1335 S Austin Blvd Cicero, IL 60804

HENRY HARGROVE III

Saturday, July 7, 2012

Bart Wisniewski - IL Inspector 450-010522

Citizen Architects Inc. 1343 N Bosworth Ave, Suite A Chicago, IL 60642

Tel: 1.847.767.4668 Fax: 1.847.859.5878 www.citizenarchitects.com info@citizenarchitects.com

Citizen Architects Inc. | CREATING HIP SPACES ON SOLID FOUNDATIONS | Design.Permits.Inspections


August 21, 2013 Dear Henry Hargrove III, RE: Report No. 1012 1335 S Austin Blvd Cicero, IL 60804 Thanks very much for choosing us to perform your home inspection. The inspection itself and the attached report comply with the requirements of the Standards of Practice of the American Society of Home Inspectors and Illinois State Home Inspector License Act. This document defines the scope of a home inspection. Clients sometimes assume that a home inspection will include many things that are beyond the scope. We encourage you to read the Standards of Practice so that you clearly understand what things are included in the home inspection and report. The report has been prepared for the exclusive use of our client. No use by third parties is intended. We will not be responsible to any parties for the contents of the report, other than the party named herein . The report is effectively a snapshot of the house, recording the conditions on a given date and time. Home inspectors cannot predict future behavior, and as such, we cannot be responsible for things that occur after the inspection. If conditions change, we are available to revisit the property and update our report. The report itself is copyrighted, and may not be used in whole or in part without our express written permission. Again, thanks very much for choosing us to perform your home inspection. Sincerely, Bart Wisniewski - IL Inspector 450-010522 on behalf of Citizen Architects Inc.

Citizen Architects Inc. 1343 N Bosworth Ave, Suite A Chicago, IL 60642 Tel: 1.847.767.4668 Fax: 1.847.859.5878 www.citizenarchitects.com info@citizenarchitects.com


Report No. 1012

SUMMARY 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

This Summary outlines potentially significant issues from a cost or safety standpoint. This section is provided as a courtesy and cannot be considered a substitute for reading the entire report. Please read the complete document. Priority Maintenance Items

Roofing FLAT ROOFING \ Rubber single ply Condition: Old, worn out Implication(s): Chance of water damage to contents, finishes and/or structure Location: Throughout Roof Task: Repair or replace Time: Less than 1 year Cost: Major Condition: Openings at seams or flashings Implication(s): Chance of water damage to contents, finishes and/or structure Location: Center Roof Task: Repair Time: Immediate Condition: Ponding Implication(s): Chance of water damage to contents, finishes and/or structure | Chance of structural movement Location: Front Center Roof Task: Repair or replace Time: Immediate FLAT ROOF FLASHINGS \ Flashings Condition: Old and worn Implication(s): Chance of water damage to contents, finishes and/or structure Location: Throughout Task: Repair or replace Time: Less than 1 year FLAT ROOF FLASHINGS \ Wear or damage Condition: Caulking, sealant dried out, cracked Implication(s): Chance of water damage to contents, finishes and/or structure Location: Center Roof Task: Replace Time: Less than 1 year

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 1 of 39


Report No. 1012

SUMMARY 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Condition: Patched Implication(s): Chance of water damage to contents, finishes and/or structure Location: Throughout Front Center Roof Task: Repair or replace Time: Less than 1 year

Structure WALLS \ Solid masonry walls Condition: Efflorescence Implication(s): Cosmetic defects | Weakened structure Location: South Exterior Wall Roof Task: Repair or replace Monitor

Electrical SERVICE BOX, GROUNDING AND PANEL \ Distribution panel Condition: Panel crowded First Floor + Basement Electrical Panel Implication(s): Electric shock | Fire hazard Location: Basement Task: Upgrade Time: When remodelling DISTRIBUTION SYSTEM \ Outlets (receptacles) Condition: Ground Fault Interrupter (GFI) needed Implication(s): Electric shock Location: Rear First Floor Second Floor Porch Task: Replace Provide Cost: Minor DISTRIBUTION SYSTEM \ Outlets (receptacles) - number or location Condition: Too few outlets Implication(s): Nuisance Location: Second Floor Kitchen Task: Provide Condition: In floors or countertops Provide GFCI receptacle Implication(s): Electric shock Location: First Floor Second Floor Living Room Task: Replace Time: Immediate Cost: Minor

