YES

Troubleshooting Fuel System

• Reassemble nozzle line. • Restart burner.

A

YES

YES

If any problem repeats itself, start over.

Does unit continue to run without shutting off on safety?

NO

NO

• If noisy, open inspection door. • Nozzle may be too large or unit may need to be vacuumed out.

• Clean or replace CAD CELL eye.

Does unit continue to run without shutting off on safety?

YES

NO

See Electrical Troubleshooting.

YES

• Check coupling between pump and motor.

Is it turning? NO

• Remove motor from burner housing. • Turn pump shaft by hand.

YES

• Check tube for any obstructions or carbon build-up on end cone.

YES

Replace pump. Go back to Box A.

Is blast tube free of any obstruction? NO

Replace coupling.

Does shaft turn freely in direction of arrow on pump cover? NO

Clean out using a brush.

Go to Box A.

F.W. Webb Heating Catalog

F.W. Webb Company

229

15 technical information

Is flame uniform and relatively quiet?

• Run for a cycle to be sure flame doesn’t cut out.