Issuu on Google+

Programmable Logic Controller

Automation Solution


Programmable Logic Controller

All-In-One PLC

With Next Generation Technology XGB is the micro PLC that offers maximum automation at minimum cost. With its high performance and functionality, it can support from simple control to complex task. Strengthening its communication functions, XGB offers user-oriented integrated control. Based on its strengths, it can be used in many fields of applications.

2


Conten ▶ ▶ ▶ ▶

Feature Main Unit Built-in functions Expansion

4 7 14 19

DC Input

19

Transistor Output

21

Relay Output

23

DC Input / Relay Output

24

Analog Input

25

Analog Output

26

Analog Input/Analog Output

27

RTD

28

Thermocouple

29

Positioning module

30

Communication

▶ ▶ ▶

Software Product list Dimension

31

32 33 34

3


Feature

(Unit: mm)

It's Slim

XBM XBC / XEC Expansion

Item

W

H

D

DR/DN16S (16pt) DN32S (32pt)

30

90

60

DR/DN32H (32pt)

114

90

64

DR/DN64H (64pt) Relay output / Ethernet

180 27

90 90

64 60

Others

20

90

60

Compactness XGB is even more compact but provides powerful functions and performance. Compact & Powerful solutions & XGB’s steadfast competitiveness.

4

64㎜

㎜ 90

60㎜

㎜ 30

㎜ 90

4㎜ 11


H

i

g

h

With its high-speed processing and system capability, XGB offers utmost efficiency for your applications.

XBC /XEC (H-Type) •83ns/Step processing speed and floating-point arithmetic with on-board CPU •Max 10 expansion modules, Max. 384 I/O point control: PLC systems for Small- and medium-scale applications •Max. 5-Ch Communication with built-in functions and expansion modules

Communication Max. 2stages

Analog Max. 10stages

Expansion I / O Max. 10stages

Max. 10stages

XBM (S-Type) •160ns/Step processing speed and floating-point arithmetic with on-board CPU •Max 7 expansion modules, Max. 256 I/O point control: PLC systems for Small- and medium-scale applications •Max. 5-Ch Communication with built-in functions and expansion modules

Communication Max. 2stages

Analog Max. 7stages

Expansion I / O Max. 7stages

Max. 7stages

5


Feature

Easiness & Convenience XGB offers convenient user interface with various network diagnosis & monitoring functions and back-up function

•Enhanced user interface with XG5000 / XG-PD Integrated programming •Various monitoring functions. environment •Network diagnosis and monitoring •Batteryless back-up •Powerful communication: Built-in RS-232C / 485, 2 Expansions for communication Optimum communication •Network configuration via Ethernet and Cnet I/F environment

Device monitoring

User event Frame monitoring

Forced I/O

6

Trend monitoring


Main Unit | DC power General Specification

Programmable Logic Controller

Item Ambient temperature Storage temperature Ambient humidity Storage humidity

Vibration resistance

Shock resistance

Noise resistance XBM-DR16S

Operating Ambience Altitude Pollution level *1) Cooling

Descriptions 0 ~ 55 °C - 25 ~ + 70 °C 5 ~ 95%RH (Non-condensing) 5 ~ 95%RH (Non-condensing) Occasional vibration Frequency Acceleration Pulse width 0.075mm 10 ≤ f < 57Hz 10 times each 57 ≤ f ≤ 150Hz 9.8m/s2 (1G) direction Continuous vibration (X, Y and Z) Frequency Acceleration Pulse width 0.035mm 10 ≤ f < 57Hz 57 ≤ f ≤ 150Hz 4.9m/s2 (0.5G) •Peak Acceleration: 147m/s2 (15g) •Duration: 11ms •Pulse waveform: Half-sine, 3times each direction per each axis Square wave ±500 V impulse noise Electrostatic 4kV discharge Radiated 80 ~ 1000MHz, 10V/m electromagnetic field noise Main unit Expansion module Fast transient/ Burst noise 2kV 1kV Free from corrosive gases and excessive dust Up to 2,000m Less than 2 Air-cooling

Standard

IEC61131-2

IEC61131-2 LSIS Standard IEC61131-2 IEC61000-4-2 IEC61131-2 IEC61000-4-3 IEC61131-2 IEC61000-4-4

*1) Pollution level indicates the degree to which conductive material is generated in the environment where the equipment is used. Pollution level 2 is the condition that only non-conductive pollution occurred but temporary conductivity may be produced due to condensing.

Performance Specification

Item Control method

XBM-DR16S

I/O control mode Programming language No. of instructions Processing speed Program capacity Max. I/O points

Data memory

XBM-DN16S XBM-DN32S

P M K L F T C S D U Z N

Number of program Operation mode Self diagnosis Program port Data retension at power failure Built-in function Internal current consumption Weight Rated voltage

XBM-DN16S XBM-DN32S Repetitive, cyclic, interrupt, constant scan Refresh mode (Batch processing by scan synchronization) Direct mode by instruction Ladder Diagram, Instruction List Basic: 28, Applied: 677 0.16㎲ / Step (for basic instruction) 10k steps 256 points 240 points (Main + 7 expansions) P0000 ~ P127F (2,048 points) M0000 ~ M255F (4,096 points) K00000 ~ K2559F (Special area: K2600 ~ 2559F) (40,960 points) L00000 ~ L1279F (20,480 points) F000 ~ F255F (4,096 points) 100ms, 10ms, 1ms: T000 ~ T255 (Changeable by Parameter setting) C000 ~ C255 S00.00 ~ S127.99 D0000 ~ D5119 (5,120 words) U00.00 ~ U07.31 (Analog data refresh area: 256 words) Z000 ~ Z127 (128 words) N0000 ~ N3935 (3,936 words) 128 RUN, STOP, DEBUG Operation delay monitoring, memory error, I/O error, etc. RS-232C Latch range setting at Basic parameter RS-232C/485, High-speed counter, PID control, Pulse catch, Input filter External interrupt, Positioning *1) 400mA 250mA 280mA 140g 100g 110g DC24V

*1) XBM-DR16S doesn’t have built-in positioning function.

7


Main Unit | DC power Names and Functions

❶ ❷

Input LED

❾ ❿

Condition LED

Descritpions

Input indication

Red On: Input signal On Red Off: Input signal Off

PWR: Power indication

Red On: Power On Red Off: Power Off

RUN: RUN indication

Green On: PLC Run Green Off: PLC Stop

ERR: Error indication

Red On-and-Off: PLC Error Red Off: PLC Normal condition

Remark

Output LED

Output LED

On: Output signal On Off: Output signal Off

Expansion module connector

Expansion module connector

Connection of expansion module (I/O, Special function, Communication)

❺ ❻

PADT connector Mode switch

PADT connection Mode setting

Connector for XG5000 / XG-PD connection Setting Run / Stop mode of PLC

Input connector / Terminal block

Input wiring connection

-

Output connector / Terminal block

Ouput wiring connection

-

❾ ❿

Built-in RS-485 connector Built-in RS-232C connector Power connector

Built- in RS-485 connection Built-in RS-232C connection Power supply connection

Input specification

Item Input point Rated input voltage Rated input current Operation voltage range Off → On Response time On → Off Common Method

Relay output specification

Item Output point Insulation method Rated load voltage / current Min. load voltage / current Max. load voltage Off leakage current Max. On / Off frequency Mechanical Service life

Electrical

Off → On On → Off Common method Response time

8

Descriptions

Name

No.

