and Over current curves

diris_837_a_1_gb_cat

Event log: Display

6

• Classification of the events according to EN50160 • Export pictures or XLM files of curves. Software can be connected to the DIRIS either in Modbus TCP / Modbus RTU over TCP or Modbus RTU over RS485. Software can be downloaded on the SOCOMEC website: www.socomec.com Curve display

diris_845_a_1_fr_cat

This software allows the DIRIS A60 event monitoring system to help you improve the reliability of your electrical installation, by detecting and allowing the analysis of the events through graphic display. It provides the following functions: • List of voltage dips, cuts, and surges, and over current • Display of the 10 curves (3V, 3U, 3I, In) related to the event with advanced zoom in functions

General Catalogue 2012-2013 SOCOMEC


Multifunction meters

DIRIS A60 diris_824_a_1_cat

 References

Basic device Auxiliary power supply Us 110 ... 400 VAC / 120 ... 350 VDC

DIRIS A60 Reference 4825 0207

Options

Plug-in-modules(1) Pulse outputs RS485 JBUS/MODBUS® communication Analogue outputs 2 inputs / 2 outputs RS485 PROFIBUS®DP communication Ethernet communication (embedded Ethernet Webserver software) Ethernet communication + RS485 gateway JBUS/MODBUS (embedded Ethernet Webserver software) Temperature inputs

Reference 4825 0090 4825 0092 4825 0093 4825 0094 4825 0205 4825 0203 4825 0204 4825 0206

(1) Ease of integration for additional functions (maximum 3).

Accessories

Description of accessories IP65 protection Panel mounting kit for a 144 x 96 mm cutout Fuse combination switches for the protection of voltage inputs (type RM) 3 poles Fuse combination switches for the protection of the auxiliary supply (type RM) 1 pole + neutral Fuses type gG 10x38 0.5 A Current transformers range

To be ordered by multiple 1 1 4 6 10

Reference 4825 0089 4825 0088 5601 0018 5601 0017 6012 0000 See page XXX

Services and Technical assistance Our expertise extends to a complete offer of services like commissioning installation audit, training, maintenance and project engineering.

 Ethernet Webserver

The Webserver is a software, based on HTML pages, that is embedded in the optional Ethernet module of the DIRIS. Access is available using an internet browser and entering the IP address of the DIRIS. It enables viewing the main electrical values, diagnostic analysis, device monitoring and setting the main parameters of the DIRIS multifunction meter.

diris_869_a_1_gb_cat

Panels for viewing all average and instantaneous electrical values.

Viewing of average and instantaneous energy consumptions.

Device setting

Alarms

diris_868_a_1_gb_cat

Use

Power and Energy

diris_870_a_1_gb_cat

diris_776_a_1_cat

diris_867_a_1_gb_cat

Instantaneous report of measurements

The last 10 alarms are date and time registered. Duration and limit reached (low limit value / high limit value), as well as the related output alarm number are also displayed. Data can be extracted in *.csv format.

SOCOMEC General Catalogue 2012-2013

7

05 dirisa ok  