STAND BY BULL Bloc SBV: Type SBV 12-18 ➔ SBV 12-230 These block batteries are designated as AGM batteries and stand out due to the universality of their applications and absolutely maintenance-free design. Other advantages include their long service life, very high power density and compatible casing dimensions. These batteries are used mainly in the UPS area for starting diesel engines and safety lighting purposes. Design

Features - Block batteries, 12 V rated voltage - Zero-maintenance for entire service life - Compensation charge voltage of 2.27 V/cell - Recommended temperature range of 20°C (max. –10°C to +40°C) - Long service life - Employment independent of position - Corrosion-resistant terminal design - Good voltage position in the high-voltage range - Non hazardous item in line with FAA und IATA (prusuant to packaging reglation 806) - Designed for a service life of 10 years + in stand by operation mode "High performance" after EUROBAT

- Positive electrode Lead/calcium, high-performance grid with pasted active mass - Negative electrode Lead/calcium, high-performance grid with pasted active mass - Separation Glass fibre non-woven web - Casing material ABS, bonded cover - Electrolyte Extremely pure sulphuric acid bound into a web - Terminal design Electrolyte-tight safety terminal sealed with epoxy resin - Cell connections Interior welding through the casing wall - Cell plug Safety valve with an overpressure ventilation system for 2 psi (14 Kpa) gas pressure


www.bannerbatteries.com

STAND BY BULL Technical details

SBV SBV SBV SBV SBV SBV SBV SBV SBV SBV SBV SBV SBV SBV SBV SBV

Type 12-18 12-26 12-33 12-44 12-55 12-70J 12-70 12-80 12-100 12-110 12-120 12-135 12-150 12-160 12-200 12-230

Rated Capacity in Ah Dimensions Charge Type Total voltage. C 20 C 10 C5 C 1 Length Width Heigth Ri Ik Termi-voltage of conn- weigth in V 1,60 V/Z. 1,80 V/Z. 1,75 V/Z. 1,65 V/Z. mm mm mm mOhm in A nal no.max. A ection kg 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12

18 26 33 44 55 70 70 80 100 110 120 135 150 160 200 230

15 23 28 42 51 63 67 80 93 95 109 135 135 164 190 230

14,5 20,2 25 36 44,3 55 58,5 70 81,5 86 96 123,5 119,5 140 164 201,5

11,2 15,2 21,2 28,5 34,8 46,2 45,2 56,9 64,6 70,4 78,4 97,7 95,7 108 131 149

181 166 195 198 228 350 260 260 306 328 408 340 482 530 520 521

76 176 130 165 138 167 168 168 168 171 176 173 170 209 240 269

167 126 160 153 210 179 212 212 212 205 227 280 242 214 220 203

9 8 5,7 5,2 5,8 4,2 4,7 4 3,4 3,2 3,0 3,2 2,8 2,7 2,5 2,2

732 900 1.100 1.400 1.700 2.100 2.100 2.400 2.900 3.000 3.300 3.750 4.200 4.700 5.400 5.900

2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

C C B C B C B B B B B C B E E E

In M 5 In M 5 In M 6 In M 6 In M 6 In M 6 In M 6 In M 6 In M 6 In M 6 In M 6 In M 6 In M 6 In M 6 In M 8 In M 8

5,4 8 10,4 13,3 17 21,6 24,3 25,4 29,6 32,5 37 40,6 44,0 55 60,9 73,5

The given electrical values are valid for loads in a fully charged condition and an ambient temperature of 20°C. * F 4.8 (Faston 4.8 mm), F 6.4 (Faston 6.4 mm), In (insert screw terminal)

Installation The blocks are suitable for position-independent installation on racks or in cabinets. On request, we supply specialracks for zones subject to earthquakes,telecommunications applications and UPS systems. The safety regulations according to EN 50272-2 are to be observed, particularly those relating to ventilation. Charging must be adjusted to the voltage limits stipulated in our data sheets. All figures relating to dimensions and weight are subject to the standard production tolerances. The electrical values are appro-. ximate. Our products are subject to ongoing development, therefore we retain the right to make changes without an obligation to inform.

Presented by:

A:

W

The adjacent drawing shows on type of installation

(D) L

L

W

(C)

(E)

W

L

W

W

(A)1

L

W

(A)2

Banner GmbH, A-4021 Linz, Banner Straße 1, Tel. 0732/3888-0, Fax 0732/3888-21598, e-mail: office@bannerbatterien.com