RS-485 + /-terminal connection RS-232C T×D, R×D, SG terminal connection DC 24V power supply

XBM-DR16S

XBM-DN16S

XBM-DN32S

8 points

8 points

16 points

DC24 V 4mA (00 ~ 03: 7mA) DC20.4 ~ 28.8V (ripple rate < 5%) 1 / 3 / 5 / 10 / 20 / 70 / 100ms (set by CPU parameter) Default: 3ms 8 points / COM 16 points / COM

XBM-DR16S 8 points Relay insulation DC 24V 2A (Resistive load) / AC 220V 2A (COSØ = 1), 5A / COM DC 5V / 1mA AC 250V, DC 125V 0.1mA (AC 220V, 60Hz) 3,600 times / hr 20millions times or more Rated load voltage / current 100,000 times or more AC 200V / 1.5A, AC 240V / 1A (COSØ = 0.7) 100,000 times or more AC 200V / 1A, AC 240V / 0.5A (COSØ = 0.35) 100,000 times or more DC 24V / 1A, DC 100V / 0.1A (L / R = 7ms) 100,000 times or more 10ms or less 12ms or less 8 points / COM


Programmable Logic Controller

Transistor output specification

Item

XBM-DN16S

XBM-DN32S

8 point

16 point Photo coupler insulation DC 12/24V DC 10.2 ~ 26.4 V 0.2A / 1 point (P 20 ~ 23: 0.1A / Point) 4A / 10ms or less DC 0.4V or less 1ms or less 1ms or less (Rated load, resistive load) 8 point / COM 16 point / COM

Output point Insulation method Rated load voltage Load voltage range Max. load voltage Max. inrush current Max. voltage drop (On) Off → On Response time On → Off Common method Extenal power Voltage supply Current External connection method

DC 12 / 24V ±10% (ripple voltage 4 Vp-p or less) 25mA or less (DC 24V connection) 20pin connector

Wiring (XBM-DR16S)

XBM-DR16S 8-point DC input

8-point Relay output

wiring (XBM-DN16S / DN32S)

Connection cable

Terminal board

Terminal board

Connection cable

XBM-DN16S XBM-DN32S

SLT-CT051-XBM

SLT-CT101-XBM

SLP-T40P

Remark 1. Cable length CT051: 0.5m CT101: 1.0m 2. Board type T40P: Terminal board RY4A: Relay board

9


Main Unit | AC or DC power General Specification

Item

Descriptions

Standard

0 ~ 55 °C - 25 ~ + 70 °C 5 ~ 95%RH (Non-condensing) 5 ~ 95%RH (Non-condensing) Ocnasional vibration Frequency Acceleration Pulse width 0.075mm 10 ≤ f < 57Hz 10 times each Vibration resistance 57 ≤ f ≤ 150Hz 9.8m/s2 (1G) IEC61131-2 direction Continuous vibration (X, Y and Z) Frequency Acceleration Pulse width 0.035mm 10 ≤ f < 57Hz 57 ≤ f ≤ 150Hz 4.9m/s2 (0.5G) •Peak Acceleration: 147m/s2 (15g) •Duration: 11ms Shock resistance IEC61131-2 •Pulse waveform: Half-sine, 3times each direction per each axis Square wave impulse noise ±1,500 V LSIS Standard Electrostatic discharge IEC61131-2 / IEC61000-4-2 4kV Radiated 80 ~ 1000 MHz, 10V/m Noise resistance IEC61131-2 / IEC61000-4-3 lectromagnetic field noise Main unit Expansion module Fast transient/ Burst noise IEC61131-2 / IEC61000-4-4 2kV 1kV Operating Ambience Free from corrosive gases and excessive dust Altitude Up to 2,000m Pollution level *1) Less than 2 Cooling Air-cooling Ambient temperature Storage temperature Ambient humidity Storage humidity

XBC-DR32H XBC-DN32H XBC-DR32H/DC XBC-DN32H/DC XEC-DR32H XEC-DN32H

*1) Pollution level indicates the degree to which conductive material is generated in the environment where the equipment is used. Pollution level 2 is the condition that only non-conductive pollution occurred but temporary conductivity may be produced due to condensing.

Performance Specification

XBC-DR64H XBC-DN64H XBC-DR64H/DC XBC-DN64H/DC XEC-DR64H XEC-DN64H

XBC-DN64H XBC-DN32H XBC-DR64H XEC-DN64H*1) XEC-DN32H*1) XEC-DR64H*1) XBC-DN64H/DC XBC-DN32H/DC XBC-DR64H/DC Repetitive, cyclic, interrupt, constant scan Control method Refresh mode (Batch processing by scan synchronization) I/O control mode Direct mode by instruction Programming language Ladder diagram or IEC standard (LD, SFC, ST)*1) Processing speed 83ns / Step (for basic instruction) Program capacity 15k step (IEC type 200KB) Max. I/O points 352 points(Main + 10 expansions) 384 points (Main + 10 expansions) 128 Number of program Operation mode RUN, STOP, DEBUG Operation delay monitoring, memory error, I/O error, battery error, power error, etc. Self diagnosis USB (Rev 1.1), RS-232C Program port Latch range setting at Basic parameter Data retension at power failure RS-232C / 485, High-speed counter, PID control, Pulse catch, Input filter Built-in function External interrupt, Positioning Built-in RTC 660mA 260mA 1040mA 330mA Internal current consumption 600g 500g 900g 800g Weight AC 100 ~ 240V or DC24V Rated voltage Data memory XEC(IEC type) XBC Symbolic variablearea (A) 32KB (Max.16K byte retain setting available) P P0000 ~ P1023F (16,384 points) Input variable (I) M M0000 ~ M1023F (16,384 points) 2KB (%IX15.15.63) Output variable (Q) K K0000 ~ K4095F(Special area: K2600~2559F) (65,536 points) 2KB (%QX15.15.63) M 16KB (Max.8K byte retain setting available) L L00000 ~ L2047F (32,768 points) Direct variable 20KB (1block) R F F000 ~ F1023F (16,384 points) W T 100ms, 10ms, 1ms: T000 ~ T1023(Changeable by Parameter setting) 20KB 2KB C C000 ~ C1023 F S S00.00 ~ S127.99 K 8KB Flag variable D D0000 ~ D10239 (10,240 word) L 4KB U U00.00 ~ U0A.31 (Analog data refresh area: 352) N 10KB U Z Z000 ~ Z127 (128 word) 1KB 20KB, 2blocks (Using R device) N N0000 ~ N5119 (5,120 word) Flash area Item

XBC-DR32H XEC-DR32H*1) XBC-DR32H/DC

*1) Only main unit for IEC standard language

10


Programmable Logic Controller

Names and Functions ❾

Name

No.

