1200AF Electronic MCCB ABS1203bE

Ratings 1200AF

Frame size Type and Pole

S-Type 2-pole

-

3-pole

ABS1203bE

4-pole)

-

Rated current, In

1200A

Rated operational voltage, Ue

AC: 600V

Rated insulation voltage, Ui

AC: 600V

Rated impulse withstand voltage, Uimp Type

Long time

Current, IR

pick-up

time

Short time

Current, Im

pick-up

time

Instantaneous Current, It pick-up

time

⑤ LED

Pre-Alarm

6kV (0.5-0.6-0.7-0.8-0.9-1.0)×In, adjustable...① 5sec ± 20% at 6×Ir, fixed (2-3-4-5-6-8-10)×ln, adjustable...② 0.1-0.2-0.3 sec, adjustable...③ 11×ln, fixed within 0.03 sec, fixed between 70 to 110% of set current Ir: LED flickering over 110% of set current Ir: stays on

④ Rated frequency Rated short-circuit breaking capacity, Icu

45kA

480/500V

50kA

415/460V

65kA

380V

65kA

220/250V

100kA 50% Overload, Short-circuit

Protective function

Electronic type

Type of trip unit Mechanical Electrical

500 operations

Connection

Standard

Front connection

Mounting

Standard

Screw fixing

d c2 c1

b

a

▶ 99 page

�Trip curves

▶ 92 page

52

2500 operations

Endurance

Dimensions (mm)

�Drawings

S-Type

AC 690V

lcs=100%Icu

For more information

50-60Hz selectable by the switch of the trip unit

Weight, kg

Pole

3p

a

220

b

400

c

105

d

159