Elia System and market overview 2011


Contents A. System and grid management and market data I. Energy I.1 Energy balance on the Elia grid in 2011

01

I.2 Elia grid load

02

I.3 Net offtake

03

II. Power II.1. Peak load on the Elia grid in 2011

04

II.2. Peak load on the Elia grid and temperature trend

04

II.3 Generating facilities

06

III. International markets and flows III.1 Belpex day-ahead market in 2011

07

III.2. Imports and exports

09

IV. System management IV.1 Balancing

15

IV.2 Reliability

16

B. Public service obligations I.1 Renewable energy : green certificates and cogeneration certificates

18

I.2 Saving energy : rational use of energy

19


01 • ELIA System and market overview 2011

A. System and grid management and market data I. Energy I.1 Energy balance on the Elia grid in 2011

1

Energy balance on the Elia grid in 20111

(All values in GWh) Imports

Exports

France :

7,221.0

France :

2,330.1

Luxembourg :

1,531.9

Luxembourg :

1,318.1

Netherlands :

4,514.5

Netherlands :

7,003.8

Net Import : 2,615.3 Net Injection Power stations :

Offtake 70,746.6

Local generation on Elia-grid :

9,646.5

From distribution networks :

653.5

Total :

81,046.6

Direct customers :

28,938.6

Distribution :

53,264.6

Total :

82,203.2

Energy losses : 1,458.7

A customer with a local generation unit draws electrical energy from the grid at the same point where the local generation unit injects energy into the grid.

Energy balance on the Elia grid in 2010

(All values in GWh) Imports

Exports

France :

3,167.0

France :

5,409.0

Luxembourg :

1,845.8

Luxembourg :

1,121.5

Netherlands :

7,382.7

Netherlands :

5,313.3

Net Import : 551.7 Net Injection Power stations : Local generation on Elia-grid : From distribution networks : Total :

1 Figures as of 30 April 2012

Offtake 76,545.2 9,068.9 697.0

86,311.2

Direct customers :

29,176.7

Distribution :

56,110.8

Total :

85,287.4

Energy losses : 1,575.4

The energy balance provides an overview of imports and exports, injections into the Elia grid in Belgium, the load on the Elia grid and losses during transmission. Net injections cover net injections into the Elia grid from power stations connected to the grid (including pumped-storage power stations) and net injections from distribution grids and local generation units that inject energy into the grid at a voltage of at least 30 kV. Injections from generation units connected to a voltage lower than 30 kV are only counted if a net injection into the Elia grid is measured.


02 • ELIA System and market overview 2011

I.2 Elia grid load

2

Elia grid load in 2010 and 2011 (by month) In the past, the load recorded on the Elia grid gave a quite accurate image of electricity consumption in Belgium. This is no longer the case following the growth in decentralised generation injected into and drawn from the distribution grids (mainly onshore wind farms and photovoltaic solar power). Henceforth, Elia will publish grid load figures. Load is divided into two categories : 1/ offtakes and local generation by customers connected directly to the Elia grid (industrial customers); 2/ offtakes by distribution system operators, which in turn transmit electricity to customers connected to their grids (small and medium-sized businesses, organisations and residential customers). The amount of energy is stated in gigawatt-hours or in terawatt-hours (TWh = 1000 GWh). By way of example, one gigawatt-hour is the amount of power needed to light 50 million 20 W energy-efficient lamps for one hour.

The graph below shows the load on the Elia grid per month (for each month in the period 2010-2011) and the average temperatures in °C. Grid load is influenced to a large extent by temperature and season. Overall, the load on the Elia grid decreased by 3.7 %, from 86.6 TWh in 2010 to 83.4 TWh in 2011. The load in 2011 (compared with 2010) dropped 0.5 % for industrial customers connected directly to the Elia grid and 5.18 % for the distribution system operators. The decrease can be explained mainly by the drop in electricity consumption following the resurgence of the economic and financial crisis, coupled with above-average temperatures and developments in renewable energies. The upturn seen in 2010 did not continue in 2011 and the values recorded are lower than the values for the corresponding months in 2010 for all months in 2011. However, they are higher than those for 2009, at the height of the economic and financial crisis that erupted in late 2008.