❶ Input LED

XBC-DR64H XBC-DN64H

Remark

Red On: Input signal On Red Off: Input signal Off Red On: Power On Red Off: Power Off Green On: PLC Run Green Off: PLC Stop

PWR: Power indication RUN: RUN indication

❷ Condition LED

Descritpions

Input indication

❹ ❺ ❻

Descriptions

ERR: Error indication

Red On-and-Off: PLC Error Red Off: PLC Normal condition

❸ Output LED

Output LED

On: Output signal On Off: Output signal Off

❹ Expansion module connector ❺ PADT connector ❻ Mode switch ❼ Input Terminal block ❽ Output Terminal block ❾ Built-in RS-485 connector ❿ Built-in RS-232C connector Power terminal

Expansion module connector

Connection of expansion module (I/O, Special function, Communication)

PADT connection Mode setting Input wiring connection Ouput wiring connection Built-in RS-485 connection Built-in RS-232C connection Power supply terminal

Connector for XG5000 / XG-PD connection Setting Run/Stop mode of PLC RS-485 + /-terminal connection RS-232C T×D, R×D, SG terminal connection AC 110-220V power supply

Input Specification

XBC-DR32H XEC-DR32H

Item Input points Rated input voltage Rated input current Operation voltage range On voltage / On current Off voltage / Off current Input resistance Response time

Off → On On → Off

Weight

Relay output specification

XBC-DN32H XEC-DN32H

Item

Service life

Response time

Electrical

Off → On On → Off

Common method

XBC-DN64H XEC-DN64H

16 points

32 points DC 24V 4mA (Contact 0~7: 9mA) DC 20.4 ~ 28.8V (Ripple rate < 5%) DC 19V or more / 3mA or more DC 6V or less / 1mA or less 5.6kΩ(P00 ~ P07: 2.7kΩ)

1 / 3 / 5 / 10 / 20 / 70 / 100 ms (Setting by CPU parameter) Initial value: 3ms 600g

Output point Insulation method Rated load voltage / current Min. load voltage / current Max. load voltage Off leakage current Max. On / Off frequency Mechanical

XBC-DR64H XEC-DR64H

500g

900g

800g

XBC-DR32H/XEC-DR32H

XBC-DR64H/XEC-DR64H

16 points

32 points

Relay insulation DC 24V 2A (Resistive load) / AC 220V 2A (COSØ = 1), 5A / COM DC 5V / 1mA AC 250V, DC 125V 0.1mA (AC 220V, 60Hz) 3,600 times / hr 20millions times or more Rated load voltage / current 100,000 times or more AC 200V / 1.5A, AC 240V / 1A (COSØ = 0.7) 100,000 times or more AC 200V / 1A, AC 240V / 0.5A (COSØ = 0.35) 100,000 times or more DC 24V / 1A, DC 100V / 0.1A (L / R = 7ms) 100,000 times or more 10ms or less 12ms or less 4 points / COM

P20 ~ 2F: 4 points / COM P30 ~ 3F: 8 points / COM

11


Main Unit | AC power Transistor output specification

Item Output point Insulation method Rated load voltage Load voltage range Max. load voltage Off leakage current Max. inrush current Max. voltage drop (On) Surge absorber Off → On Response time On → Off

XBC-DN32H/XEC-DN32H XBC-DN64H/XEC-DN64H 16 points 32 points Photo coupler insulation DC 12 / 24V DC 10.2 ~ 26.4 V 0.5A / 1point (P 20 ~ 23: 0.1A / point) 0.1mA or less 4A / 10ms or less DC 0.4V or less Zener Diode 1ms or less 1ms or less (Rated load, resistive load) P20 ~ 2F: 4 points / COM 4 points / com P30 ~ 3F: 8 points / COM DC 12 / 24V ± 10% (ripple voltage 4 Vp-p or less) 10mA or less (DC 24V connection)

Common method External power supply

Voltage Current

Input wiring (XBC-DR32H / XBC-DN32H XEC-DR32H / XEC-DN32H)

RX

TX

SG

485+ 485-

P01

P03

P02

P00

P05

P04

P07

P06

P09

P08

P0B

P0A

P0D

P0F

24G

POC POE COM

24V

Input wiring (XBC-DR64H / XBC-DN64H XEC-DR64H / XEC-DN64H)

RX

TX SG P01 P03 P05 P07 P09 P0B P0D POF NC P11 P13 P15 P17 P19 P1B P1D P1F 24G

485+ 485- P00 P02 P04 P06 P08 P0A P0C P0E COM0 P10 P12 P14 P16 P18 P1A P1C P1E COM1 24V

Relay output wiring (XBC-DR32H/XEC-DR32H)

AC100 ~ 240V FG

12

P20 NC

P22 COMO P25

P21

P23

P24

P27

P28 P2A COM2 P2D P2F

P26 COM1 P29

P2B P2C

P2E COM3


Programmable Logic Controller

Transistor output Wiring (XBC-DN32H/XEC-DN32H)

AC100 ~ 240V FG

P20 P

P21

P22 COMO P25 P23

P24

P27

P28

P26 COM1 P29

P2A COM2 P2D P2B

P2C

P2F

P2E COM3

Relay output Wiring (XBC-DR64H/XEC-DR64H)

AC100 240V

P20 P22 COM0 P25 P27 P28 P2A COM2 P2D P2F P30 P32 P34 P36 COM4 P39 P3B P3D P3F

FG

NC P21 P23 P24 P26 COM1 P29 P2B P2C P2E COM3 P31 P33 P35 P37 P38 P3A P3C P3E COM5

Transistor output wiring (XBC-DN64H/XEC-DN64H)

AC100 ~ P20 P22 COM0 P25 P27 P28 P2A COM2 P2D P2F P30 P32 P34 P36 COM4 P39 P3B P3D P3F 240V FG

P

P21 P23 P24 P26 COM1 P29 P2B P2C P2E COM3 P31 P33 P35 P37 P38 P3A P3C P3E COM5

13


Built-in functions | High-speed counter Terminal (XBM)

1-Phase

Terminal number

Encoder

Signal name CH0 counter input CH1 counter input CH2 counter input CH3 counter input Ch0 preset 24V Ch1 preset 24V Ch2 preset 24V Ch3 preset 24V Input COMMON

000 001 002 003 004 005 006 007 COM0

2-Phase Description Counter input Counter input Counter input Counter input Preset input Preset input Preset input Preset input COMMON

Signal name Ch0 A-phase input Ch0 B-phase input Ch2 A-phase input Ch2 B-phase input Ch0 preset 24V Ch2 preset 24V Input COMMON

Description A-phase input B-phase input A-phase input B-phase input preset input preset input COMMON

High-speed counter One phase:4Ch,20kpps Two phase :2Ch,10kpps

Terminal (XBC/XEC)

High-speed counter One phase: 100kpps 4ch, 20kpps 4ch Two phase: 50kpps 2ch, 10kpps 2ch

Terminal number(XBC) P000 P001 P002 P003 P004 P005 P006 P007 P008 P009 P00A P00B P00C P00D P00E P00F COM0

1-Phase Signal name CH0 counter input CH1 counter input CH2 counter input CH3 counter input CH4 counter input CH5 counter input CH6 counter input CH7 counter input Ch0 preset 24V Ch1 preset 24V Ch2 preset 24V Ch3 preset 24V Ch4 preset 24V Ch5 preset 24V Ch6 preset 24V Ch7 preset 24V Input COMMON

