Alpha Wire

Page 97

UL TYPE CMP UL AWM STYLE 20229 CSA CMP FT6 RoHS COMPLIANT 300 VOLT

XTRA•GUARD® 5 MULTIPAIR, FOIL SHIELD

EXTRA HIGH-TEMPERATURE/CHEMICAL-RESISTANT FEP TEFLON® JACKET

CHOOSE XTRA•GUARD 5 FOR: ■

Unmatched Performance at Temperatures from –80°C to 200°C ■ Suitable for Use in Class 1 Clean Rooms ■ FDA Recognized as Food/Medical Grade (can be sterilized) ■ 100% Impervious to All Chemicals, Acids, Fuels, Solvents and Water ■ 20-30% Smaller Cable Diameter ■ Extremely Low Friction Jacket for Ease of Routing ■

XTRA•GUARD 5 APPLICATIONS: ■

Military Electronic Applications Steel, Glass and Metal Foundries ■ Mining Instruments and Controls ■ Food and Beverage Plants ■ Clean Room Environments ■ Refinery Cracker Unit Controls ■

XTRA•GUARD 5 Part No. 55491 55492 55493 55496 55499 55499/11

No. of Pairs 1 2 3 6 9 11

Jacket Thickness Inches mm 0.025 0.025 0.025 0.025 0.025 0.025

0,64 0,64 0,64 0,64 0,64 0,64

Nominal Diameter Inches mm 0.15 0.19 0.22 0.28 0.32 0.35

XTRA•GUARD 5 Part No.

OPERATING TEMPERATURE: ■ –80°C to 200°C (UL, CSA -150°C) VOLTAGE RATING: ■ 300 Volt COLOR DESCRIPTION: ■ Color Code: Chart A Page 374 ■ Jacket Color: Tan PRODUCT DESCRIPTION: ■ Conductor: Stranded Tinned Copper ■ Insulation: Color-Coded FEP Teflon® ■ Shield: Aluminum/Polyester Foil Facing In with Stranded Tinned Copper Drain Wire Equal in Size to Insulated Conductors of Cable ■ Jacket: FEP Teflon®

SPECIFICATIONS ■

UL Type CMP UL AWM Style 20229 ■ CSA CMP FT6 ■ Passes 210,000 BTU Flame Test ■ Passes Steiner Tunnel Test: (Low Smoke and Flame Generation) ■ Pennsylvania Bureau of Deep Mine Safety Approved P-MWMS-1-85 ■ RoHS Compliant ■

55481 55482 55483 55486 55489 55489/12

No. of Pairs 1 2 3 6 9 12

Jacket Thickness Inches mm 0.025 0.025 0.025 0.025 0.025 0.025

0,64 0,64 0,64 0,64 0,64 0,64

Nominal Diameter Inches mm 0.16 0.21 0.24 0.31 0.36 0.41

4,1 5,4 6,2 7,9 9,2 10,3

20 AWG (0,56mm2), 7/28 (7x0,32mm), Insulation Thickness: 0.010" (0,25mm) XTRA•GUARD 5 Part No. 55451 55452 55453 55455 55456 55459 55459/12

No. of Pairs 1 2 3 5 6 9 12

Jacket Thickness Inches mm 0.025 0.025 0.025 0.025 0.025 0.025 0.025

0,64 0,64 0,64 0,64 0,64 0,64 0,64

Nominal Diameter Inches mm 0.17 0.22 0.25 0.30 0.32 0.38 0.42

4,3 5,6 6,4 7,7 8,2 9,5 10,6

18 AWG (0,90mm2), 7/26 (7x0,40mm), Insulation Thickness: 0.010" (0,25mm) XTRA•GUARD 5 Part No. 55371 55372 55373 55376 55379

No. of Pairs 1 2 3 6 9

Jacket Thickness Inches mm 0.025 0.025 0.025 0.025 0.025

0,64 0,64 0,64 0,64 0,64

Nominal Diameter Inches mm 0.19 0.26 0.31 0.40 0.47

4,8 6,7 7,8 10,1 11,8

Teflon® is a registered trademark of E.I. DuPont Viton® is a registered trademark of DuPont Dow Elastomers

FIT® TUBING RECOMMENDATION

®

FIT® -650 – Chemical and Temperature Resistant Irradiated Viton® (See Page 132 for Product Specifications) FIT® -400 – Temperature/Chemical Resistant FEP Teflon® (See Page 129 for Product Specifications)

AVAILABILITY Made-To-Order only, 1000 ft minimum

Web Site: www.alphawire.com Email: info@alphawire.com

3,8 4,9 5,6 7,0 8,2 8,8

22 AWG (0,35mm2), 7/30 (7x0,25mm), Insulation Thickness: 0.010" (0,25mm)

CHARACTERISTICS

24 AWG (0,23mm2), 7/32 (7x0,20mm), Insulation Thickness: 0.010" (0,25mm)

F O R C O M P L E T E P R O D U C T P E R F O R M A N C E D ATA , SEE TECHNICAL SECTION IN THE BACK OF THIS BOOK.

Toll Free: 1-800-52 ALPHA • Telephone: 908-925-8000 • Fax: 908-925-6923 Europe/UK Telephone: +44 (0) 1932 772422 • Europe/UK Fax: +44 (0) 1932 772433

87


Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.