°C

TWh/month

25.00

9.00 8.00

20.00 7.00 6.00

15.00

5.00 10.00 4.00 3.00

5.00 Energy 2010 (TWh)

2.00 0.00

Energy 2011 (TWh)

5.00

Avg. temp. 2011 (°C)

1.00

Avg. temp. 2010 (°C)

0.00 Jan

Feb March April May June July Aug Sept

Oct

Nov

Dec

2 The load on the Elia grid is based on injections of electrical energy into the Elia grid. It comprises the net generation of units injecting power into the Elia grid (at a voltage of at least 30 kV), the balance of imports and exports at the borders with the Elia control area, and net injections from distribution grids. The energy needed to pump water into the reservoirs of pumped-storage power stations connected to the Elia grid is subtracted. The Elia grid includes grids with a voltage of at least 30 kV in Belgium as well as the Sotel/Twinerg grid in the south of Luxembourg. NOTE: The load on the Elia grid increasingly diverges from consumption in Belgium due to the increase in decentralised generation connected to the distribution grids (at voltages below 30 kV).


03 • ELIA System and market overview 2011

Jan

Feb

March

April

May

June

July

Aug

Sept

Oct

Nov

Dec

Energy 2011 (TWh)

8.03

7.20

7.55

6.74

6.79

6.56

6.34

6.46

6.60

6.85

7.04

7.04

Energy 2010 (TWh)

8.19

7.31

7.61

6.93

6.92

6.73

6.56

6.53

6.80

7.27

7.50

8.20

Avg. temp. 2011 (°c)

4.00

5.40

7.70

14.10

14.80

16.80

16.00

17.30

16.50

12.10

8.60

6.10

Avg. temp. 2010 (°c)

0.10

2.50

6.70

10.30

11.20

17.40

20.50

17.00

14.20

10.60

6.10

-0.70

I.3 Net offtake The net offtake of electrical energy is the sum of the net energy taken off the grid at all access points, including the net offtake (measured at the Belgian border) of Luxembourg system operator Sotel. It does not include local generation by industrial customers connected directly to the Elia grid. The net offtake per region is based on the location of the offtake points and hence is an approximation of the real net offtake per region.

Net offtake in the Elia control area per region GWh Flanders

2008

2009

2010

2011

48,187

43,884

45,472

42,806

Brussels

5,896

5,863

5,907

5,711

Wallonia (Sotel included)

24,420

24,044

25,010

24,527

Total Belgium

78,503

73,791

76,390

73,044

Net offtake in the Elia control area per type of customer GWh

2008

2009

2010

2011

Direct customers

20,775

18,559

20,143

19,779

Distribution networks

57,728

55,232

56,247

53,265

Total

78,503

73,791

76,390

73,044


04 • ELIA System and market overview 2011

II. Power II.1 Peak load on the Elia grid in 2011 The load on the Elia grid peaked at 13,208 MW on 11 January 2011 between 17:45 and 18:00. This was 5.9 % lower than the absolute record set on 17 December 2007 (14,033 MW) and 4.6 % lower than the 2010 peak (13,845 MW set on 1 December 2010). The lowest load (6,232 MW) was set on 24 July 2011 between 06:15 and 06:30, 0.7 % less than the lowest point in 2010 (6,278 MW, 25 July 2010).

II.2 Peak load on the Elia grid and temperature trend The table and graph below show the maximum load on the Elia grid (in MW) for every month during the period 2009-2011.

Maximum load on the Elia grid in 2009, 2010 and 2011 (synchronous peak) MW 14,500 14,000 13,500 13,000 12,500 12,000 11,500 11,000 2009 10,500

2010

10,000

2011 Jan

MW

Feb

Jan

March

Feb

April

March

May

April

June

July

May

Aug

June

Sept

July

Oct

Aug

Nov

Dec

Sept

Oct

Nov

Dec

2009

13,531

12,752

11,820

11,021

10,923

11,035

11,354

11,221

11,314

11,969

12,365

13,046

2010

13,692

13,335

12,616

11,613

11,808

11,472

11,567

11,459

11,468

12,236

13,467

13,845

2011

13,208

13,201

12,536

11,420

11,123

11,370

10,650

11,202

11,217

11,660

12,514

12,507


05 • ELIA System and market overview 2011

Maximum load on the Elia grid and average temperatures 3 per month in 2011 The differences in maximum load can be explained mainly by the differences in temperature and intensity of economic activity in Belgium. The graph and table below show the maximum load per month as well as average maximum and minimum temperatures for each month (in °C). MW

°C 25.00

13,500

13,000 20.00 12,500 15.00

12,000

11,500

10.00

11,000 5.00 10,500

Synchronous peak Avg. max. temp. (°c)

0.00

10,000 Jan

Feb

March

April

May

June

Juily

Aug

Sept

Oct

Nov

Avg. min. temp. (°c)

Dec

Facilities with a CIPU contract with Elia; values based on the maximum technical capacity.

