Industrial Catalog

Page 50

SPEC 4310

January, 2008

FREP

®

FR-EPR/CPE, Control, Unshielded 600V, UL Type TC-ER1—E-1 Color Code Product Construction Conductor:

• 14 AWG thru 10 AWG fully annealed stranded tinned copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

• Flame-retardant Ethylene Propylene Rubber (FR-EPR) Type II • Color-coded per ICEA Method 1; Table E-1 (Includes white or green)

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. COND. THICKNESS CABLE O.D. LBS/ OF SIZE COND. THICKNESS LBS/ COND. (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

14 AWG MULTI CONDUCTORS 280590 280230 280240 280250 280260 280270 280280 280290* 385350* 385360* 385370*

2 Flat 3 4 5 7 9 12 19 25 30 37

14 14 14 14 14 14 14 14 14 14 14

7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03

.365 x .230 9.30 x 5.80

0.390 0.425 0.465 0.505 0.620 0.700 0.815 0.935 1.030 1.110

9.91 10.80 11.81 12.83 15.75 17.78 20.70 23.75 26.16 28.19

26 39 53 66 92 118 158 250 323 387 466

38 59 78 98 137 176 235 372 481 576 694

61 92 115 139 173 240 301 468 624 747 875

91 137 171 207 257 357 448 696 929 1112 1302

40 41 64 85 106 149 191 247 391 515 618 762

60 82 61 94 95 124 127 157 158 191 221 268 285 337 368 428 582 688 767 854 920 1002 1134 1240

122 140 185 234 284 399 502 637 1024 1271 1491 1845

64 65 100 134 167 234 295 402

95 97 150 199 249 349 440 598

168 190 256 348 423 567 691 969

12 AWG MULTI CONDUCTORS 279850 2 Flat 2 280350* 3 280360 4 279910 5 280370 7 280380 9 280390* 12 280400 19 383930* 25 383940* 30 383950* 37 330800*

12 12 12 12 12 12 12 12 12 12 12 12

7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305

280600* 280420* 279920 279930 330990* 280430* 382880* 383970*

10 10 10 10 10 10 10 10

7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03 2.03

.400 x .245 10.20 x 6.20

0.410 0.435 0.475 0.520 0.595 0.695 0.765 0.940 1.095 1.150 1.240

10.41 11.05 12.07 13.21 15.11 17.65 19.43 23.88 27.81 29.21 31.50

10 AWG MULTI CONDUCTORS 2 Flat 2 3 4 5 7 9 12

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080

1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03

.445 x .270 11.30 x 6.90

0.455 0.485 0.560 0.615 0.670 0.760 0.950

11.56 12.32 14.22 15.62 17.02 19.30 22.99

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1Approved as TYPE TC-ER for Exposed Run applications of 3 or more conductors as defined by NEC.

113 128 172 234 284 381 464 651

Jacket:

• Flame-retardant thermoplastic Chlorinated Polyethylene (CPE)

Print

• GENERAL CABLE® (WC) FREP® XX/C XXAWG EPR/CPE (UL) Type TC-ER1 XHHW-2 CDRS 90°C WET or DRY 600V DIR BUR SUN RES DAY/ MONTH/YEAR OF MFG sequential footage mark

Options:

• 2kV version • Bare copper conductor • Class C stranding • E-2 Color Code—See Spec 4300 • Overall shielded multi conductor • Flame-retardant Cross-Linked Polyethene (FR-XLPE) insulation • Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket • Other constructions available upon request

Applications:

• In free air, raceways or direct burial • In wet or dry locations • Permitted for Exposed Run ‘ER’ use in accordance with NEC for 3 or more conductors • Approved for direct burial, Class I, Div. 2 industrial hazardous locations per NEC

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical, thermal and electrical properties • Sunlight- and weather-resistant • Excellent moisture resistance • Excellent resistance to compression cuts and heat deformation • Low coefficient of fri ction for easy pulling • Excellent flame resistance—burns to ash; does not exhibit thermoplastic drip • Excellent low temperature cold bend characteristics • Meets cold bend test at -40˚C • Meets the crush and impact requirements of Type MC cable for 3 or more conductors

Compliances:

Industry Compliances: • UL 44 Type XHHW-2 • UL 1277 Type TC-ER for 3 or more conductors • UL 1581 • ICEA S-73-532 • ICEA S-95-658/NEMA WC70 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 • ICEA T-29-520 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.