September 2006 — Approval Guide Gas Safety Shutoff Valves

12-20

Nominal Pipe Size, in.

Designation

Port Size, in. (mm)

Max Rated Optg. Press., psi (kPa)

1

Full

11⁄4

’’

300 (2070) 300 (2070) 600 (4135) 600 (4135) 125 (860) 125 (860) 100 (690) 70 (485) 70 (485) 40 (275) 30 (205) 50 (345) 40 (275) 40 (275) 60 (415) 50 (345)

Coen Co Inc, 1510 Tanforan Ave, Woodland CA 95776 Series CC-4730#†† CC-4730-D†† CC-4760†† CC-4760-D††

1

Full

1 1⁄ 4

’’

3⁄ 4

11⁄16 (18) 11⁄16 (18) 31⁄32 (25) 11⁄8 (29) 17⁄16 (37) 11 1 ⁄16×17⁄16 (43×37) 23⁄4×17⁄16 (70×37) 21⁄4 (57) 23⁄4 (70) 23⁄4 (70) 33⁄4 (95) 41⁄2 (114)

#

Series CC-5000 ††

1 1 1⁄ 4 1 1⁄ 2 2 2 1⁄ 2 3 #

Series CC-5000-CP ††

21⁄2 3 4

Series CC-7000#††

4 6

#

Indicates letter suffixes as follows: S - steel body, D - dc solenoid, and digit suffix to indicate type of factory-installed proof-of-valve closure switch. Switch suffix numbers are as follows: 0 - no factory-installed switch, 1 - factory-installed SPDT switch, 2 - factory-installed DPDT switch.

Karl DUNGS Inc, 524 Apollo Dr, Suite 10-30, Lino Lakes MN 55014 MV Series. Models MV (or MVD) 505 (or 507, 510, 512, 515, 520, 525, 530)/6. 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 and 3 in. NPT respectively. 7 psi (0.5 bar) MWP. MVDLE 205 (or 207, 210, 212, 215, 220, 225, 230)/6. 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2, 21⁄2 and 3 in. NPT respectively. 3 psi (0.2 bar) MWP. Operating voltage 24 V dc or 120 V ac MVD 505, 507, 510; MVDLE 205, 207, 210 available for 24 V ac operation. Available with Model CPI 400 open and closed position electrical indicator/switch with NEMA 4 housing. MVD and MVDLE models are rated for an upstream close-off pressure of 15 psi (1 bar). Models suffixed /604 are suitable for use in NEMA 4X environments. Dual Modular Valve, DMV-D and DMV-DLE Series. Models DMV-D (or -DLS) 525/11, 701 (or 702, 703) model suffixed /602 or /6; 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2, 2 and 21⁄2 in. NPT. DMV 701, 702, and 703 models suffixed /612, /622, or /632 are for proof of closure overtravel applications; DMV 701, 702, and 703 models suffixed /614, /624, or /634 are for NEMA 4X applications and proof of closure overtravel applications. DMV-D (or -DLE) 5040/11, 5050/11, 5065/11, 5080/11, 5100/11, 5125/11; 50, 65, 80, 100 and 125 DIN. DMV-ZRD (or -ZRDLE) 701 (or 702, 703)/6 or /602; 1⁄2, 3⁄4, 1, 11⁄4, 11⁄2 and 2 in. NPT. DMV ZRD and ZRDLE 701, 702, and 703 models suffixed /612, /622, or /632 are for proof of closure overtravel applications. All DMV series are 7 psi (0.5 bar) MWP. Operating voltage 120Vac, 240 V ac, 24 V ac or 24 V dc. Available with Model CPI 400 open and closed position electrical indicator/switch with NEMA 4 housing, Type K01/1 open and closed position indicator switch, GAO (or GMH, GML)-A2 pressure switches, VPS 504 S06 valve proving system and FRI .../6 series pressure regulators. Available with a vent block adaptor to allow venting between the dual valves. Series SV Gas Safety Shutoff Valves NPT Threaded Series SV(D)(DLE) abb/6cd (D) = on-off safety valve with stroke adjustment. (DLE) = Slow opening, on/off safety valve with stroke adjustment. a = pressure rating (2 = 2 psi), (5 = 5 psi), (10 = 10 psi). bb = body size (05 = 1⁄2 in.), (07 = 3⁄4 in.), (10 = 1 in.), (12 = 11⁄4 in.), (15 = 11⁄2 in.), (2 = 2 in.). c = proof of closure (0 = no proof-of-closure), 1 = with proof-of-closure using valve seal overtravel and interlock. d = type rating (2 or 4).

NPT Flanged Series SV(D)(DLE) abb/6cd (D) = on-off safety valve with stroke adjustment. (DLE) = Slow opening, on/off safety valve with stroke adjustment. a = pressure rating (2 = 2 psi), (5 = 5 psi), (10 = 10 psi). bb = body size (05 = 1⁄2 in.), (07 = 3⁄4 in.), (10 = 1 in.), (12 = 11⁄4 in.), (15 = 11⁄2 in.), (2 = 2 in.). c = proof of closure (0 = no proof-of-closure), 1 = with proof-of-closure using valve seal overtravel and interlock. d = type rating (2 or 4).

Eclipse Combustion, 1665 Elmwood Rd, Rockford IL 61103 Nominal Pipe Size, in.

Port Size, in. (mm)

Max Rated Optg. Press., psi (kPa)

Cat. No. ECI-L8040G22

1⁄ 2

G23

3⁄ 4

H7

1⁄ 4

3⁄4 (19) 3⁄4 (19) 3⁄8 (10)

2 (1) 2 (15) 15 (105)

Designation

FM Approvals