2011

Jan

Feb

March

April

May

June

July

Aug

Sept

Oct

Nov

Dec

13,208

13,201

12,536

11,420

11,123

11,370

10,650

11,202

11,217

11,660

12,514

12,507

Avg. max. temp. (°c)

8.70

12.50

16.50

21.20

21.90

20.10

21.70

20.00

19.60

12.40

8.10

6.70

Avg. min. temp. (°c)

3.60

5.20

8.30

12.20

13.20

12.40

12.10

9.50

8.50

2.80

2.30

1.60

April

May

June

July

Aug

Sept

Oct

Nov

Dec

Synchronous peak in MW

Average temperature per month 3

Jan

Feb

March

Avg. temp. 2011 (°c)

4.00

5.40

7.70

14.10

14.80

16.80

16.00

17.30

16.50

12.10

8.60

6.10

Avg. temp. 2010 (°c)

0.10

2.50

6.70

10.30

11.20

17.40

20.50

17.00

14.20

10.60

6.10

-0.70

Source : Belgian Royal Meteorological Institute


06 • ELIA System and market overview 2011

II.3 Generating facilities Total power per type of generation facility Type

5,926

CCGT and gas turbines

5,349

Conventional power plants

2,016

Multifuels

668

One fuel

1,348

Hydroelectric

95

Pump stations

1,308

Other Diesel engines

2% 1%

MW

Nuclear power plants

Breakdown of installed generation capacity in 2011

8% 8% 36%

Nuclear CCGT and gas turbines

12%

Conventional Other

398

Pump stations

5

Wind turbines

Turbojets

210

Incinerators

183

Cogeneration

943

Wind turbines

310

Total with pump stations

15,402

Total without pump stations

14,094

Hydroelectric

33%

Breakdown of generation by type of facility in 2011 1% 1% 1% 5% 6% Nuclear CCGT and gas turbines 58%

28%

Other Conventional Pump stations Wind turbines Hydroelectric

Monthly generation of electricity by type of generation unit in 2011 GWh 8,000

7,000

6,000

5,000

4,000

3,000

Nuclear Conventional Pump stations

2,000

CCGT and gas turbines Other

1,000

Wind turbines Hydroelectric

0 Jan

Feb

March

April

May

June

July

Aug

Sept

Oct

Nov

Dec


07 • ELIA System and market overview 2011

III. International markets and flows III.1 Belpex day-ahead market in 2011 €/Mwh

Price trends on the Belpex day-ahead market in 2011

70

€/MWh 70

60

60 50 50 40 40 30 30 20 20

APX Belpex

10

10

EPEX Spot FR EPEX Spot DE

0 Jan

Feb

March

April

May

June

July

Aug

Sept

Oct

Nov

Dec

Total

Source : APX, Belpex, EPEX Spot

In 2011 Average price on the Belpex day-ahead market : 49.37 €/MWh Average price on the EPEX Spot day-ahead market (France): 48.89 €/MWh Average price on the APX day-ahead market (Netherlands) : 52.03 €/MWh Average price on the EPEX Spot day-ahead market (Germany) : 51.12 €/MWh

Price convergence with energy exchanges in neighbouring countries After the 9 November 2010 roll-out of pentalateral coupling for the Belpex, APX, EPEX Spot France and EPEX Spot Germany (including Luxembourg) day-ahead markets and ITVC (Interim Tight Volume Coupling) with the market in the Nordic countries, 2011 was the first full year of coupling within the Central West Europe (CWE) zone. Looking at 2011 as a whole, we see that prices on the day-ahead markets in Belgium, France, Germany and the Netherlands were the same 65.75 % of the time (total convergence between electricity prices in those countries), and prices were identical in France, Belgium and the Netherlands another 5.16 % of the time. This figure is significantly higher than in 2010, where CWE market coupling was just 7.99 % of the total for the year (55.05 % for the period from 9 November to 31 December 2010). However, trilateral market coupling (Belgium, France, Netherlands) was an additional 52.33 % in 2010.

In 2011 price convergence between the day-ahead markets in Belgium and France was reached 99.18 % of the time. Price convergence between Belgium and the Netherlands was 71.28 %, while price convergence with Germany was 67.42 %. Following Germany’s unilateral decision in March 2011 to implement a moratorium on nuclear energy, leading to the immediate closure of eight nuclear reactors in Germany, price convergence within the CWE zone dropped to 40.56 % in June, before rising to a record 82.15 % in October. Temperature remains a key factor in determining the level of price convergence in the CWE zone, but this factor has now been supplanted by the level of power generation from renewable sources, such as wind and solar, mainly in Germany. This factor influences prices within the CWE zone, with a price divergence when cross-border capacity is no longer sufficient to cope with the considerable volumes involved.

