1713 W Touhy Ave Unit C Chicago, IL 60626

KIMERON DUFF

Friday, September 28, 2012

Bart Wisniewski - IL Inspector 450-010522

Citizen Architects Inc. 1343 N Bosworth Ave, Suite A Chicago, IL 60642

Tel: 1.847.767.4668 Fax: 1.847.859.5878 www.citizenarchitects.com info@citizenarchitects.com

Citizen Architects Inc. | CREATING HIP SPACES ON SOLID FOUNDATIONS | Design.Permits.Inspections


August 21, 2013 Dear Kimeron Duff, RE: Report No. 1015 1713 W Touhy Ave Unit C Chicago, IL 60626 Thanks very much for choosing us to perform your home inspection. The inspection itself and the attached report comply with the requirements of the Standards of Practice of the American Society of Home Inspectors and Illinois State Home Inspector License Act. This document defines the scope of a home inspection. Clients sometimes assume that a home inspection will include many things that are beyond the scope. We encourage you to read the Standards of Practice so that you clearly understand what things are included in the home inspection and report. The report has been prepared for the exclusive use of our client. No use by third parties is intended. We will not be responsible to any parties for the contents of the report, other than the party named herein . The report is effectively a snapshot of the house, recording the conditions on a given date and time. Home inspectors cannot predict future behavior, and as such, we cannot be responsible for things that occur after the inspection. If conditions change, we are available to revisit the property and update our report. The report itself is copyrighted, and may not be used in whole or in part without our express written permission. Again, thanks very much for choosing us to perform your home inspection. Sincerely, Bart Wisniewski - IL Inspector 450-010522 on behalf of Citizen Architects Inc.

Citizen Architects Inc. 1343 N Bosworth Ave, Suite A Chicago, IL 60642 Tel: 1.847.767.4668 Fax: 1.847.859.5878 www.citizenarchitects.com info@citizenarchitects.com


Report No. 1015

SUMMARY 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

This Summary outlines potentially significant issues from a cost or safety standpoint. This section is provided as a courtesy and cannot be considered a substitute for reading the entire report. Please read the complete document. Priority Maintenance Items

Roofing General Roof Condition Disclosure Requested (no access at the time of inspection) Location: Throughout Exterior Roof Task: Request disclosure Time: Immediate

Exterior ROOF DRAINAGE \ Downspouts Condition: Downspouts discharging onto roofs Implication(s): Chance of water damage to contents, finishes and/or structure Location: Front Rear First Floor Foyer Task: Monitor Correct Time: Less than 1 year Cost: Minor EXTERIOR GLASS \ Glass (glazing) Condition: Broken Implication(s): Chance of water entering house | Chance of pests entering house | Increased heating and cooling costs | Reduced comfort Location: Rear Second Floor Bedroom Task: Replace Time: Immediate

Electrical DISTRIBUTION SYSTEM \ Wiring - damaged or exposed Condition: Exposed on walls or ceilings Conduit wrapped in paper Implication(s): Electric shock Location: First Floor Living Room Task: Replace Further evaluation Time: Immediate

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 1 of 41


Report No. 1015

SUMMARY 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

DISTRIBUTION SYSTEM \ Wiring - installation Condition: Wrong type Implication(s): Electric shock | Fire hazard Location: First Floor Kitchen Task: Repair or replace Further evaluation Time: Immediate DISTRIBUTION SYSTEM \ Outlets (receptacles) Condition: Ungrounded Implication(s): Electric shock Location: Various First Floor Second Floor Bedroom Task: Repair or replace Time: Immediate Condition: Ground Fault Interrupter (GFI) needed Implication(s): Electric shock Location: Rear Exterior Wall Deck Task: Replace Time: Immediate Cost: Minor DISTRIBUTION SYSTEM \ Smoke detectors Condition: None Implication(s): Fire hazard Location: Throughout DISTRIBUTION SYSTEM \ Carbon monoxide (CO) detectors Condition: None Location: Throughout