2-Phase Description Counter input Counter input Counter input Counter input Counter input Counter input Counter input Counter input Preset input Preset input Preset input Preset input Preset input Preset input Preset input Preset input COMMON

Signal name Ch0 A-phase input Ch0 B-phase input Ch2 A-phase input Ch2 B-phase input Ch4 A-phase input Ch4 B-phase input Ch6 A-phase input Ch6 B-phase input Ch0 preset 24V Ch2 preset 24V Ch4 preset 24V Ch6 preset 24V Input COMMON

Description A-phase input B-phase input A-phase input B-phase input A-phase input B-phase input A-phase input B-phase input preset input preset input preset input preset input COMMON

Wiring

Voltage output encoder

14

Open collector encoder


Programmable Logic Controller

Performance Specification

Item Count input signal

Signal Input type Signal level

Max. counting speed

Number of channels Counting range Count mode (Program setting) Input mode (Program setting) Signal type 1 phase input Up/Down setting

2 phase input CW/CCW 1 phase input

Multiplication function

2 phase input

Control input

CW/CCW Signal Signal level Signal type Output points

External output

Input Specification

Description A-phase, B-phase Voltage input (Open collector) 24V XBM: One phase: 20kpps 4ch Two phase: 10kpps 2ch XBC: One phase: 100kpps 4ch, 20kpps 4ch Two phase: 50kpps 2ch, 10kpps 2ch XBM: 4 channels (In case of 2-phase, 2 channels available) XBC: 8 channels (In case of 2-phase, 4 channels available) Signed 32 Bit (-2,147,483,648 ~ 2,147,483,647) Linear count (if 32-bit range exceeded, Carry/Borrow occurs) Ring count (repeated count within setting range) 1-phase input 2-phase input CW/CCW input Voltage Increasing/Decreasing operation setting by B-phase input Increasing/Decreasing operation setting by program Automatic setting by difference in phase A-phase input: increasing operation B-phase input: decreasing operation 1 multiplication 4 multiplication 1 multiplication Preset instruction input DC 24V input type Voltage 1 point/channel (for each channel): terminal output available (XBC: 2points)

Type

Select single-compared (>, >=, =, =<, <) or section compared output (included or excluded) (program setting)

Output type

Relay, Open-collector output (Sink)

Count Enable

To be set through program (count available only in enable status)

Preset function Auxiliary mode

To be set through terminal (contact) or program Count latch

Item Input voltage Input current On voltage (min.) Off voltage (max.)

Description 24V DC (20.4V ~ 28.8V) 4mA 20.4V 6V

15


Built-in functions | Positioning Terminal (XBM) Pin layout

Item

Pin number

Pulse Pulse output (Open collector) Direction Pulse output (Open collector) Output DC 24V External 24V power supply A9/A10 Output COM External 24V GND B9/B10 Limit L A1 A3 Low limit Limit H A2 A4 High limit DOG A5 A7 Near point Zero A6 A8 Zero signal (+24V) Input Input COM Common A9/A10, B9/B10

Servo/Stepping drive Servo/Stepping motor

Positioning Max.2channels,100kpps

Terminal (XBC/ XEC) Pin layout

Item

Pin number(XBC)

X axis P0008 P0009 P000C Input P000D

Y axis P000A P000B P000E P000F

Signal name

Limit L Low limit Limit H High limit DOG Near point Origin Zero signal (+24V) Input COM Common COM Pulse Pulse/CW (Open collector) P0020 P0021 Output P0022 P0023 Direction Direction/CCW (Open collector) DC12V External power supply P Output COM External 24V GND COMO

Servo/Stepping drive Servo/Stepping motor

Positioning Max.2channels,100kpps

Performance Specification

Item

Edge Edge Edge Edge -

→ → → → ← ← ← ← ←

Direction of positioning Operating signal to external condition ← ← ← ← ← → → → →

7.4mA 24/V

DC5~24V

Description

No. of control axis Interpolation

2 axes 2-axis linear interpolation

Control mode

Position control, Speed control, Speed/Position switching control, Position/speed switching control

Control unit

Pulse

Positioning data

30-step pattern for each axis (XBC: 80step) (operation step number : 1 ~ 30, XBC : 1~80)

Positioning monitor

Dedicated monitoring function for positioning in XG5000 Permanent Backup of downloaded parameter (FLASH memory) 2-month Super Cap.Backup of parameter/data modified during operation(XBM)Battery back-up (XBC) Permanent Backup of parameter/data in RAM by instruction (FLASH memory) Absolute / incremental method -2,147,483,648 ~ 2,147,483,647 1 ~ 100,000 (pulse/sec)

Back-up Positioning method Positioning range Speed range Positioning Acceleration / Deceleration type Acceleration / Deceleration time Max. output pulse Max. distance of connection

16

Direction of positioning Operating condition signal to external

Signal name

X axis Y axis A1 A2 A3 A4

Trapezoidal acceleration / deceleration 1 ~ 10,000㎳ (4 patterns each can be set) 100 Kpps 2m


Programmable Logic Controller

Electrical specification Signal

Rated input Load voltage Max. load Max. voltage Leakage Response voltage range current/inrush current drop (On) current (Off) time

Output Output pulse Signal Input

Wiring

DC 5~24V

DC 4.75~26.4V

Rated input Load voltage voltage/current range

External high limit DC 24V/7mA External low limit Approximate zero DC 24V/4mA zero

DC 20.4 ~ 28.8V

100mA(1 point) 1A/10ms or less

DC 0.3V or less

0.1mA or less

100㎲ or less

On voltage/current

Off voltage/current

Input resistance

Response time

DC 19V/5.7mA or more

DC 6V/1.8mA or less

3.3Ω

DC 19V/3.4mA or more

DC 6V/1.1mA or less

5.6Ω

0.5ms or less

Wiring with DC 5V

Wiring with DC 24V

17


Built-in functions | PID/Pulse catch/Input filter/Task Performance Specification (PID)

Item No. of control loop Control mode Control period Forward/Reverse Mixed control Function

Pulse catch

Description 16-loop independent control P control, PI control, PD control, PID control 10ms ~ 6,563.5ms (Setting unit: 0.1ms) Switching control direction automatically when exceeding dead band

Cascade SV Ramp

Improved control precision by serial connection between Master loop and Slave loop Preventing overload caused by excessive SV change by setting variation slope

Alarm

Improved control stability with various alarm function such as MV high limit/low limit, PV high limit/low limit, PV variation width

Auto tuning Additional function

Auto tuning with improved auto-tuning algorithm PWM output, PV Tracking, ▵MV, ▵PV, etc

When the On-condition time of input signal (P0000~P0007) is shorter than 1 scan time (Min. 50㎲), Pulse catch processes the input signal as normal input.

External input signal Input image data Item No. of setting points Min. pulse width

Input filter

XBM 8 points: P000 ~ P007 50㎲

XBC 4 points: P000 ~ P003 10㎲

4 points: P004 ~ P007 50㎲

Input filter prevents processing of the input signal that is shorter than the filtering time. (Filtering time is set by parameter) In the application site where noise is frequently generated, input filter prevents wrong input caused by noise.