0 Jan

Fév

Ma


08 • ELIA System and market overview 2011

Price convergence between the day-ahead markets in Belgium, the Netherlands, France and Germany from 1 January to 31 December 2011 75,67%

Jan

13,04%

75,89%

Feb

10,27%

71,74%

March April

66,53%

May

64,11%

6,67% 5,56%

50,56% 5,38%

52,28%

Aug

44,49% 7,66%

38,17%

71,94%

Sept

18,61% 30,24%

47,58%

July

5,06% 6,10% 17,50%

40,56%

June

7,66%

4,17%

21,39%

82,15%

Oct Nov

11,01%

81,81%

5,83%

59,68%

Dec 0%

10 %

20 %

30 %

15,19%

40 %

50 %

60 %

70 %

9,01%

80 %

9,86% 12,50%

90 %

100 %

CWE Full Price Convergence DE = NL <> FR <> BE

BE = FR = NL <> DE BE = NL <> FR <> DE

BE = DE = FR <> NL BE = FR <> NL <> DE

DE = FR <> BE <> NL DE = FR <> BE = NL

DE = NL <> BE = FR

FR = DE = NL <> BE

BE = DE = NL <> FR

All Different

Volumes traded on Belpex In 2011, the average daily volume traded on the Belpex day-ahead market was 33,839 MWh, accounting for 14.8 % of the load on the Elia grid. That was slightly more than in 2010, when the daily volume was 32,446 MWh, i.e. 13.7 % of the load on the Elia grid. The volume record on the Belpex day-ahead market was set on 16 December 2011, with 73,300.1 MWh traded, a record 29 % of the load on the Elia grid.


09 â&#x20AC;˘ ELIA System and market overview 2011

III.2. Imports and exports

Physical flows of energy with neighbouring countries Volumes imported and exported (2010-2011) The table gives an overview of physical flows of electrical energy measured at the borders each year. Physical flows do not necessarily correspond to contractual flows, as electrical energy is divided up over the grid on the basis of resistance, always choosing the path of least resistance, and does not take account of the contents of commercial agreements. 2011

Lux Export

Lux Import

Fr Export

Fr Import

Nl Export

Nl Import

Jan

111.6

-169.0

145.4

-641.2

291.9

-558.2

Feb

101.3

-156.5

98.8

-574.3

212.0

-424.9

March

99.6

-165.6

120.0

-778.4

401.0

-483.1

April

98.6

-155.3

155.6

-636.7

585.1

-234.4

May

123.9

-154.4

138.6

-733.1

877.1

-117.3

June

123.0

-170.6

65.1

-1,041.7

1,010.6

-85.0

July

137.5

-143.5

101.8

-819.3

1,107.8

-144.0

Aug

110.7

-14.1

110.5

-665.0

1,109.2

-180.6

Sept

157.0

0.0

81.4

-638.6

803.2

-242.3

Oct

107.1

-36.2

389.3

-218.3

239.2

-672.4

Nov

78.5

-186.0

461.6

-229.8

186.4

-637.9

Dec

69.3

-180.6

461.9

-244.6

180.2

-734.3

2010

Lux Export

Lux Import

Fr Export

Fr Import

Nl Export

Nl Import

Jan

95.7

-159.5

806.2

-123.1

110.5

-945.6

Feb

87.8

-153.0

602.4

-93.8

257.7

-669.0

March

103.5

-157.2

611.3

-150.1

325.6

-622.1

April

107.7

-142.3

449.8

-162.8

264.0

-455.1

May

132.8

-102.1

595.7

-165.7

427.9

-585.2

June

72.8

-159.8

116.8

-575.8

744.4

-325.9

July

99.5

-153.8

178.3

-389.6

840.6

-245.3

Aug

51.6

-151.5

125.5

-486.4

1,166.7

-182.9

Sept

103.3

-145.2

248.3

-368.0

570.3

-391.5

Oct

108.3

-172.9

850.9

-89.4

199.7

-1,066.5

Nov

99.4

-153.6

499.9

-231.6

282.0

-826.7

Dec

59.2

-194.8

323.8

-330.8

124.1

-1,066.9

Net balance of electricity imports in 2011 In 2011, the balance of imports and exports on the Elia grid in the Belgian control area yielded a net import of 2.61 TWh, significantly higher than the net import of 0.55 TWh seen in 2010. This difference is due to the significant increase in imports, mainly from France (up 128.0 % compared to 2010), whereas total exports were down 10.1 % (mainly due to the 56.9 % drop in exports to France). Physical exchanges of electricity with neighbouring countries via the Elia grid totalled 23.92 TWh, down 1.3 % compared to the 2010 total of 24.24 TWh.