Heating GAS FURNACE \ Life expectancy Condition: Near end of life expectancy Implication(s): Equipment failure | No heat for house Location: First Floor Utility Room Task: Upgrade Remove

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 2 of 41


Report No. 1015

SUMMARY 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Plumbing SUPPLY PLUMBING \ Supply piping in building Condition: Galvanized steel Implication(s): Reduced water pressure and volume Location: Throughout Task: Replace Time: When remodelling Cost: Major WATER HEATER \ Life expectancy Condition: High failure probability Implication(s): No domestic hot water Location: Kitchen Task: Repair or replace Further evaluation Time: When remodelling WASTE PLUMBING \ Drain piping - performance Condition: Leak Implication(s): Sewage entering the house Location: Second Floor Bathroom Task: Repair or replace Condition: Clogged Implication(s): Sewage entering the house Location: First Floor Bathroom Task: Repair or replace Condition: Poor slope Implication(s): Sewage entering the house Location: First Floor Kitchen Task: Repair or replace FIXTURES AND FAUCETS \ Faucet Condition: Drip, leak Implication(s): Chance of water damage to contents, finishes and/or structure Location: Various Throughout First Floor Second Floor Kitchen Bathroom Task: Replace Cost: Major FIXTURES AND FAUCETS \ Toilet Condition: Loose Implication(s): Chance of water damage to contents, finishes and/or structure | Sewage entering the house Location: First Floor Second Floor Bathroom Task: Replace

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 3 of 41


Report No. 1015

SUMMARY 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Interior WALLS \ Plaster or drywall Condition: Water damage Implication(s): Cosmetic defects Location: Dining Room Task: Repair or replace Further evaluation DOORS \ Glass (glazing) Condition: Safety glass not installed Implication(s): Physical injury Location: First Floor Dining Room Task: Replace Time: Immediate STAIRS \ Width Condition: Too narrow Implication(s): Physical injury Task: Demolish Upgrade Time: When remodelling Cost: $3,000-$5,000 STAIRS \ Guardrails Condition: Too low Implication(s): Fall hazard Location: Second Floor Task: Replace DESCRIPTION OF REPORT The report that follows includes a Description of the systems and components in the house as well as any Limitations that may have restricted our inspection. The most important part of the report is the Recommendations section. It is here that we identify any defects in the home and suggest improvements. LIMITING FACTORS The inspection is performed by a generalist, and in some cases, we will recommend specialists to further investigate conditions that we have identified. This is very similar to the doctor who is a general practitioner, identifying a physical condition and recommending further testing by a specialist. Home inspectors have a limited amount of time on site. Market conditions and inspection fees dictate that inspections typically run about three hours. As a result, there will be things that are not picked up by inspectors. We ask that you understand and accept this. The inspection provides great value, and adds considerably to your understanding of the home. But it is not an insurance policy with a one-time only premium, no exclusions, no deductible and no limits. A home inspection does not include an examination for pests, rot or wood destroying insects. There are specialists available who can provide these services.

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 4 of 41


Report No. 1015

SUMMARY 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Please read the report carefully, and feel free to ask any questions that you may have of the inspector. Again, we will remind you that a home inspection addresses visually accessible components of the home, and does not include destructive testing. We will operate mechanical systems with normal homeowner controls. Where there are many systems of a similar type and a home, we inspect a representative sample. For example, we do not inspect every electrical outlet, every piece of siding or every brick or every window. As you read the report, we encourage you to contact us with any questions about the report or the home. Information about Carbon Monoxide: http://www.inspectionlibrary.com/Carbon_Monoxide.htm Information about Radon: http://epa.gov/radon/ Information about Lead Based Paint: http://www.epa.gov/lead/ Home Improvement - ballpark costs

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 5 of 41


Report No. 1015

ROOFING 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Flat roofing material:

Modified bitumen

Unknown

Limitations Roof inspection limited/prevented by: Inspection performed:

Lack of access

From the ground

Recommendations General 1. Roof Condition Disclosure Requested (no access at the time of inspection) Location: Throughout Exterior Roof Task: Request disclosure Time: Immediate

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 6 of 41


Report No. 1015

EXTERIOR 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Gutter & downspout material: Gutter & downspout type:

Aluminum

Eave mounted

Gutter & downspout discharge: Lot slope:

Away from house

Wall surfaces - masonry: Walkway:

Fence:

Brick

Concrete

Exterior steps: Patio:

Below grade

Concrete

Concrete Wrought iron

Limitations Inspection limited/prevented by: Upper floors inspected from: Exterior inspected from:

Vines/shrubs/trees against wall

Ground level

Ground level

Recommendations ROOF DRAINAGE \ Downspouts 2. Condition: Downspouts discharging onto roofs Implication(s): Chance of water damage to contents, finishes and/or structure Location: Front Rear First Floor Foyer Task: Monitor Correct Time: Less than 1 year Cost: Minor

1. Downspouts discharging onto roofs This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 7 of 41


Report No. 1015

EXTERIOR 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

WALLS \ Wood siding 3. Condition: Paint or stain - needed Implication(s): Shortened life expectancy of material Location: Throughout Second Floor Task: Repair or replace

2. Paint or stain - needed

3. Paint or stain - needed

EXTERIOR GLASS \ General 4. Condition: Water leaks Implication(s): Chance of water damage to contents, finishes and/or structure Location: Various 5. Condition: Air leaks Implication(s): Increased heating and cooling costs | Reduced comfort Location: Various EXTERIOR GLASS \ Glass (glazing) 6. Condition: Broken Implication(s): Chance of water entering house | Chance of pests entering house | Increased heating and cooling costs | Reduced comfort Location: Rear Second Floor Bedroom Task: Replace Time: Immediate

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 8 of 41


Report No. 1015

EXTERIOR 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

4. Broken DOORS \ Doors and frames 7. Condition: Damage Implication(s): Cosmetic defects | Chance of damage to finishes and structure | Poor security Location: Front First Floor Task: Replace Time: Immediate

5. Damage

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 9 of 41


Report No. 1015

EXTERIOR 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Click on image to enlarge.

Click on image to enlarge.

LANDSCAPING \ Walkway 8. Condition: Improper slope or drainage Implication(s): Chance of water damage to contents, finishes and/or structure Location: Front Rear Exterior Wall Task: Correct

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 10 of 41


Report No. 1015

EXTERIOR 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

Click on image to enlarge.

REFERENCE

6. Improper slope or drainage

7. Improper slope or drainage

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 11 of 41


Report No. 1015

STRUCTURE 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Foundation material: Floor construction:

Poured concrete Joists

Exterior wall construction: Roof and ceiling framing:

Masonry Trusses

Not visible

Limitations Inspection limited/prevented by: Attic/roof space: Crawl space:

Wall, floor and ceiling coverings

Carpet/furnishings

No access

No access

Percent of foundation not visible:

100 %

Recommendations

Click on image to enlarge.

WALLS \ Lintels 9. Condition: Rust Implication(s): Weakened structure | Chance of structural movement Location: Various Rear Task: Monitor Clean Protect Time: Less than 1 year Cost: Minor

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 12 of 41


Report No. 1015

STRUCTURE 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

8. Rust at Lintel, clean the vents

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 13 of 41


Report No. 1015

ELECTRICAL 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Service entrance cable and location: Service size:

Underground copper

200 Amps (240 Volts)

Main disconnect/service box rating:

200 Amps

System grounding material and type: Distribution panel rating:

Not visible

150 Amps

Distribution panel type and location: Distribution wire material and type:

Breakers - utility room Copper - non-metallic sheathed

Type and number of outlets (receptacles):

Grounded and ungrounded - typical

Circuit interrupters: Ground Fault (GFCI) & Arc Fault (AFCI): Smoke detectors:

No GFCI

No AFCI

None noted

Carbon monoxide (CO) detectors:

None noted

Limitations Inspection limited/prevented by: System ground: Circuit labels:

Insulation

Continuity not verified

Quality of ground not determined

The accuracy of the circuit index (labels) was not verified.