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 2 of 39


Report No. 1012

SUMMARY 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Heating RECOMMENDATIONS \ Overview Condition: One gas meter only for (3) units / (2) furnaces Location: North Task: Further evaluation Provide Time: Immediate CHIMNEY AND VENT \ Masonry chimney vent connector Condition: Abandoned openings for flue connections Implication(s): Hazardous combustion products entering home Location: Basement Task: Correct Remove Time: Immediate

Plumbing WASTE PLUMBING \ Floor drain Condition: Missing Implication(s): Chance of water damage to contents, finishes and/or structure Location: Basement Task: Provide Time: Immediate

Interior BASEMENT \ Wet basement - evidence Condition: Dampness on floor or walls Implication(s): Cosmetic defects | Chance of water damage to contents, finishes and/or structure | Material deterioration Location: Various Front Basement Task: Repair or replace Further evaluation Monitor Request disclosure Time: Immediate Cost: Major Condition: Water on floor Implication(s): Chance of water damage to contents, finishes and/or structure Location: Center Basement Task: Further evaluation Monitor Request disclosure Time: Immediate Cost: Major

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 3 of 39


Report No. 1012

SUMMARY 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

APPLIANCES \ Range Condition: Anti-tip device missing Implication(s): Physical injury Location: Throughout First Floor Second Floor Kitchen Task: Provide Time: Immediate Cost: Minor APPLIANCES \ Dryer Condition: Not vented to exterior Implication(s): Chance of condensation damage to finishes and/or structure Location: Basement Task: Provide DESCRIPTION OF REPORT The report that follows includes a Description of the systems and components in the house as well as any Limitations that may have restricted our inspection. The most important part of the report is the Recommendations section. It is here that we identify any defects in the home and suggest improvements. LIMITING FACTORS The inspection is performed by a generalist, and in some cases, we will recommend specialists to further investigate conditions that we have identified. This is very similar to the doctor who is a general practitioner, identifying a physical condition and recommending further testing by a specialist. Home inspectors have a limited amount of time on site. Market conditions and inspection fees dictate that inspections typically run about three hours. As a result, there will be things that are not picked up by inspectors. We ask that you understand and accept this. The inspection provides great value, and adds considerably to your understanding of the home. But it is not an insurance policy with a one-time only premium, no exclusions, no deductible and no limits. A home inspection does not include an examination for pests, rot or wood destroying insects. There are specialists available who can provide these services. Please read the report carefully, and feel free to ask any questions that you may have of the inspector. Again, we will remind you that a home inspection addresses visually accessible components of the home, and does not include destructive testing. We will operate mechanical systems with normal homeowner controls. Where there are many systems of a similar type and a home, we inspect a representative sample. For example, we do not inspect every electrical outlet, every piece of siding or every brick or every window. As you read the report, we encourage you to contact us with any questions about the report or the home. Information about Carbon Monoxide: http://www.inspectionlibrary.com/Carbon_Monoxide.htm Information about Radon: http://epa.gov/radon/

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 4 of 39


Report No. 1012

SUMMARY 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Information about Lead Based Paint: http://www.epa.gov/lead/ Home Improvement - ballpark costs

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 5 of 39


Report No. 1012

ROOFING 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Sloped roofing material: Asphalt shingles at Garage - new roof Flat roofing material:

Synthetic rubber

Probability of leakage:

High

Limitations Inspection performed:

By walking on roof

Recommendations SLOPED ROOF FLASHINGS \ Drip edge flashings 1. Condition: Missing Implication(s): Chance of water damage to contents, finishes and/or structure Location: Throughout Garage Task: Upgrade