10 â&#x20AC;˘ ELIA System and market overview 2011

Monthly import and export volumes in 2011 and 2010 The charts below show physical exchanges of electricity with neighbouring countries (in GWh) in 2011 and 2010. Negative volumes indicate imports while positive volumes indicate exports. Electricity chooses the path of least resistance, so that physical exchanges of electricity do not necessarily correspond to commercial exchanges. However, the grid operator must take account of the actual physical flows at Belgiumâ&#x20AC;&#x2122;s borders in order to ensure the safe operation of the electricity system.

Import and export volumes in 2011 Imports

Exports

Jan Feb March April May June July Aug Sept

Exchanges with Luxembourg

Oct Nov

Exchanges with the Netherlands

Dec

Exchanges with France

-2,000

-1,500

-1,000

-500

0

500

1,000

1,500

GWh

Import and export volumes in 2010 Imports

Exports

Jan Feb March April May June July Aug Sept

Exchanges with Luxembourg

Oct Nov

Exchanges with the Netherlands

Dec

Exchanges with France

-2,000

-1,500

-1.000

-500

0 GWh

500

1,000

1,500


11 • ELIA System and market overview 2011

Commercial energy exchanges with neighbouring countries Use of cross-border capacities Transmission capacity at the borders is divided into three categories and allocated to the market players on an annual, monthly and daily basis. The market players can use their annual and monthly capacity by nominating it today for the next day (day-ahead). Allocated annual and monthly capacity which is not nominated is once again made available to the market in the form of additional daily capacity. The principle of netting has been used since 2008 to define the quantity of daily capacity available. This involves “netting out” import and export nominations of annual and monthly capacities, thereby freeing up additional available daily capacity. Since 2007, it has also been possible to acquire and use intraday border capacity on the day of delivery at the border between France and Belgium. This system was also introduced at the Dutch-Belgian border in May 2009. The amount of intraday capacity available is mainly determined by the level

of unused daily capacity. Since 17 February 2011, intraday capacity has been allocated in the north border via an implicit mechanism based on continuous trading on the APX-ENDEX and Belpex intraday markets. This happens via the Elbas trading platform. The charts below illustrate the average nominations of annual, monthly, daily and intraday capacity each month at each border. Nominations are compared to the capacity physically available to the market (net transmission capacity, or NTC). The monotonic curve for the use of cross-border capacity represents the use of available capacity over the course of one year, with all hours of the year listed in descending order, from the hour with the highest load to the hour with the lowest. The year’s 8,760 hours are shown on the x-axis, while the y-axis represents the percentage of capacity used for imports and exports. The monotonic curve makes it possible to determine the period of time during which a given cross-border flow took place.

Use of transmission capacity at Belgium’s south border in 2011 Imports

Exports

Jan Feb March April May June July Aug Sept

Year Month

Oct

Day

Nov

Intraday

Dec -3,500

Not nominated -3,000

-2,500

-2,000

-1,500

-1,000

-500

0

500

1,000

1,500

GWh

Use of transmission capacity at Belgium’s south border in 2010 Imports

Exports

Jan

Janvier

Feb

Février

March

Mars

April

Avril

May

Mai

June

Juin

July

Juillet

Aug Sept

Year

Oct

Month

Nov

Day Intraday

Dec -3,500

Not nominated -3,000

-2,500

-2,000

-1,500

-1,000 GWh

-500

0

500

1,000

1,500

Août Septembre Octobre Novembre Décembre -3.500

-3.000

-2.500

-2


12 • ELIA System and market overview 2011

Monotonic curve for the use of transmission capacity at Belgium’s south border in 2011 % Capacities 100%

The monotonic curve for the use of cross-border capacity represents the use of available capacity over the course of one year, with all hours of the year listed in descending order, from the hour with the highest load to the hour with the lowest. - The year’s 8,760 hours are shown on the x-axis (as percentage), - while the y-axis represents the percentage of capacity used for imports and exports.

90% 80% 70% 60% 50% 40%

The monotonic curve makes it possible to determine the period of time during which a given cross-border flow took place.