External input signal Input image data Item No. of setting points Input filtering time setting Setting range

Task

Description Every input contact Assigning for each module 1 ~ 100㎳ (1,3,5,10,20,70,100)

Task function is the processing method of internal/external signal generated preriodically or aperiodically. (Total 24 task can be assigned.) It stops operation of scan program for the moment and then execute the assigned task.

Types of Task 1. Initialization task setting Running a task one time before INIT_DONE at initial execution

2. Fixed-cycle task setting Item No. of setting points Setting range

Description 8 points 1~42,94,967,295ms

3. External points task setting XBM XBC Item No. of setting points P000 ~ P007 P000 ~ P003 P004 ~ P007 Min. pulse width 50㎲ 10㎲ 50㎲ Up, Down, Change Condition

18

4. Internal device task setting Item No. of setting points Condition

Description 8 points Up, Down, Change, On, Off


Expansion | DC Input

Programmable Logic Controller

Specification

Model

Specification Input point

XBE-DC08A 8 points

Rated input voltage / current

XBE-DC32A

16 points

32 points

DC 24V / 4mA

Operation voltage range

DC 20.4 ~ 28.8V (Ripple rate < 5%)

Input resistance Response time

XBE-DC16A

5.6kΩ Off → On

On → Off Insulation pressure

1 / 3 / 5 / 10 / 20 / 70 / 100ms (setting by CPU parameter) Initial value: 3ms AC 560Vrms / 3 Cycle (altitude 2000m)

Insulation resistance

10MΩor more by megger

COMMON method Internal current consumption

8 points / COM

16 points / COM

32 points / COM

30mA

40mA

50mA

XBE-DC08A XBE-DC16A XBE-DC32A

Wiring (XBE-DC08A / DC16A)

8-point DC input

16-point DC input

XBE-DC08A

XBE-DC16A

19


Expansion | DC Input Wiring (XBE-DC32A)

PLC

Smart Link

Pin number B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B09 B08 B07 B06 B05 B04 B03 B02 B01

Input wiring with Smart Link (XBE-DC32A)

20

Terminal number

XBE-DC32A A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A09 A08 A07 A06 A05 A04 A03 A02 A01

SLP-T40P

00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F NC NC

10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F NC NC

COM

COM

A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8 A9 B9 A10 B10

A11 B11 A12 B12 A13 B13 A14 B14 A15 B15 A16 B16 A17 B17 A18 B18 A19 B19 A20 B20


Expansion | Transistor Output Specification

Model

Specification

Programmable Logic Controller

XBE-TN08A XBE-TP08A XBE-TN16A XBE-TP16A XBE-TN32A XBE-TP32A Sink

Type

Source 8 point

Output point

DC 10.2 ~ 26.4 V

DC 0.4V

Off → On

1mA or less

On → Off

Common method Internal current consumption Voltage External Power supply

0.2A / 1point, 2A / COM 0.1mA or less

Max. voltage drop (On) Response time

Source 32 point

Load voltage range 0.2A / 1point

Sink

16 point DC 12 / 24V

Off leakage current

Wiring (XBE-TN08A / TN16A)

Source

Rated load voltage Max. load current

XBE-TN08A XBE-TN16A XBE-TN32A

Sink

Current

1mA or less (Rated load, resistive load) 8 points / COM

16 points / COM

32 points / COM

40mA

60mA

120mA

DC 12 / 24V ± 10% (Ripple voltage ≤ 4 Vp-p) 20mA or less 10mA or less (DC 24V connection) (DC 24V connection)

8-point sink Output

16-point sink Output

XBE-TN08A

XBE-TN16A

21


Expansion | Transistor Output Wiring (XBE-TN32A)

PLC

Smart Link

Pin number B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B09 B08 B07 B06 B05 B04 B03 B02 B01

SLP-T40P Output wiring (XBE-TN32A)

Terminal number

SLP-RY4A Output wiring (XBE-TN32A)

Terminal number

22

XBE-DC32A A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A09 A08 A07 A06 A05 A04 A03 A02 A01

SLP-T40P

00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F NC NC

10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F NC NC

DC 12 / 24V

COM

A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8 A9 B9 A10 B10

A11 B11 A12 B12 A13 B13 A14 B14 A15 B15 A16 B16 A17 B17 A18 B18 A19 B19 A20 B20


Expansion | Relay Output Specification

Model Specification Output point Insulation method Rated input voltage / current Min. load voltage / current Max. load voltage Off leakage current Max. on / off frequency Surge absorber Mechanical Service life

Response time XBE-RY08A XBE-RY16A

Wiring (XBE-RY08A / RY16A)

Programmable Logic Controller

Electrical Off → On On → Off

COMMON method Internal current consumption Operation indicator External connection method

XBE-RY08A

XBE-RY16A

8 points

16 points Relay insulation DC 24V 2A (resisitive load) / AC 220V 2A (COSΨ = 1), 5A /COM DC5V 1mA AC 250V, DC 125V 0.1mA (AC 220V, 60Hz) 3,600 times / hr None 20million times or more Rated load voltage / current 100,000 times or more AC 200V / 1.5A, AC 240V / 1A (COSΨ = 0.7) 100,000 times or more AC 200V / 1A, AC 240V / 0.5 (COSΨ = 0.35) 100,000 tiems or more DC 24V / 1A, DC 100V / 0.1A (L / R = 7ms) 100,000 times or more 10ms or less 12ms or less 8 points / 1COM 230mA 420mA Output On, LED On 9-pin terminal block connector 9-pin terminal block connector × 2

8-point Relay Output

16-point Relay Output

XBE-RY08A

XBE-RY16A

23


Expansion | DC Input / Relay output DC Input Specification

Model Specification Input point Insulation method Rated input voltage Rated input current Operation voltage range On voltage / On current Off voltage / Off current Input resistance Off → On Response time On → Off COMMON method Weight

DC Input (XBE-DR16A) 8 points Photo coupler DC24V 4mA DC20.4 ~ 28.8V (Ripple rate < 5%) DC19V or more / 3mA or more DC6V or less / 1mA or less 5.6kΩ 1 / 3 / 5 / 10 / 20 / 70 / 100ms (setting by CPU parameter) init value: 3ms 8 points / COM 81g

XBE-DR16A

Relay Output Specification

Model Specification Output point Insulation method Rated input voltage / current Min. load voltage / current Max. load volfage Off leakage current Max. on / off frequency Surge absorber Mechanlcal Service life

Response time

Electrical Off → On On → Off

COMMON method Internal current consumption Operation indicator External connection method

Relay output (XBE-DR16A) 8 points Relay insulation DC 24V 2A (resisitive load) / AC 220V 2A (COSΨ = 1), 5A /COM DC5V 1mA AC 250V, DC 125V 0.1mA (AC 220V, 60Hz) 3,600 times / hr None 20million times or more Rated load voltage / current 100,000 times or more AC 200V / 1.5A, AC 240V / 1A (COSΨ = 0.7) 100,000 times or more AC 200V / 1A, AC 240V / 0.5 (COSΨ = 0.35) 100,000 tiems or more DC 24V / 1A, DC 100V / 0.1A (L / R = 7ms) 100,000 times or more 10ms or less 12ms or less 8 points / 1COM 250mA Output On, LED On 9-pin terminal block connector

Wiring (XBE-DR16A) 8-point DC input

24

8-point Relay Output


Expansion | Analog Input Specification

Item

Analog range selection

Digital data

Resolution

Names and Functions

Max. conversion speed Max. absolute input Accuracy Analog Input channels Insulation method Connection terminal Occupied I/O points DC 5V Current consumption DC 24V

No.

