RISER DIAGRAM 602RF POWER SUPPLY

1512 or 1572 MAGNETIC LOCK

TO 120VAC POWER SOURCE TO FIRE ALARM – CLOSED CONTACT CONNECTION

2 COND

4 COND

2 COND 1

2

4

5

3 6

7

8

9

*

0

#

925 KEYPAD

422 EXIT SWITCH

NOTES: (1) ALL LOW VOLTAGE SIGNAL WIRING SHALL BE 20-GAUGE MINIMUM. THE MINIMUM INDUCTIVE LOAD (LOCK) POWER WIRE GAUGE SHALL BE DETERMINED PER THE SDC WIRE GAUGE CHART. ALL WIRING (SINGLE OR MULTI-CONDUCTOR) SHALL BE COLOR CODED WITHOUT SPLICES. A MINIMUM OF TWO SPARE CONDUCTORS IS RECOMMENDED. (2) SPECIFY VOLTAGE WHEN ORDERING PRODUCTS. VOLTAGE IS NOT SPECIFIED ON THIS WIRE DIAGRAM, BE SURE ALL PRODUCTS ARE VOLTAGE COMPATIBLE. (3) ALL WIRING MUST CONFORM TO NATIONAL, STATE AND LOCAL CODES. (4) ALWAYS CONSULT WITH THE AUTHORITY HAVING JURISDICTION (AHJ) BEFORE INSTALLATION. (5) WHERE REQUIRED BY CODE, CONNECT FAILSAFE SYSTEMS TO THE LOCAL FIRE LIFE SAFETY SYSTEM FOR EMERGENCY RELEASE.

Components Qty 1 1 1 1

Description Double Magnetic Lock Power Supply Push Button Exterior Digital Keypad

Part Number 1512 or 1572 EMLock 602RF 422 925

Manufacturer SDC SDC SDC SDC

Method of Operation Access/Egress: Entering a valid digital code releases the locking device momentarily for access. Pressing the exit switch button releases the locking device momentarily for egress. Entry and exit momentary unlock time is determined by digital keypad programming. Emergency Release: All locks will release automatically (see note 5) upon activation of the fire life safety system.

© 2004 Security Door Controls Printed in U.S.A

PROJECT NAME: DWG. NO.: 1-RS-Library-0005-R2 CONTACT:

LOCATION:

DISTRIBUTOR:

SO. NO.: DATE: 10-2004

DWN BY: MD

TM

EntryCheck

SECURITY DOOR CONTROLS 3580 Willow Lane Westlake Village CA 91361-4921 Tel. 805-494-0622 FAX: 805-494-8861


EMLock

R

Exit Check

SELECTRIC

R

R

TM

Spacesaver

R

HiTower

Sure Exit

R

TM

EntryCheck

POINT TO POINT WIRING DIAGRAM TO 120VAC PRIMARY VOLTAGE CONNECTION

925 KEYPAD

3

1

2

4

5

7

8

9

*

0

#

6

G W B

REFER TO POWER SUPPLY INSTRUCTIONS FOR 12 OR 24V VOLTAGE SELECTION PROCEDURE

925 ENTRY CHECK

+

-

602 SERIES POWER SUPPLY

+

C

-

J3 NO

J4 1 + 2 -

POWER

3 DISABLE/INHIBIT 4 COMMON 5 REQUEST TO ENTER

1

COMMON

2

NC

3

OUTPUT #3

4

OUTPUT #4

5

NO

6

COMMON

7

NC COMMON GROUND

8

-

STANDBY BATTERY CONNECTION

12VDC OR 24VDC OUTPUT

-

9

(REMOVE FACTORY JUMPER ONLY IF FIRE ALARM IS USED)

6 EARTH GROUND

CLOSED FIRE ALARM CONTACT

1512 or 1572 SERIES DOUBLE MAGNETIC LOCK 400 SERIES EXIT SWITCH

BAS PLUG IN

EXAMPLE: 422RE MO - SPDT

BAS

NC

DPS

ORG

{ {

BAS PLUG IN

NO BAS

COM NC NO

DPS

COM NC

{ {

NO COM NC NO COM

WHT

YEL

C

NO

-

NC

+

+ POWER

J1

POWER

-

J1

© 2004 Security Door Controls Printed in U.S.A

PAGE 1 OF 1

PROJECT NAME:

LOCATION.:

DIST.:

CONTACT:

DWG. NO.: 1-PP-Library-0005-R2

DATE: 10 / 2004

DRAWN BY: MD

SECURITY DOOR CONTROLS 3580 Willow Lane Westlake Village CA 91361-4921 Tel. 805-494-0622 FAX: 805-494-8861


Visio-SDC-RS-Library-R2