1. Missing FLAT ROOFING \ Rubber single ply 2. Condition: Old, worn out Implication(s): Chance of water damage to contents, finishes and/or structure Location: Throughout Roof Task: Repair or replace Time: Less than 1 year Cost: Major

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 6 of 39


Report No. 1012

ROOFING 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

2. Old, worn out

3. Old, worn out

4. Old, worn out 3. Condition: Openings at seams or flashings Implication(s): Chance of water damage to contents, finishes and/or structure Location: Center Roof Task: Repair Time: Immediate

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 7 of 39


Report No. 1012

ROOFING 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

Click on image to enlarge.

REFERENCE

5. Openings at seams 4. Condition: Ponding Implication(s): Chance of water damage to contents, finishes and/or structure | Chance of structural movement Location: Front Center Roof Task: Repair or replace Time: Immediate

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 8 of 39


Report No. 1012

ROOFING 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

Click on image to enlarge.

REFERENCE

6. Ponding 5. Condition: Mastic on EPDM Implication(s): Shortened life expectancy of material FLAT ROOF FLASHINGS \ Flashings 6. Condition: Old and worn Implication(s): Chance of water damage to contents, finishes and/or structure Location: Throughout Task: Repair or replace Time: Less than 1 year

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 9 of 39


Report No. 1012

ROOFING 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

7. Old and worn

8. Old and worn

9. Old and worn

10. Old and worn

FLAT ROOF FLASHINGS \ Wear or damage 7. Condition: Caulking, sealant dried out, cracked Implication(s): Chance of water damage to contents, finishes and/or structure Location: Center Roof Task: Replace Time: Less than 1 year

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 10 of 39


Report No. 1012

ROOFING 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

11. Caulking, sealant dried out, cracked

12. Caulking, sealant dried out, cracked

8. Condition: Patched Implication(s): Chance of water damage to contents, finishes and/or structure Location: Throughout Front Center Roof Task: Repair or replace Time: Less than 1 year

13. Patched

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 11 of 39


Report No. 1012

EXTERIOR 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Gutter & downspout material: Gutter & downspout type:

Aluminum

Eave mounted

Gutter & downspout discharge: Lot slope:

Below grade

Away from house

Wall surfaces - masonry:

Brick

Wall surfaces : Vinyl siding at Back Porch Driveway:

Concrete

Walkway:

Concrete

Porch:

Wood

Exterior steps: Fence:

Concrete

Chain link

Limitations No or limited access to:

Garage

Upper floors inspected from: Exterior inspected from:

Ground level

Ground level

Recommendations ROOF DRAINAGE \ Gutters 9. Condition: Clogged Implication(s): Chance of water damage to contents, finishes and/or structure Location: Rear Roof Task: Monitor Inspect annually

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 12 of 39


Report No. 1012

EXTERIOR 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

14. Clogging Possibility / Monitor

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 13 of 39


Report No. 1012

STRUCTURE 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Configuration:

Basement

Foundation material: Floor construction:

Masonry block Joists

Exterior wall construction: Roof and ceiling framing:

Masonry Rafters/roof joists

Limitations Inspection limited/prevented by: Knee wall areas:

Wall, floor and ceiling coverings

New finishes/paint

No access

Percent of foundation not visible:

80 %

Recommendations FOUNDATIONS \ Foundation 10. Condition: Large trees close to building Implication(s): Weakened structure | Chance of structural movement Location: Front Task: Monitor WALLS \ Solid masonry walls 11. Condition: Prior repairs Implication(s): Weakened structure Location: South Task: Repair or replace Monitor

15. Mastic at grade - prior repairs

16. Mastic at grade - prior repairs

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 14 of 39


Report No. 1012

STRUCTURE 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

17. Mastic at grade - prior repairs

18. Parging damaged or missing

20. Mastic at grade - prior repairs

19. Prior repairs 12. Condition: Bowing, leaning or bulging Implication(s): Weakened structure | Chance of structural movement Location: Front Exterior Wall Roof Task: Further evaluation Monitor Time: When necessary