XG5000 I/O Parameter Analog range 0 ~ 10V 4 ~ 20mA 0 ~ 20mA Unsigned value 0 ~ 4000 Signed value -2000 ~ 2000 Precise value 0 ~ 1000 400 ~ 2000 0 ~ 2000 Percentile value 0 ~ 1000 Data format of digital output is set by user program or I/O parameter (Setting for each channel is available.) Resolution Resolution Analog input Analog input (1 / 4000) (1 / 4000) 4 ~ 20mA 2.5mV 0 ~ 10V 5.0㎂ 0 ~ 20mA 1.5ms / channel ±15V ±25mA ±0.5% or less 4 channel / module Photocoupler insulation between I/O terminal and power supply 11-point terminal block Fixed type: 64 points 120mA 62mA

Name

Descriptions

❸ Terminal block

▶ Indicates condition of module •LED On: Normal condition •LED On and Off: Error •LED Off: Power Off or module malfunction ▶ Voltage / Current selection switch •V: Voltage input selection •I: Current input selection ▶ External device connection

❹ External power supply terminal

▶ External DC 24V input

❶ RUN LED

❷ Input selection S/W

Wiring

XBF-AD04A DC 0 ~ 10 V (input resistance: 1MΩ min.) DC 4 ~ 20mA, DC 0 ~ 20mA (input resistance 250Ω)

Analog range ❶

XBF-AD04A

Programmable Logic Controller

Wiring with 2-wire sensor

Wiring with 4-wire sensor

※Use 22AWG, 2 conductor, twist shielded cable when wiring between analog module and external device.

25


Expansion | Analog Output Specification

Item Analog range

Analog range Selection Output range Unsigned value Signed value Digital data Precise value Percentile value Data format Resolution

XBF-DV04A XBF-DC04A

Names and Functions

Max. conversion speed Max. absolute output Accuracy Analog output channels Insulation method Connection terminal Occupied I/O points DC 5V Current consumption DC 24V

XBF-DV04A

DC 0 ~ 10 V 4 ~ 20mA / 0 ~ 20mA (Load resistance ≥ 2kΩ) (Load resistance ≤510Ω) XG 5000 I/O parameter 0 ~ 10 V 4 ~ 20mA / 0 ~ 20mA 0 ~ 4000 0 ~ 4000 - 2000 ~ 2000 - 2000 ~ 2000 0 ~ 1000 400 ~ 2000 / 0 ~ 2000 0 ~ 1000 0 ~ 1000 Data format of digital input is set by user program or I/O parameter (Setting for each channel is available.) Resolution (1 / 4000) 2.5mV 5㎂ 1ms / channel ±15V ±25mA ±0.5% or less 4 channel / module Photocoupler insulation between I/O terminal and power supply 11-point terminal block Fixed type: 64 points 110mA 110mA 70mA 120mA

Name

No.

XBF-DC04A

Descriptions

❷ Terminal block

▶ Indicates condition of module •LED On: Normal condition •LED On and Off: Error •LED Off: Power Off or module malfunction ▶ External device connection

❸ External power supply terminal

▶ External DC 24V input

❶ RUN LED

Wiring 2kΩ or more

XBFDV04A

26

2kΩ or more

510Ω or less

XBFDC04A

510Ω or less


Expansion | Analog Input/Analog Output

Programmable Logic Controller

Specification

XBF-AH04A

Item ❶ ❷ ❽

Analog channel

Analog range ❸ ❹

Analog range Selection Unsigned value Signed value Digital data Precise value

Percentile value Resolution(1/4000)

XBF-AH04A

Names and Functions

Max. conversion speed Max. absolute output Accuracy Insulation method Connection terminal Occupied I/O points Current DC 5V consumption DC 24V

No.

❷ OUTPUT LED

❸ Input selection S/W ❹ Output selection S/W ❻

Terminal block

❼ External power supply terminal ❽ Expansion connector

Wiring

Output

2 channels

2 channels

DC 1 ~ 5V, DC 0 ~ 5V, DC 0 ~ 10V (Input resistance: 1 MΩmin.)

DC 1 ~ 5V, DC 0 ~ 5V, DC 0 ~ 10V (Load resistance ≥ 2kΩ)

DC 4 ~ 20mA, DC 0 ~ 20mA (Input resistance 250Ω)

DC 4 ~ 20mA, DC 0 ~ 20mA (Load resistance ≤510Ω)

XG 5000 I/O parameter and External switch 0 ~ 4000 -2000 ~ 2000 100 ~ 500 (DC 1 ~ 5V), 0 ~ 500 (DC 0 ~ 5V), 0 ~ 1000 (DC 0 ~ 10V) 400 ~ 2000 (DC 4 ~ 20mA), 0 ~ 2000 (DC 0 ~ 20mA) 0 ~ 1000 1.25mV (DC 1~5V, 0~5V), 2.5mV (DC 0~10V) 5 (DC4~20mA, 0~20mA) ±15V, 25mA 1ms / channel ±0.5% or less Photocoupler insulation between I/O terminal and power supply 11-point terminal block Fixed type: 64 points 120mA 130mA

Name

❶ INPUT LED

Input

Descriptions ▶ Indicates input condition of module •LED On: Normal condition •LED On and Off: Error •LED Off: Power Off or module malfunction ▶ Indicates output condition of module •LED On: Normal condition •LED On and Off: Error •LED Off: Power Off or module malfunction ▶ Voltage / Current selection switch for input ▶ Voltage / Current selection switch for output ▶ Terminal for external input device ▶ Terminal for external output device ▶ Terminal for external DC 24V input ▶ Terminal for expansion

Wiring with 2-wire sensor (for analog input)

Wiring with 4-wire sensor (for analog input)

※Use 22AWG, 2 conductor, twist shielded cable when wiring between analog module and external device.

27


Expansion | RTD Specification ❶ ❷

Item Number of channels PT 100 Sensor Type JPT 100 PT 100 Temperature range JPT 100 PT 100 Digital JPT 100 output Scaling 25℃ Accuracy 0 ~ 55℃ Conversion speed Wiring method DC 5V Current consumption DC 24V

XBF-RD04A 4 JIS C1804-1997 JIS C1604-1981, KS C1603-1991 - 200 ~ 600℃ - 200 ~ 600℃ - 2000 ~ 6000 - 2000 ~ 6000 0 ~ 4000 ±0.3% or less ±0.5% or less 40ms / Ch 3Wire 100mA 100mA

XBF-RD04A

Names and Functions

No.

