SPEC 4500

January, 2008

CVTC

®

XLPE/PVC, Control, Unshielded 600V, UL Type TC-ER1—E-2 Color Code Product Construction Conductor:

• 14 AWG thru 10 AWG fully annealed stranded bare copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

• Flame-retardant Cross-Linked Polyethylene (XLPE) • Color-coded per ICEA Method 1; Table E-2 (Does not include white or green)

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. COND. THICKNESS CABLE O.D. LBS/ OF SIZE COND. THICKNESS LBS/ COND. (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

14 AWG MULTI CONDUCTORS 770460 771080* 770530 770610 770420 770560 770540 770470 770550 770450* 295320* 770430*

2 Flat 2 3 4 5 7 9 12 19 25 30 37

14 14 14 14 14 14 14 14 14 14 14 14

7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03

.235 x .370 5.97 x 9.40

0.365 0.390 0.425 0.465 0.590 0.620 0.680 0.800 0.985 1.050 1.130

9.27 9.91 10.80 11.81 14.99 15.75 17.27 20.32 25.02 26.67 28.70

25 25 40 53 66 93 119 159 252 323 387 490

37 37 59 79 99 138 177 237 375 481 571 729

62 73 93 116 140 176 245 302 460 641 740 888

92 109 138 173 208 262 365 449 685 954 1101 1322

40 41 86 65 86 108 150 193 258 403 515 618 741

60 86 61 96 128 143 96 125 128 157 160 191 224 260 288 340 385 429 600 681 767 885 920 1005 1103 1185

128 143 213 186 234 284 387 506 638 1013 1317 1496 1764

66 67 135 101 135 167 234 295 402

98 100 200 150 200 249 349 440 598

170 193 299 257 351 427 552 713 958

12 AWG MULTI CONDUCTORS 770480 2 Flat 2 346920* 365720 3+ Grnd 3 770570 4 770490 5 770410 7 770950 9 770580 12 770520 19 770700* 25 347110* 30 347120* 37 347130*

12 12 12 12 12 12 12 12 12 12 12 12 12

7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305

770590 2 Flat 2 346930* 770670 3+ Grnd 3 770600 4 770370 5 770380 7 770900 9 770390* 12 770400

10 10 10 10 10 10 10 10 10

7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03 2.03

.245 x .400 6.22 x 10.16

0.410 0.435 0.435 0.475 0.515 0.595 0.695 0.780 0.930 1.095 1.150 1.240

10.41 11.05 11.05 12.07 13.08 15.11 17.65 19.81 23.62 27.81 29.21 31.50

10 AWG MULTI CONDUCTORS 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080

1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03

.290 x .480 7.37 x 12.19

0.455 0.485 0.485 0.515 0.615 0.670 0.785 0.895

11.56 12.32 12.32 13.08 15.62 17.02 19.94 22.73

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1Approved as TYPE TC-ER for Exposed Run applications of 3 or more conductors as defined by NEC.

114 130 201 173 236 287 371 479 644

Jacket:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)

Print

• GENERAL CABLE® (WC) CVTC® XX/C XXAWG FR-XLP/PVC (UL) Type TC-ER1 XHHW-2 CDRS DIR BUR SUN RES 90˚C WET or DRY 600V DAY/ MONTH/YEAR OF MFG sequential footage mark

Options:

• Tinned copper conductor • Class C stranding • E-1 Color Code • Overall shielded multi conductors • Ethylene Propylene Rubber (EPR) insulation • Low-lead Hypalon Chlorosulfonated Polyethylene (CSPE)/Elastomer blend—See CHTC® Spec 4050 • Insulated or uninsulated ground conductor • Other constructions available upon request

Applications:

• In free air, raceways and direct burial • In wet or dry locations • Approved for direct burial, Class I, Div. 2 industrial hazardous locations per NEC • Permitted for Exposed Run ‘ER’ use in accordance with NEC for 3 or more conductors

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent electrical properties • Abrasion- and chemical-resistant • Sunlight- and weather-resistant • Meets cold bend test at -25˚C • Meets the crush and impact requirements of Type MC cable

Compliances:

Industry Compliances: • UL 44 Type XHHW-2 • UL 1277 Type TC-ER for 3 or more conductors • UL 1581 • ICEA S-73-532 • ICEA S-95-658/NEMA WC 70 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging: • Material cut to length and shipped on non-returnable wood reels