30% 20% 10%

Import

0% 0%

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

% Of Time

Use of transmission capacity at Belgium’s north border in 2011 Imports

Exports

Jan Feb March April May June July Aug Sept

Year Month

Oct

Day

Nov

Intraday

Dec -2,000

Not nominated -1,500

-1,000

-500

0

500

1,000

1,500

2,000

GWh

Use of transmission capacity at Belgium’s north border in 2010 Imports

Exports

Jan Feb March April May June July Aug Sept

Year Month

Oct

Day

Nov

Intraday

Dec -2,000

Not nominated -1,500

-1,000

-500

0 GWh

500

1,000

1,500

2,000

Export


13 â&#x20AC;˘ ELIA System and market overview 2011

Monotonic curve for the use of transmission capacity at Belgiumâ&#x20AC;&#x2122;s north border in 2011 % Capacities 100% 90% 80% 70% 60% 50% 40% 30% 20% 10%

Export

0%

Import 0%

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

% Of Time

Congestion The graphs show in percentage and in both directions the average number of hours per month with congestion on a border, as against the total number of hours during the month. Imports are on the left, exports on the right.

Congestion at the south border in 2011 Imports

Exports

Jan Feb March April May June July Aug Sept Oct Nov Percentage of hours with congestion

Dec -100 %

-80 %

-60 %

-40 %

-20 %

0%

20 %

40 %

60 %

80 %

100 %


14 â&#x20AC;˘ ELIA System and market overview 2011

Congestion at the south border in 2010 Imports

Exports

Jan Feb March April May June July Aug Sept Oct Nov Dec -100 %

-80 %

-60 %

-40 %

-20 %

0%

20 %

40 %

60 %

80 %

100 %

Percentage of hours with congestion

Congestion at the north border in 2011 Imports

Exports

Jan Feb March April May June July Aug Sept Oct Nov Percentage of hours with congestion

Dec -100 %

-80 %

-60 %

-40 %

-20 %

0%

20 %

40 %

60 %

80 %

100 %

Congestion at the north border in 2010 Imports

Exports

Jan Feb March April May June July Aug Sept Oct Nov Percentage of hours with congestion

Dec -100 %

-80 %

-60 %

-40 %

-20 %

0%

20 %

40 %

60 %

80 %

100 %


15 • ELIA System and market overview 2011

IV. System management IV.1 Balancing Every balance responsible party is responsible for the quarterhourly balance of his injection and offtake portfolio. As the operator of the electricity transmission grid, Elia oversees total balance within its control area between injections and offtakes of electricity. To that end, Elia contracts reserve power. Where necessary, Elia can decrease or increase injections of energy or reduce offtake by ‘interruptible’ customers. Reserve power is broken down into primary, secondary and tertiary categories primarily according to response time and

the period during which the reserve is made available. In addition to tertiary reserve power activated via generation units, Elia can also deploy reserves acquired under contracts signed with interruptible customers. Interruptible customers are prepared to temporarily reduce their offtake at Elia’s request and according to contractually defined conditions. The table and chart below outline the amounts of electricity used by Elia to balance the grid each month.