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 15 of 39


Report No. 1012

STRUCTURE 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

21. Bowing, leaning or bulging

22. Bowing, leaning or bulging

13. Condition: Masonry deteriorating Implication(s): Weakened structure | Chance of structural movement Location: South Exterior Wall Task: Monitor

23. Masonry deteriorating 14. Condition: Efflorescence Implication(s): Cosmetic defects | Weakened structure Location: South Exterior Wall Roof Task: Repair or replace Monitor

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 16 of 39


Report No. 1012

STRUCTURE 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

24. Efflorescence

25. Efflorescence

15. Condition: Lintels rusting Implication(s): Weakened structure | Chance of structural movement Location: South Exterior Wall Task: Monitor Protect

26. Lintels rusting 16. Condition: Mortar deteriorating Implication(s): Weakened structure | Chance of structural movement Location: North South Exterior Wall Task: Repair Time: Less than 2 years

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 17 of 39


Report No. 1012

STRUCTURE 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

27. Masonry and Mortar deteriorating

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 18 of 39


Report No. 1012

ELECTRICAL 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Service entrance cable and location: Service size:

Overhead

200 Amps (240 Volts)

Main disconnect/service box rating: 100 Amps (1) 100 Amp Electrical Panel - 1st Floor + Basement - 17 Circuits Installed - Panel overloaded above 80% (1) 100 Amp Electrical Panel - 2nd Floor - 7 Circuits Installed

28. 100 Amps (Crowded)

29. 100 Amps

Main disconnect/service box type and location: System grounding material and type: Distribution wire material and type:

Breakers - basement

Aluminum - ground rods Copper - metallic sheathed

Type and number of outlets (receptacles):

Grounded - minimal

Circuit interrupters: Ground Fault (GFCI) & Arc Fault (AFCI): Smoke detectors:

GFCI - bathroom

GFCI - kitchen

Present

Limitations System ground:

Quality of ground not determined

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 19 of 39


Report No. 1012

ELECTRICAL 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Circuit labels:

The accuracy of the circuit index (labels) was not verified.

Recommendations SERVICE BOX, GROUNDING AND PANEL \ Distribution panel 17. Condition: Panel crowded First Floor + Basement Electrical Panel Implication(s): Electric shock | Fire hazard Location: Basement Task: Upgrade Time: When remodelling DISTRIBUTION SYSTEM \ Outlets (receptacles) 18. Condition: Loose Implication(s): Electric shock | Fire hazard Location: First Floor Bedroom Task: Correct Cost: Minor

30. Loose 19. Condition: Ground Fault Interrupter (GFI) needed Implication(s): Electric shock Location: Rear First Floor Second Floor Porch Task: Replace Provide Cost: Minor

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 20 of 39


Report No. 1012

ELECTRICAL 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

Click on image to enlarge.

REFERENCE

31. Ground Fault Interrupter (GFI) needed DISTRIBUTION SYSTEM \ Outlets (receptacles) - number or location 20. Condition: Too few outlets Implication(s): Nuisance Location: Second Floor Kitchen Task: Provide

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 21 of 39


Report No. 1012

ELECTRICAL 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

32. Too few outlets 21. Condition: In floors or countertops Provide GFCI receptacle Implication(s): Electric shock Location: First Floor Second Floor Living Room Task: Replace Time: Immediate Cost: Minor

33. In floors or countertops

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 22 of 39


Report No. 1012

HEATING 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Fuel/energy source: System type:

Gas

Furnace

Furnace manufacturer: Ducane Model number: A80UH & 80G1UH

34.

35.

