Issuu on Google+

DEPRO速 -FRM5/24V/5A Fused Relay Module

n

Relay with fused contacts.

n

24Vdc coil, 5A contacts.

n

Compact, requires just 20mm of DIN rail.

n

cCSAus certified for Class 1 Division 2 and Zone 2 applications.

The DEPRO速 - FRM5/24V/5A

Provision is made for a standard

Ordering Information

combines a relay module and a

5x20mm fuse (not included). These

Catalog Number

fuse terminal to make a compact

are suitable for non-overload C1D2

module that saves panel space and

applications (see application note at

installation time.

www.emphatec.com. The socket mounted fuse is accessed by removing

The output is a 1 form C (SPDT)

a single screw that holds the protective

contact with a fuse in series with the

cover in place. A test point is provided

commin connection. The contact is

to allow easy checking of the fuse

rated 5A max. at 30Vdc/230Vac. To

condition - a voltage at this test point

increase vibration resistance the relay

indicates a healthy fuse.

is soldered to the PCB. A green LED illuminates when the coil is energized.

10A spy court, markham on l3r 5h6 tel: [905] 475-0220 fax: [905] 475-8796 [eng.] fax: [905] 475-8117 [prod.] email: info@emphatec.com www.emphatec.com

330199


DEPRO速 -FRM Catalog Number: 330199 Coil Voltage: 24Vdc nominal Current: 7mA nominal Status LED: Green Contacts Rating: 5A max. at 24Vdc / 230Vac Configuration: 1 form C (SPDT) Fuse Type: 5x20mm Rating: 5A max. Test Point: Allows connection of a voltmeter to the load side of the fuse. Other test lead is connected to the neutral or 0V of the supply feeding the common contact. A voltage indicates the fuse is healthy. Other Specifications Terminations: 26 - 12AWG 0.5 - 0.6Nm, 6mm stripping length Approvals: cCSAus Class 1 Division 2, Groups A, B, C, D, Temperature code T5 Ex nA IIC, Zone 2, AEx nA IIC Spare fuse cover and retaining screw (package of 8): Catalog Number 330316

Green

V+ 0V

! WARNING

TB1 1 2

TP1 WHITE

1 2

K1

3 4 5

F1

TB2

T5A 250V

3 2 1

COM NC NO

For Class 1 Division 2 Applications EXPLOSION HAZARD: SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS 1, DIVISION 2; DO NOT DISCONNECT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS

10A spy court, markham on l3r 5h6 tel: [905] 475-0220 fax: [905] 475-8796 [eng.] fax: [905] 475-8117 [prod.] email: info@emphatec.com www.emphatec.com

Printed in Canada 330199DS