Recommendations SERVICE BOX, GROUNDING AND PANEL \ Service box 10. Condition: No single main disconnect Implication(s): Electric shock

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 14 of 41


Report No. 1015

ELECTRICAL 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

9. No single main disconnect SERVICE BOX, GROUNDING AND PANEL \ Distribution panel 11. Condition: Poor location Location: Utility Room Task: Further evaluation

10. Poor location

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 15 of 41


Report No. 1015

ELECTRICAL 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

SERVICE BOX, GROUNDING AND PANEL \ Panel wires 12. Condition: Not well secured Implication(s): Electric shock | Fire hazard Location: Utility Room Task: Repair or replace Further evaluation

11. Poor location DISTRIBUTION SYSTEM \ Wiring - damaged or exposed 13. Condition: Exposed on walls or ceilings Conduit wrapped in paper Implication(s): Electric shock Location: First Floor Living Room Task: Replace Further evaluation Time: Immediate

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 16 of 41


Report No. 1015

ELECTRICAL 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

Click on image to enlarge.

REFERENCE

12. Exposed on walls or ceilings DISTRIBUTION SYSTEM \ Wiring - installation 14. Condition: Permanent wiring used as extension cord Implication(s): Electric shock | Fire hazard Location: Living Room Task: Correct

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 17 of 41


Report No. 1015

ELECTRICAL 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

13. Permanent wiring used as extension cord

Click on image to enlarge.

15. Condition: Wrong type Implication(s): Electric shock | Fire hazard Location: First Floor Kitchen Task: Repair or replace Further evaluation Time: Immediate

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 18 of 41


Report No. 1015

ELECTRICAL 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

14. Wrong type DISTRIBUTION SYSTEM \ Lights 16. Condition: Improper closet lighting Implication(s): Fire hazard Location: Throughout

15. Improper closet lighting

16. Improper closet lighting

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 19 of 41


Report No. 1015

ELECTRICAL 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

DISTRIBUTION SYSTEM \ Outlets (receptacles) 17. Condition: Ungrounded Implication(s): Electric shock Location: Various First Floor Second Floor Bedroom Task: Repair or replace Time: Immediate

17. Ungrounded

18. Ungrounded

19. Ungrounded 18. Condition: Ground Fault Interrupter (GFI) needed Implication(s): Electric shock Location: Rear Exterior Wall Deck Task: Replace Time: Immediate Cost: Minor

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 20 of 41


Report No. 1015

ELECTRICAL 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

Click on image to enlarge.

REFERENCE

20. Ground Fault Interrupter (GFI) needed DISTRIBUTION SYSTEM \ Smoke detectors 19. Condition: None Implication(s): Fire hazard Location: Throughout

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 21 of 41


Report No. 1015

ELECTRICAL 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

DISTRIBUTION SYSTEM \ Carbon monoxide (CO) detectors 20. Condition: None Location: Throughout

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 22 of 41


Report No. 1015

HEATING 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Fuel/energy source: System type:

Gas

Furnace

Furnace manufacturer: Heat distribution:

American Standard

Ducts and registers

Approximate capacity: Efficiency:

50,000 BTU/hr

Conventional

Approximate age:

Near end of life expectancy

Failure probability:

High

Main fuel shut off at:

Utility room

Chimney/vent:

Masonry

Chimney liner:

Not visible

Limitations Inspection prevented/limited by: Safety devices:

Not tested as part of a home inspection

Heat loss calculations: Heat exchanger:

System was inoperative

Not done as part of a home inspection

Not visible

Recommendations GAS FURNACE \ Life expectancy 21. Condition: Near end of life expectancy Implication(s): Equipment failure | No heat for house Location: First Floor Utility Room Task: Upgrade Remove

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 23 of 41


Report No. 1015

HEATING 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

21. Near end of life expectancy

22. Near end of life expectancy

23. Mold at utility room GAS FURNACE \ Thermostat 22. Condition: Damage Implication(s): Increased heating costs | Reduced comfort | No heat for house Location: First Floor Living Room Task: Replace

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 24 of 41


Report No. 1015

HEATING 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

Click on image to enlarge.

REFERENCE

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 25 of 41


Report No. 1015

COOLING & HEAT PUMP 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Air conditioning type:

None present

Limitations General:

No Air Conditioning

Heat gain/loss calculations: Heat gain calculations:

Not done as part of a home inspection

Not done as part of a home inspection

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 26 of 41


Report No. 1015

INSULATION AND VENTILATION 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Attic/roof insulation material:

Glass fiber

Attic/roof insulation amount/value: Attic/roof ventilation:

Not visible

Soffit vent

Attic/roof air/vapor barrier: Wall insulation material:

Not visible

Not visible

Wall insulation amount/value:

R-8

Foundation wall insulation material:

Spot checked only Not determined

Foundation wall insulation amount/value: Floor above crawlspace insulation material: Crawlspace ventilation:

Not visible Not determined

None Found

Limitations Attic inspection performed: Air/vapor barrier system:

No attic Continuity not verified

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 27 of 41


Report No. 1015

PLUMBING 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Water supply source:

Public

Service piping into building: Supply piping in building:

Galvanized steel Galvanized steel

Main water shut off valve at the: Water flow and pressure:

Exterior wall

Below average

Water heater fuel/energy source: Water heater manufacturer: Tank capacity:

Electric

Gama

30 gallons

Water heater approximate age: Typical life expectancy:

20 years

8 to 12 years

Water heater failure probability: Waste piping in building:

Plastic

High Cast Iron

Limitations Fixtures not tested/not in service:

Water heater

Items excluded from a home inspection:

Concealed plumbing

Water heater relief valves are not tested

Recommendations SUPPLY PLUMBING \ Supply piping in building 23. Condition: Galvanized steel Implication(s): Reduced water pressure and volume Location: Throughout Task: Replace Time: When remodelling Cost: Major

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 28 of 41


Report No. 1015

PLUMBING 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

Click on image to enlarge.

REFERENCE

24. Galvanized steel WATER HEATER \ Life expectancy 24. Condition: High failure probability Implication(s): No domestic hot water Location: Kitchen Task: Repair or replace Further evaluation Time: When remodelling

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 29 of 41


Report No. 1015

PLUMBING 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

25. High failure probability

Click on image to enlarge.

WATER HEATER \ Capacity 25. Condition: Inadequate Implication(s): Inadequate domestic hot water

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 30 of 41


Report No. 1015

PLUMBING 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

WASTE PLUMBING \ Drain piping - performance 26. Condition: Leak Implication(s): Sewage entering the house Location: Second Floor Bathroom Task: Repair or replace

26. Leaks 27. Condition: Clogged Implication(s): Sewage entering the house Location: First Floor Bathroom Task: Repair or replace

27. Slow Drain

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 31 of 41


Report No. 1015

PLUMBING 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Click on image to enlarge.