Activated volumes for balancing in 2011 Decrease injections

Increase injections

Jan Feb March April May Secondary reserve +

June

Secondary reserve -

July

Generation +

Aug

Generation -

Sept

Tertiary reserve

Oct

Contractual interruptions

Nov

Inter TSO Import

Dec -100,000

Inter TSO Export -50,000

0

50,000

100,000

150,000

MWh Month 2011

Secundary reserve +

Secundary reserve -

Generation + (free offers) 4

Generation - (free offers) 5

Tertiary reserve

Contractual interruptions

Inter TSO Import

Jan

59,031 MWh

-10,571 MWh

Feb

34,097 MWh

-21,159 MWh

March

20,200 MWh

April

20,521 MWh

May June

46,843 MWh

-496 MWh

15,077 MWh

0 MWh

0 MWh

0 MWh

17,773 MWh

-4,040 MWh

3,771 MWh

0 MWh

0 MWh

-200 MWh

-45,602 MWh

4,166 MWh

-33,773 MWh

760 MWh

0 MWh

0 MWh

-1,900 MWh

-39,372 MWh

5,603 MWh

-14,618 MWh

1,295 MWh

0 MWh

400 MWh

-1,675 MWh

16,550 MWh

-48,740 MWh

2,794 MWh

-23,760 MWh

1,173 MWh

0 MWh

0 MWh

-2,450 MWh

23,478 MWh

-38,506 MWh

5,773 MWh

-10,027 MWh

711 MWh

771 MWh

0 MWh

-1,250 MWh

July

24,377 MWh

-36,902 MWh

3,253 MWh

-6,732 MWh

229 MWh

0 MWh

0 MWh

-1,400 MWh

Aug

30,957 MWh

-33,864 MWh

10,612 MWh

-7,145 MWh

2,600 MWh

0 MWh

0 MWh

-4,975 MWh

Sept

28,578 MWh

-28,844 MWh

7,964 MWh

-5,151 MWh

2,610 MWh

0 MWh

0 MWh

-1000 MWh

Oct

19,510 MWh

-40,920 MWh

6,400 MWh

-19,156 MWh

624 MWh

369 MWh

0 MWh

-5,150 MWh

Nov

23,153 MWh

-36,043 MWh

10,215 MWh

-17,763 MWh

1,123 MWh

0 MWh

0 MWh

-1,325 MWh

Dec

17,441 MWh

-48,883 MWh

11,036 MWh

-25,127 MWh

1,860 MWh

817 MWh

150 MWh

-5,125 MWh

Load-shedding in the context of the load-shedding plan and activated volumes for congestion management are not included in the activated volumes for balancing. 4- 5 Free offers under the CIPU contract.

Inter TSO Export


16 • ELIA System and market overview 2011

Trend in imbalance prices in 2011

Negative imbalance price

2011

Min (€/MWh)

Positive imbalance price

Max (€/MWh)

Avg (€/MWh)

Min (€/MWh)

Max (€/MWh)

Avg (€/MWh)

Jan

16.83 MWh

252.92 MWh

69.42 MWh

-10.17 MWh

76.40 MWh

37.75 MWh

Feb

12.55 MWh

3238.92 MWh

67.57 MWh

0.00 MWh

2759.08 MWh

30.27 MWh

March

11.15 MWh

346.62 MWh

62.20 MWh

-15.69 MWh

68.94 MWh

27.78 MWh

April

8.91 MWh

338.46 MWh

62.08 MWh

-15.98 MWh

82.86 MWh

25.84 MWh

May

5.67 MWh

334.23 MWh

55.67 MWh

-16.16 MWh

71.58 MWh

24.07 MWh

June

1.74 MWh

331.08 MWh

47.16 MWh

-23.39 MWh

61.73 MWh

21.13 MWh

July

4.48 MWh

300.19 MWh

55.95 MWh

-22.52 MWh

65.20 MWh

24.29 MWh

Aug

11.76 MWh

313.42 MWh

64.04 MWh

-14.95 MWh

72.32 MWh

31.98 MWh

Sept

12.09 MWh

269.31 MWh

61.63 MWh

-3.36 MWh

108.09 MWh

28.60 MWh

Oct

17.20 MWh

294.06 MWh

65.99 MWh

0.00 MWh

102.05 MWh

33.30 MWh

Nov

11.35 MWh

293.40 MWh

56.09 MWh

-13.26 MWh

69.36 MWh

23.26 MWh

Dec

11.35 MWh

293.40 MWh

56.09 MWh

-13.26 MWh

69.36 MWh

23.26 MWh

Contracted reserve power in 2011 Summary of reserves in 2011 Reservation

MW

Primary reserve R1

106

Secondary reserve R2

137

Tertiary reserve R3

400

Interruptible customers

261

Inter-TSO reserve

2 x 250 (Not guaranteed)

IV.2 Reliability Reliability indicators The Elia grid is very reliable. Reliability is measured using three statistical parameters: the annual average interruption time on the Elia grid, spread across all customers (given in minutes per customer and per year), the annual average number of interruptions to an Elia grid customer’s electricity supply and the average duration (in minutes) per interruption on the Elia grid and per year. In percentage terms, the Elia grid achieves an average reliability rate of over 99.999 %. Annual average interruption time (AIT) 6 Time (hours:minutes:seconds) 00:07:00 00:06:00 00:05:00 00:04:00 00:03:00 00:02:00 00:01:00

Number of minutes per customer per year

00:00:00

Average per five years 1999

2000

2001

2002

2003

2004

2005

2006

2007

2008

2009

2010

2011


17 â&#x20AC;˘ ELIA System and market overview 2011

Annual average interruption frequency per customer (AIF) 7 Frequency 0.150 0.125 0.100 0.075 0.050 0.025

Annual frequency Average per five years

0.000 1999

2000

2001

2002

2003

2004

2005

2006

2007

2008

2009

2010

2011

Average interruption duration per affected customer (AID) 8 Time (hours:minutes:seconds) 1:00:00 0:55:00 0:50:00 0:45:00 0:40:00 0:35:00 0:30:00 0:25:00 0:20:00 0:15:00