Name

RUN LED

ALM LED

❸ ❹ ❺

Terminal block External power terminal Expansion connector

Descriptions ▶ Displays the hardware operation status (Fatal fault) •On: Normal status •Flickering: Error (0.2s flickering) •Off: hardware error or power off ▶ Displays the status of the channels (Light fault) •Flickering: Line disconnection (1s flickering) •Off: Normal status ▶ 3-wire RTD sensors can be connected ▶ Supplies the external DC 24V ▶ Connects the module with an expansion module

Wiring

Terminal

2 Wire

28

Terminal

3 Wire

Terminal

4 Wire


Expansion | Thermocouple Specification

Programmable Logic Controller

Item Number of channels ❶ ❷

Input sensor type K J T R Temperature display unit Digital output Scaling display (Defined by user) Normal temperature (25℃) Accuracy Temperature coneffcient (0 ~ 55℃) Max. conversion speed Warming-up time Terminal I/O points occupied DC 5V Current consumption DC 24V Temperature Input range

XBF-TC04S 4 Thermocouple K / J / T / R JIS C1602-1995 - 200.0℃ ~ 1300.0℃ (-328.0℉ ~ 2372.0℉) - 200.0℃ ~ 1200.0℃ (-328.0℉ ~ 2192.0℉) - 200.0℃ ~ 400.0℃ (-328.0℉ ~ 752.0℉) 0.0℃ ~ 1700.0℃ (32.0℉ ~ 3092.0℉) Display down to one decimal place K, J, T: 0.1℃ R: 0.5℃ Unsigned scaling (0 ~ 65535) Signed scaling (-32768 ~ 32767) ±0.2% ±100 ppm / ℃ 50ms / Channel 15 minutes or more 11-point terminal 64 points 100mA 100mA

XBF-TC04S

Names and Functions

No.

Name

RUN LED

ALM LED

❸ ❹ ❺ ❻

Terminal block External power terminal Expansion connector RJC

Descriptions ▶ Displays the hardware operation status (Fatal fault) •On: Normal status •Flickering: Error (0.2s flickering) •Off: hardware error or power off ▶ Displays the status of the channels (Light fault) •Flickering: Line disconnection (1s flickering) •Off: Normal status ▶ Terminals to connect the thermo-couple sensor ▶ Terminals to supply the external DC 24V ▶ Terminal to connect the expansion modules ▶ Device for reference junction compensation

Wiring Module

Compensation cable

Terminals

Shield cable

Sensor

29


Expansion | Positioning module Specification ❶

Item N0. of control axis Pulse output type Max. pulse output Max. connection length Control mode Interpolation Positioning data Configuration tool Back-up

Positioning method Unit Positioning range Speed range Acceleration/Deceleration type Acceleration/Deceleration time

Positioning

XBF-PD02A

Names and Functions

Max. encoder input Error/Operation Occupied / O points (XBC) Connection terminal Current consumption

No.

Name

RUN LED

Terminal block

Terminal

Descriptions 1. RUN ▶ Displays the hardware operation status •On: Normal status •Off: Abnormal status 2. X_AXIS, Y_AXIS •On: Operation •Flickering: Error ▶ Terminals to connect the MPG, external device and drive device.

Pin number X axis

B A 20 19 18 17 16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01

30

XBF-PDO2A 2 axis Line drive 2Mpps 10m Position control, Speed control, Speed / Position switching control, Position / Speed switching control linear interpolation, Circula interpolation 150 operation data for each axis Built-in function parameter of XG5000 Flash memory Absolute / incremental method pulse - 2,147,483,648 ~ 2,147,483,648 1~2,000,000(pulse/초) Trapezoidal acceleration / deceleration 0~65,535ms, Asymmetric acceleration / deceleration 200kpps(Line drive) LED Fixed type: 64points 40pin connector 500mA

B20 A20 B19 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A09 A08 A07 A06 A05 A04 A03 A02 A01

Signal name

Y axis

B18 B17 B16 B15 B14 B13 B12 B11 B10 B09 B08 B07 B06 B05 B04 B03 B02 B01

MPG A+ MPG AMPG B+ MPG BFP+ FPRP+ RPOV+ OVDOG

MPG/Encoder A+ input MPG/Encoder A- input MPG/Encoder B+ input MPG/Encoder B- input Forward pulse+ Forward pulseReverse pulse+ Reverse pulseHigh limit Low limit Near point

NC

-

COM NC INP INP COM CLR CLR COM HOME +5V HOME COM NC

Common Inposition signal Inposition signal common Deviation counter clear signal Deviation counter clear signal common Zero signal(DC5V) Zero signal Common -


Expansion | Communication Ethernet (XBL-EMTA)

Programmable Logic Controller

Item Communication spec. Protocol With LS PLCs With other devices Service Application

XBL-EMTA

HS link sending / receiving data

10 / 100 Base-TX TCP / IP, UDP / IP High-speed link, P2P service P2P service Dedicated protocol service, XG5000 service 200words / block (Max.64blocks)

No. of channel connectable to upper stage

6 channels

Service

Communication with PC (HMI) and external devices, High-speed communication among LSIS PLCs

Media Current consumption

UTP / STP Category 5 300mA

XBL-EMTA

RS-232C, RS-422 / 485

Item Interface MODEM Function Dedicate XG5000 mode Mode P2P Operation Server (slave) Mode Client (master) Start Bit Data Bit Data format Stop Bit Parity Setting

XBL-C21A XBL-C41A

Synchronous Speed (bps) Station number Distance MODEM communication Network Diagnostic Max. expansion

Built-in RS-232C

XBL-C21A

Built-in RS-485

XBL-C41A

RS-232C 1Ch RS-232C 1Ch RS-485 1Ch RS-422 / 485 1Ch Remote communication via the external MODEM (XBL-C21A Only) 1:1 or 1:N via the dedicated protocol Program download, upload and control via the remote control Communication defined by the protocol using XG-PD XGT / Modbus master XGT / Modbus Server, User-defined communication XGT / Modbus P2P Master, User-defined communication 1 7 or 8 1 or 2 Even / Odd / None Setting by XG-PD parameter Asynchronous 1,200 / 2,400 / 4,800 / 9,600 / 19,200 / 38,400 / 57,600 / 115,200 bps Setting by XG-PD, Max. 32 stations RS-232C: Max.15m (Expansion by MODEM), RS-422/485: Max 500m Support 1: 1 Via LED and XG-PD Built-in

1: N 2 stages

Built-in

2 stages

31


Software XG5000 (Programming software)

•Program editing & Engineering software •Windows-based easy operation •Multi-PLC, Multi-programming support •Various monitoring and diagnosis functions •Windows 2000, XP (Limited use in Windows 98, ME)

Variable Monitor

Ladder Monitor

Forced I/O

Trend Monitor

XG -PD (Network setting software)

Special Module Monitor

•Convenient network setting •Extended monitoring funchion for network system and communication modules •Fast interface with CPU by effective network management •Various bult-in diagnosis, functions (CPU condition, Link conditon, Service condition, Frame monitoring) Parameter setting