28. Condition: Poor slope Implication(s): Sewage entering the house Location: First Floor Kitchen Task: Repair or replace

28. Poor slope FIXTURES AND FAUCETS \ Faucet 29. Condition: Drip, leak Implication(s): Chance of water damage to contents, finishes and/or structure Location: Various Throughout First Floor Second Floor Kitchen Bathroom Task: Replace Cost: Major

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 32 of 41


Report No. 1015

PLUMBING 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

29. Drip, leak

30. Drip, leak

31. Drip, leak

32. Drip, leak

FIXTURES AND FAUCETS \ Toilet 30. Condition: Loose Implication(s): Chance of water damage to contents, finishes and/or structure | Sewage entering the house Location: First Floor Second Floor Bathroom Task: Replace

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 33 of 41


Report No. 1015

PLUMBING 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

Click on image to enlarge.

REFERENCE

33. Loose

34. Loose

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 34 of 41


Report No. 1015

INTERIOR 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Major floor finishes: Major wall finishes:

Carpet Plaster/drywall

Major ceiling finishes: Windows: Glazing:

Plaster/drywall

Single/double hung Single

Exterior doors - type/material:

Hinged

Sliding glass

Limitations Inspection limited/prevented by: No access to:

Roof

No access to:

Crawlspace

Not tested/not in service:

Range

Carpet

Oven

Not included as part of a building inspection:

Perimeter drainage tile around foundation, if any

Recommendations FLOORS \ Carpet on floors 31. Condition: Odors Implication(s): Hygiene issue Location: Throughout Task: Replace Further evaluation

35. Odors

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 35 of 41


Report No. 1015

INTERIOR 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

WALLS \ Plaster or drywall 32. Condition: Damaged Implication(s): Cosmetic defects Location: Various Task: Repair or replace

36. Damaged

Click on image to enlarge.

33. Condition: Water damage Implication(s): Cosmetic defects Location: Dining Room Task: Repair or replace Further evaluation

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 36 of 41


Report No. 1015

INTERIOR 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

Click on image to enlarge.

REFERENCE

37. Water damage DOORS \ Glass (glazing) 34. Condition: Safety glass not installed Implication(s): Physical injury Location: First Floor Dining Room Task: Replace Time: Immediate

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 37 of 41


Report No. 1015

INTERIOR 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

38. Safety glass not installed

Click on image to enlarge.

STAIRS \ Width 35. Condition: Too narrow Implication(s): Physical injury Task: Demolish Upgrade Time: When remodelling Cost: $3,000-$5,000

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 38 of 41


Report No. 1015

INTERIOR 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

39. Too narrow

Click on image to enlarge.

STAIRS \ Guardrails 36. Condition: Too low Implication(s): Fall hazard Location: Second Floor Task: Replace

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 39 of 41


Report No. 1015

INTERIOR 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

40. Too low APPLIANCES \ Range 37. Condition: Old Implication(s): Reduced system life expectancy Location: Kitchen Task: Replace

41. Old APPLIANCES \ Doorbell 38. Condition: Inoperative Implication(s): Equipment inoperative END OF REPORT

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 40 of 41


Report No. 1015

REFERENCE LIBRARY 1713 W Touhy Ave Unit C, Chicago, IL SUMMARY

ROOFING

EXTERIOR

www.citizenarchitects.com

September 28, 2012

STRUCTURE

ELECTRICAL

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

The links below connect you to a series of documents that will help you understand your home and how it works. These are in addition to links attached to specific items in the report. Click on any link to read about that system.

01. ROOFING, FLASHINGS AND CHIMNEYS 02. EXTERIOR 03. STRUCTURE 04. ELECTRICAL 05. HEATING 06. COOLING/HEAT PUMPS 07. INSULATION 08. PLUMBING 09. INTERIOR 10. APPLIANCES 11. LIFE CYCLES AND COSTS 12. SUPPLEMENTARY Asbestos Radon Urea Formaldehyde Foam Insulation (UFFI) Lead Carbon Monoxide Mold Household Pests Termites and Carpenter Ants

13. HOME SET-UP AND MAINTENANCE 14. MORE ABOUT HOME INSPECTIONS

This Confidential Report is prepared exclusively by Citizen Architects Inc. for our Clients only.

Page 41 of 41


Townhouse pre 1950s