Minutes per interuption

0:10:00 0:05:00

Average per five years

0:00:00 1999

2000

2001

2002

2003

2004

2005

2006

2007

2008

2009

2010

2011

Average Interruption Time6

Average Interruption Frequency7

Average Interruption Duration8

Reliability Elia grid

Number of days per year

1999

00:04:12

0.1160

0:36:00

99.99920 %

365

2000

00:06:42

0.1240

0:54:00

99.99873 %

366

2001

00:04:00

0.0850

0:47:00

99.99924 %

365

2002

00:02:26

0.0690

0:35:00

99.99954 %

365

2003

00:05:53

0.1180

0:50:00

99.99888 %

365

2004

00:01:58

0.0500

0:40:00

99.99963 %

366

2005

00:03:01

0.0960

0:31:27

99.99943%

365

2006

00:05:14

0.1300

0:41:23

99.99900 %

365

2007

00:03:32

0.0904

0:39:07

99.99933 %

365

2008

00:03:07

0.0800

0:38:29

99.99941 %

366

2009

00:01:34

0.0910

0:17:12

99.99970 %

365

2010

00:04:51

0.1300

0:37:24

99.99908 %

365

2011

00:02:19

0.0903

0:25:44

99.99956 %

365

6 Average Interruption Time is the average duration of power cuts spread across all customers. 7 Average Interruption Frequency is the annual average number of power interruptions per customer. A value of 0.09 indicates that on average a customer experiences a power cut every 11 years. 8 Average Interruption Duration is the average duration of a power cut experienced by a customer.


18 • ELIA System and market overview 2011

B. Public service obligations I.1 Renewable energy : green certificates and cogeneration certificates The Belgian federal and regional governments have developed support mechanisms in order to boost investments in electricity generation from renewable energy sources. One of these is the system of “green certificates” and “cogeneration certificates” (the latter only in Flanders) issued to generators by the regulators, proving the green origin of the electricity they generate. These certificates can then be sold on the electricity supplier market or purchased by Elia or distribution system operators. Each year, suppliers must present a certain number of green certificates to the regulator. The required number is based on their power sales. As the transmission system operator, Elia has a legal obligation to purchase the certificates offered at a minimum price defined by law. For green certificates and cogeneration certificates in Flanders, Elia places acquired green certificates on the market. Federal green certificates (offshore wind power generation) and green certificates for the Walloon Region and Brussels Capital Region may not be resold by Elia and must be removed from the market permanently. The cost of federal, Walloon and Brussels certificates, as well as the balance corresponding to the difference between the price at which Elia purchases the certificates and the price at which they are sold on the market in Flanders, is factored into transmission tariffs in the form of public service obligations, taxes and levies.

Green certificates and cogeneration certificates (Flanders) purchased by Elia Million € 90 80 70 60 50

GWh

40 30

■ Combined Heat and Power certificates - Flemish Region ■ Green certificates - Flemish Region

20 10

■ Green certificates - Walloon Region

0

■ Federal green certificates (offshore) 2009

2010

2011


19 • ELIA System and market overview 2011

Prices and volumes of green certificates sold in Flanders

13,967

Number

€/Certificate

GC Flanders region

2,250

2,090

2,050 1,850 1,650 1,450 1,250 1,050

118.74

850

672

650 450 250 50

117.52 110.76

313

258 17-02-06

981

117.47

25-10-06

02-02-07

663

112 109.13 421

125.00

970

120.00 115.00

112

110.00 105.00

363 97

78.35 28-10-10 29-02-08 12-03-09 10-12-09 14-11-11 28-09-07 24-10-08 Sales date

100.00 95.00 90.00

Price Number

Prices and volumes of cogeneration certificates sold in Flanders In 2011 as part of its public service obligations in Flanders, Elia was – for the first time - required to purchase cogeneration certificates in Flanders : 236,130 certificates at a unit price of € 27, i.e. a total of € 6,375,510. Elia resold 12,100 certificates at an average unit price of € 18.83.

I.2 Saving energy: rational use of energy Promoting rational use of energy by our customers As part of its public service obligations in Flanders, Elia implements an action plan each year to promote rational use of energy (RUE) by its industrial customers connected at voltages between 30 and 70 kV. In this connection, Elia provides its customers with the resources required to make recurrent savings of 2.5 % on their primary energy consumption for each MWh supplied. The target for 2011 was a savings of 37.8 GWh of electric power. In fact, actual savings amounted to 41.6 GWh. Forty-eight projects were submitted and our customers pledged to invest in 44 energy-saving projects. Thanks to Elia’s initiatives targeting its industrial customers, cumulative energy savings since 2003 stood at 497 GWh at the end of December 2011, i.e. some 162,000 tonnes of CO2.