Industrial Catalog

Page 75

SPEC 5350

August, 2008

GenFree™ LSZH

XLPO, Low-Smoke, Zero-Halogen (LSZH), Low-Voltage Power, Unshielded 600V, Type RHH/RHW-LS/USE, CSA AWM I A/B, Class B

Product Construction Conductor:

Applications (cont’d.):

• USE rating for Direct Burial Applications • CT-rated for installation in Cable Tray – 1/0 AWG and larger • For use in all closed environments or populated spaces such as auditoriums, arenas and health facilities where more stringent specifications for smoke and toxicity emission levels are desired • Ideally suited for use in a broad range of commercial and Industrial applications where reliability is the major concern, where maximum performance is demanded and where space is limited

• 14 AWG thru 750 kcmil tinned coated compressed copper per ASTM B3 and B33. Class B stranding per ASTM B8.

Composite Insulation/Jacket:

• Flame-retardant, oil-resistant, limited smoke, Cross-Linked Polyolefin (XLPO), Black

Print:

• General Cable® (PLANT OF MFG) (UL) Type USE or RHH or RHW-LS VW-1 (Size) 600V Oil Res. I Sun Res. FOR CT USE*/CSA AWM I A/B 105˚C 600V FT4 month/year of MFG Sequential Footage Mark

• UL Type RHH/RHW/USE Rated at 90˚C dry, 75˚C wet • CSA AWM I A/B Rated at 105˚C • UL AWM styles 3237 and 3578 • Smooth surface for reduced coefficient of friction for ease of installation • Excellent moisture resistance • Excellent resistance to salt water • Available in colors for ease of phase identification • Minimum acid gas emissions under combustion • Meets cold bend test at -40˚C • Meets UL Oil Res. I and II

Options:

• Available in Blue, Green, Red and Gray

Applications:

• General purpose 600V Power Cable Applications • For use in conduit, open tray, underground duct and aerial installations when properly supported and installed • RHH/RHW ratings for installation in conduit or raceway

CATALOG NUMBER

COND. STRAND (CLASS B)

• UL 44 Standard for Rubber Insulated Wire • UL 758 Standard for Appliance Wiring Material • UL 854 Standard for Service Entrance Cable • UL 1685 Standard for Vertical Tray Fire Propagation and Smoke Release Test for Electrical and Optical Fiber Cables • Telcordia GR347 Core • UL Listed VW-1 • ICEA S-95-658/NEMA WC 70 • IEEE 1202 (70,000 BTU/hr) • IEEE 383 (70,000 BTU/hr) • Sizes 1/0 AWG and larger are listed “FOR CT USE” • CSA FT4 • CSA Standard C22.2 No. 0.3 • CSA Standard C22.2 No. 210.2 • Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA acceptable

Features:

* Sizes smaller than 1/0 AWG do not include “FOR CT USE”

COND. SIZE (AWG/ kcmil)

Compliances:

NOMINAL COND. DIAMETER inCHES mm

MINIMUM AVG. INSULATION THICKNESS INCHES mm

Packaging:

• Material cut to length and shipped on nonreturnable wood reels

NOMINAL CABLE O.D. INCHES mm

COPPER WEIGHT LBS/ 1000 FT

NET WEIGHT

kg/km

LBS/ 1000 FT

kg/km

14 AWG - 750 kcmil CONDUCTORS, CLASS B 14311.011400 14311.011200 14311.011000 14311.010800 14311.010600 14311.010400 14311.010200 14311.010100 14311.015100 14311.015200 14311.015300 14311.015400 14311.016000 14311.016200 14311.016500 14311.017000

14 12 10 8

7/.0242 7/.0305 7/.0385 7/.0486

0.07 0.09 0.12 0.15

1.78 2.29 3.05 3.81

0.045 0.045 0.045 0.060

1.14 1.14 1.14 1.52

0.17 0.19 0.22 0.28

4.32 4.83 5.59 7.11

13 20 32 50

19 30 48 75

18 25 38 58

27 37 57 86

6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750

7/.0612 7/.0772 7/.0974 19/.0644 19/.0745 19/.0837 19/.0940 19/.1055 37/.0822 37/.0973 37/.1162 61/.1109

0.18 0.23 0.28 0.32 0.36 0.41 0.46 0.51 0.56 0.66 0.79 0.97

4.57 5.84 7.11 8.13 9.14 10.41 11.68 12.95 14.22 16.76 20.07 24.64

0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.095 0.095 0.095 0.110

1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.41 2.41 2.41 2.79

0.31 0.36 0.42 0.49 0.53 0.58 0.63 0.68 0.76 0.87 1.00 1.21

7.87 9.14 10.67 12.45 13.46 14.73 16.00 17.27 19.30 22.10 25.40 30.73

81 129 205 258 326 411 518 653 772 1081 1544 2316

121 192 305 385 485 612 771 972 1149 1609 2298 3447

116 171 257 331 406 495 612 757 905 1237 1728 2572

173 254 382 493 604 737 911 1126 1347 1841 2571 3827

Dimensions and weights are nominal; subject to industry tolerances.

Phone: 888-593-3355 www.generalcable.com


Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.