Heat distribution:

Ducts and registers

Approximate capacity: 80,000 BTU/hr (1) Furnace - 1st Floor + Basement (1) Furnace - 2nd Floor Efficiency:

Conventional

Approximate age:

1 year

Typical life expectancy: Failure probability: Main fuel shut off at:

Furnace (conventional or mid-efficiency) 18 to 25 years

Low Basement

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 23 of 39


Report No. 1012

HEATING 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Fireplace:

Decorative only

Chimney/vent:

Masonry

Chimney liner:

None

Metal

Required for upgrade/conversion

Limitations Safety devices:

Not tested as part of a home inspection

Warm weather:

Prevented testing in heating mode

Air conditioner or heat pump: Heat loss calculations: Heat exchanger:

No Air Conditioning

Not done as part of a home inspection

Not visible

Recommendations RECOMMENDATIONS \ Overview 22. Condition: One gas meter only for (3) units / (2) furnaces Location: North Task: Further evaluation Provide Time: Immediate

36. One gas meter only GAS FURNACE \ Mechanical air filter 23. Condition: Missing Implication(s): Increased heating costs | Reduced comfort | Increased maintenance costs Location: Second Floor Task: Provide Time: Immediate Cost: Minor

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 24 of 39


Report No. 1012

HEATING 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

Click on image to enlarge.

REFERENCE

37. Missing CHIMNEY AND VENT \ Masonry chimney 24. Condition: No chimney liner Old existing clay liner. Metal liner upgrade desired. Implication(s): Material deterioration | Hazardous combustion products entering home Location: North Roof Task: Upgrade

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 25 of 39


Report No. 1012

HEATING 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

Click on image to enlarge.

REFERENCE

38. Old existing clay liner. Metal liner desired CHIMNEY AND VENT \ Masonry chimney vent connector 25. Condition: Abandoned openings for flue connections Implication(s): Hazardous combustion products entering home Location: Basement Task: Correct Remove Time: Immediate

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 26 of 39


Report No. 1012

HEATING 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

Click on image to enlarge.

REFERENCE

39. Abandoned openings for flue connections CHIMNEY AND VENT \ Masonry chimney cap 26. Condition: Rain cap missing or damaged Implication(s): Chance of water entering house | Chance of pests entering house Location: Roof Task: Provide

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 27 of 39


Report No. 1012

COOLING & HEAT PUMP 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Air conditioning type:

None present

Limitations Heat gain calculations:

Not done as part of a home inspection

Heat gain/loss calculations:

Not done as part of a home inspection

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 28 of 39


Report No. 1012

INSULATION AND VENTILATION 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Attic/roof insulation amount/value: Attic/roof air/vapor barrier: Wall insulation material:

Not visible

None found

Not visible

Not determined

Not determined

Not visible

Wall insulation amount/value:

Not determined

Foundation wall insulation amount/value:

Not determined

Not visible

Limitations Roof ventilation system performance: Air/vapor barrier system:

Not evaluated

Continuity not verified

Mechanical ventilation effectiveness:

Not verified

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 29 of 39


Report No. 1012

PLUMBING 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Water supply source:

Public

Service piping into building: Supply piping in building:

Not visible Copper

Main water shut off valve at the: Water flow and pressure:

Basement

Functional

Water heater fuel/energy source: Water heater type:

Gas

Conventional

Water heater manufacturer: Rheem (2) Richmond 6YR Model number: 6G40-36FI Tank capacity:

40 gallons

Water heater approximate age: Typical life expectancy:

New

8 to 12 years

Water heater failure probability: Waste piping in building: Pumps:

Plastic

Low Cast Iron

Sump pump

Floor drain location: Gas piping:

None found

Steel

Limitations Inspection limited/prevented by:

Water supply turned off

Items excluded from a home inspection:

Water quality

Isolating/relief valves & main shut-off valve

Water heater

relief valves are not tested

Recommendations WASTE PLUMBING \ Floor drain 27. Condition: Missing Implication(s): Chance of water damage to contents, finishes and/or structure Location: Basement Task: Provide Time: Immediate

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 30 of 39


Report No. 1012

PLUMBING 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

40. Missing Floor Drain FIXTURES AND FAUCETS \ Faucet 28. Condition: Loose Implication(s): Equipment failure Location: First Floor Kitchen Task: Repair or replace

41. Loose FIXTURES AND FAUCETS \ Bathtub 29. Condition: Drain stop missing Location: Throughout Bathroom Task: Repair or replace Cost: Minor

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 31 of 39


Report No. 1012

PLUMBING 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

42. Drain stop missing

43. Drain stop missing

Click on image to enlarge.

