8-76
Switching Devices Switches — Rotary Disconnect February 2007
Product Family Overview
Technical Data and Specifications Table 8-117. UL 508 Technical Characteristics Description
M-Frame
R-Frame
W-Frame
Catalog Number
Catalog Number
Catalog Number
C362NM16 C362NM20 C362NM25 C362NR30 C362NR40 C362NW60 C362NW80 C362NW100 C362NW125 Rating (3 Poles)
16A
80A
100A
UL Approval
UL508/cUL UL508/cUL UL508/cUL UL508/cUL UL508/cUL UL508/cUL
UL508/cUL
UL508/cUL
UL508/cUL
Short Circuit Rating kA
5
5
5
10
10
10
10
10
10
Fuse Type
RK5
RK5
RK5
RK5
RK5
RK5
RK5
RK5
RK5
Fuse Rating (A)
30
30
30
80
80
150
150
150
150
2
3
5
7-1/2
10
15
20
25
25
Maximum UL Horsepower Ratings (3-Phase)
8
Maximum UL Horsepower
220 – 240 Vac
20A
25A
30A
40A
60A
125A
440 – 480 Vac
7-1/2
7-1/2
10
15
20
30
40
50
50
600 Vac
7-1/2
10
15
25
30
40
50
60
60
120 Vac
1/2
1
1-1/2
2
2
3
5
5
5
Ratings (1-Phase)
240 Vac
1.5
2
3
5
5
10
15
15
15
Electrical Endurance
(Operation Cycles)
6000
6000
6000
6000
6000
6000
6000
6000
6000
Mechanical Endurance
(Operation Cycles)
6000
6000
6000
6000
6000
6000
6000
6000
6000
Terminal Lugs
Wire Size
#6 – #10
#6 – #10
#6 – #10
#14 – #8
#14 – #8
#14 – #3
#14 – #3
#14 – #3
#14 – #3
Wire Type
Cu
Cu
Cu
Cu
Cu
Cu
Cu
Cu
Cu
.32 (.15)
.32 (.15)
.32 (.15)
.44 (.20)
.44 (.20)
.66 (.30)
.66 (.30)
.66 (.30)
.66 (.30)
Weight in Lbs. (kg)
Table 8-118. IEC Technical Characteristics Description
M-Frame
R-Frame
W-Frame
Catalog Number
Catalog Number
Catalog Number
C362NM16 C362NM20 C362NM25 C362NR30 C362NR40 C362NW60 C362NW80 C362NW100 C362NW125 Thermal Current Ith (40°C)
16A
20A
25A
32A
40A
63A
80A
100A
125A
Rated Insulation Voltage Ui (V)
800
800
800
690
690
690
690
690
690
Rated Impulse Withstand Uimp (kV)
8
9
8
8
8
8
8
8
8
Operational Current (A)
3 Poles
3 Poles
3 Poles
3 Poles
3 Poles
3 Poles
3 Poles
3 Poles
3 Poles
400 Vac – ac 22 A – ac 23 A
16 16
20 20
25 25
32 25
40 25
63 63
80 63
80 63
80 63
500 Vac – ac 22 A – ac 23 A
16 16
20 16
25 20
32 25
40 25
63 45
80 45
80 45
80 45
690 Vac – ac 22 A – ac 23 A
16 16
20 16
25 20
32 25
40 25
63 40
80 40
80 40
80 40
400 Vac– ac 23
8
9
11
11
11
25
25
25
25
500 Vac – ac 23
9
9
11
15
15
25
25
25
25
690 Vac – ac 23
12.5
12.5
15
22
22
25
25
25
25
Short Circuit Current with Fuses (kA rms)
50
50
50
50
50
50
50
50
50
Maximum Rating for Associated Fuses gG (A)
16
20
25
32
40
63
80
80
80
Motor Power (kW)
Overload Capacity
Cutoff Current
5.9
5.9
5.9
5
5
8
8
8
8
Short Time Withstand Current lcw 1 s (kA)
1.2
1.2
1.2
1
1
1.5
1.5
1.5
1.5
100,000
100,000
100,000
20,000
20,000
20,000
20,000
20,000
20,000
1,500
1,500
1,500
1,500
1,500
1,500
1,500
1,500
1,500
1.5 to 6
1.5 to 6
1.5 to 6
1.5 to 16
1.5 to 16
1.5 to 35
1.5 to 35
1.5 to 35
1.5 to 35
Withstand Mechanical Electrical (400 Vac 23)
Connection Cu (mm2)
For more information visit: www.eaton.com
CA08101001E