Network Scan

Link Monitoring

Fast Ethernet

XGT Panel Cnet Other PLC

Smart I/O LS Inverter

Frame Monitoring

32

Other net devics

Service Condition Monitoring


Product list Product list

Programmable Logic Controller

Item

Model

Specification

XBM-DR16S XBM-DN16S XBM-DN32S XBC-DR32H XBC-DN32H XBC-DR64H XBC-DN64H Main unit XBC-DR32H/DC XBC-DN32H/DC XBC-DR64H/DC XBC-DN64H/DC XEC-DR32H XEC-DN32H XEC-DR64H XEC-DN64H XBE-DC08A XBE-DC16A XBE-DC32A XBE-RY08A XBE-RY16A XBE-TN08A Expansion I/O module XBE-TN16A XBE-TN32A XBE-TP08A XBE-TP16A XBE-TP32A XBE-DR16A XBF-AD04A XBF-AH04A XBF-DV04A Special module XBF-DC04A XBF-RD04A XBF-TC04S XBF-PO2A XBL-C41A Communication XBL-C21A module XBL-EMTA PMC-310S Loader Cable USB-301A Memory module XBO-M1024A

Terminal board

Connection cable

SLT-CT051-XBM SLT-CT101-XBM SLP-T40P SLT-CT051-XBE (Terminal SLT-CT101-XBE board) SLT-CT151-XBE SLT-CT201-XBE SLT-CT301-XBE SLP-CT051-XBE SLP-RY4A SLP-CT101-XBE SLP-CT151-XBE (Relay board) SLP-CT201-XBE SLP-CT301-XBE

DC24V power supply, 8-point DC24V input, 8-point relay output DC24V power supply, 8-point DC24V input, 8-point TR output, Built-in positioning function DC24V power supply, 16-point DC24V input, 16-point TR output, Built-in positioning function AC110~220V, 16-point DC input, 16-point Relay output AC110~220V, 16-point DC input, 16-point TR output AC110~220V, 32-point DC input, 32-point Relay output AC110~220V, 32-point DC input, 32-point TR output DC24V, 16-point DC input, 16-point Relay output DC24V, 16-point DC input, 16-point TR output DC24V, 32-point DC input, 32-point Relay output DC24V, 32-point DC input, 32-point TR output AC110~220V, 16-point DC input, 16-point Relay output (IEC standard language) AC110~220V, 16-point DC input, 16-point TR output (IEC standard language) AC110~220V, 32-point DC input, 32-point Relay output (IEC standard language) AC110~220V, 32-point DC input, 32-point TR output (IEC standard language) 8-point DC24V input 16-point DC24V input 32-point DC24V input 8-point relay output 16-point relay output 8-point Transistor (sink) output 16-point Transistor (sink) output 32-point Transistor (sink) output 8-point Transistor (source) output 16-point Transistor (source) output 32-point Transistor (source) output 8-point DC24V input, 8-point relay output 4-channel analog input (current/voltage) 2-channel analog input (current/voltage)/2-channel analog output (current/voltage) 4-channel analog output (voltage) 4-channel analog output (current) 4-channel RTD input 4-channel Thermocouple input Line drive 2axis Cnet (RS-422/485) I/F Cnet (RS-232C) I/F Ethernet I/F Connection cable (PC to PLC), 9pin (PC)-6pin (PLC), Soft tube type cable Connection cable (PC to PLC), USB External memory for program back-up (1024kbyte)

XBM-DN16S XBM-DN32S

XBE-DC32A

XBE-TN32A

XBE-TP32A

● ● -

● ● ● ● ● -

● ● ● ● ● ● ● ● ● ●

● ● ● ● ● -

Remark

1. Cable length CT051: 0.5m CT101: 1.0m CT151: 1.5m CT201: 2.0m CT301: 3.0m

33


Dimension Download cable diagram

Dimension

90

60

64

90

100

30

64

W

(Unit: mm)

Item

Model

W

XBC-DR32H/DN32H XEC-DR32H/DN32H

Item XBM XBC/XEC

Common

34

Length

Model Main unit DR/DN32H (32pt) DR/DN64H (64pt) RY output / EMTA DC input TR output Analog

114

Item

Model

Length

W

XBC-DR64H/DN64H XEC-DR64H/DN64H

180

W

H

D

30 114 180 27

90 90 90 90

60 64 64 60

20

90

60


MEMO

Programmable Logic Controller

35


� For your safety, please read user's manual thoroughly before operating. � Contact the nearest authorized service facility for examination, repair, or adjustment. � Please contact qualified service technician when you need maintenance. Do not disassemble or repair by yourself!

Safety Instructions

� Any maintenance and inspection shall be performed by the personnel having expertise concerned.

ⓒ 2006. LS Industrial Systems Co., Ltd. All Rights Reserved.

www.lsis.biz � HEAD OFFICE LS Tower 1026-6, Hogye-dong, Dongan-gu, Anyang-si, Gyeonggi-do 431-848, Korea �NORTH AMERICA/EUROPE/CIS +82-2-2034-4676 sukyong@lsis.biz �ASIA/LATIN AMERICA +82-2-2034-4888 cshwang@lsis.biz �MIDDLE EAST/AFRICA/TURKEY +82-2-2034-4881 khchoi1@lsis.biz

Specifications in this catalog are subject to change without notice due to continuous product development and improvement.

2010. 05

� Global Network �LS Industrial Systems (Middle East) FZE >> Dubai, U.A.E. Address: P.O.Box-114216, API World Tower, 303B, Sheikhe Zayed Road, Dubai, U.A.E. Tel: 971-4-332-8289 Fax: 971-4-332-9444 e-mail: hwyim@lsis.biz �Dalian LS Industrial Systems Co., Ltd. >> Dalian, China Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn �LS Industrial Systems (Wuxi) Co., Ltd >> Wuxi, China Address: 102-A, National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R. China Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn �LS-VINA Industrial Systems Co., Ltd >> Hanoi, Vietnam Address: Nguyen Khe - Dong Anh - HaNoi - VietNam Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@hn.vnn.vn �LS Industrial Systems Tokyo Office >> Tokyo, Japan Address: 16FL, Higashi-Kan, Akasaka Twin Tower 17-22, 2-chome, Akasaka, Minato-ku Tokyo 107-8470, Japan Tel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: jschuna@lsis.biz �LS Industrial Systems Shanghai Office >> Shanghai, China Address: Room E-G, 12FL Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn �LS Industrial Systems Beijing Office >> Beijing, China Address: B-Tower 17FL. Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District, Beijing 100013, P.R. China Tel: 86-10-5825-6025, 7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn �LS Industrial Systems Guangzhou Office >> Guangzhou, China Address: Room 1403,14FL, New Poly Tower, 2 Zhongshan Liu Road, Guangzhou, P.R. China Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.biz �LS Industrial Systems Chengdu Office >> Chengdu, China Address: 12FL, Guodong Buiding, No.52 Jindun Road Chengdu, 610041, P.R. China Tel: 86-28-8612-9151 Fax: 86-28-8612-9236 e-mail: yangcf@lsis.com.cn �LS Industrial Systems Qingdao Office >> Qingdao, China Address: 7B40, Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn

LS XGB (E) 2006. 06/ (09) 2010. 05

Printed in Korea

HumanPower


PLC XGB