FIXTURES AND FAUCETS \ Hose bibb 30. Condition: Backflow prevention missing Implication(s): Contaminated drinking water Location: North Exterior Wall Task: Upgrade Time: When remodelling

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 32 of 39


Report No. 1012

PLUMBING 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

44. Backflow prevention missing

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 33 of 39


Report No. 1012

INTERIOR 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

Hardwood

Ceramic

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Major floor finishes: Major wall finishes:

Plaster/drywall

Major ceiling finishes: Windows: Glazing:

Plaster/drywall

Single/double hung Double

Exterior doors - type/material: Evidence of basement leakage: Range fuel:

Gas

Appliances:

Refrigerator

Laundry facilities:

Solid wood Dampness

Water

Musty or damp odor

Microwave oven

Dryer Vent not Found

Limitations Inspection limited/prevented by: No access to:

New finishes/paint

Garage

Restricted access to:

Garage

Not included as part of a building inspection: Basement leakage:

Appliances

Cannot predict how often or how badly basement will leak

Recommendations BASEMENT \ Wet basement - evidence 31. Condition: Dampness on floor or walls Implication(s): Cosmetic defects | Chance of water damage to contents, finishes and/or structure | Material deterioration Location: Various Front Basement Task: Repair or replace Further evaluation Monitor Request disclosure Time: Immediate Cost: Major

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 34 of 39


Report No. 1012

INTERIOR 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

45. Dampness on floor or walls

46. Dampness on floor or walls

47. Dampness on floor or walls

48. Dampness on floor or walls

32. Condition: Water on floor Implication(s): Chance of water damage to contents, finishes and/or structure Location: Center Basement Task: Further evaluation Monitor Request disclosure Time: Immediate Cost: Major

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 35 of 39


Report No. 1012

INTERIOR 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

Click on image to enlarge.

Click on image to enlarge.

REFERENCE

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 36 of 39


Report No. 1012

INTERIOR 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

49. Water on floor

50. Water on floor

APPLIANCES \ Range 33. Condition: Anti-tip device missing Implication(s): Physical injury Location: Throughout First Floor Second Floor Kitchen Task: Provide Time: Immediate Cost: Minor

51. Anti-tip device missing

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 37 of 39


Report No. 1012

INTERIOR 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

APPLIANCES \ Dryer 34. Condition: Not vented to exterior Implication(s): Chance of condensation damage to finishes and/or structure Location: Basement Task: Provide END OF REPORT

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 38 of 39


Report No. 1012

REFERENCE LIBRARY 1335 S Austin Blvd, Cicero, IL SUMMARY

ROOFING

www.citizenarchitects.com

July 7, 2012

EXTERIOR

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

The links below connect you to a series of documents that will help you understand your home and how it works. These are in addition to links attached to specific items in the report. Click on any link to read about that system.

01. ROOFING, FLASHINGS AND CHIMNEYS 02. EXTERIOR 03. STRUCTURE 04. ELECTRICAL 05. HEATING 06. COOLING/HEAT PUMPS 07. INSULATION 08. PLUMBING 09. INTERIOR 10. APPLIANCES 11. LIFE CYCLES AND COSTS 12. SUPPLEMENTARY Asbestos Radon Urea Formaldehyde Foam Insulation (UFFI) Lead Carbon Monoxide Mold Household Pests Termites and Carpenter Ants

13. HOME SET-UP AND MAINTENANCE 14. MORE ABOUT HOME INSPECTIONS

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 39 of 39