Airwell 2011 Catalogue

Page 39

DUO / TRIO / QUATTRO

Cooling

Heating

Outdoor unit

Power supply 1-230V - 50 Hz

Capacity Power input EER/Energy Label Operating limits Capacity Capacity at -15°C Power input COP/Energy Label Operating limits Sound pressure level 1 mt Sound power level Airflow Compressor type Dimensions (WxDxH) Weight Part number

Power supply side Power supply 1-230V - 50Hz Power cable section Fuse rating Electrical connections Suction pipe diameter Pipe line Liquid pipe diameter Max lenght Max lenght per circuit Max height between indoor and outdoor units Max height between indoor units

ACCESSORIES Mounting bracket

* Available - Not available

7ACTL0016

kW kW °C kW kW kW °C dB(A) dB(A) m3/h mm kg

mm2 A mm2 inches inches m m m m

DUO-YAZ2 18 DCI

TRIO-YAZ3 18 DCI

TRIO-YAZ3 24 DCI

QUATTRO-YAZ4 30 DCI

5 (1.2-6.4) 1.47 3.4/A -10°/ 46° Dry bulb 6.0 (1.0-6.8) 3.7 1.66 3.61/A -15°/24° Dry Bulb 53 63 2160 Rotary DC Inverter 795x290x610 39 7SP091150

6.8 (2.2-10.00) 2.11 3.22/A -5°/43° Dry Bulb 8.0 (2.8-11.0) 2.21 3.62/A -15°/24° Dry Bulb 58 68 3300 Rotary DC Inverter 955x396x700 59 7SP091156

7.35 (1.3-9.0) 2.24 3.28/A -10/46°C Dry Bulb 9.2 (0.95-11.0) 5.4 2.31 3.98/A -15°/24° Dry Bulb 57 69 3600 Twin Rotary DC Inverter 950x413x864 69 7SP091149

8 (1.4-9.2) 2.38 3.36/A -10°/46° Dry Bulb 9.8 (0.95-11) 5.7 2.36 4.15/A -15°/24° Dry Bulb 57 69 3600 Twin Rotary DC Inverter 950x413x864 70 7SP091151

Outdoor 3x2.5 20 2x(4x1.5) 2x3/8” 2x1/4” 30 25 10 5

Outdoor 3x4.0 32A 3x (4x1.0) 3x3/8” 3x1/4” 70 20 10 10

Outdoor 3x2.5 25 3x(4x1.5) 2x3/8” + 1x1/2” 3x1/4” 50 25 15 15

Outdoor 3x2.5 25 4x(4x1.5) 3x3/8” + 1x1/2” 4x1/4” 70 25 15 15

DUO- YAZ2 18 DCI

TRIO- YAZ3 24 DCI

QUATTRO- YAZ4 30 DCI

*

-

-

39