SYN3000
Description
Auxiliary Supply: Model 20-56 V Operating Range: Power Consumption: Type Tests:
Temperature Range: Ambiente Temperature: Storage Temperature:
20-56 VDC 8W IEC 61000-4, Part 2, 3, 4, 5, Testlevel III IEC 60255, Part 5, Testlevel III IEC 60255/22, Part 1, Testlevel III
0 to +50 Degree -20 to +70 Degree
7.2. Case and Dimensions The SYN3000 has a standard 19" case with 42 U width and 3 U height and is also supplied with a panel mounting frame. Dimensions: Sub Rack Model Width x Height x Depth: 213 x 129 x 232 mm Weight: 1,5 kg Dimensions: Mounting Frame with Sub Rack Model Width x Height x Depth: 247 x 164 x 232 mm Weight: 2 kg Dimensions: Projection Mounting Model Width x Height x Depth: 247 x 164 x 266 mm Weight: 3,5 kg
7.3. Parameter Setting Ranges The following values contain the minimum and maximum values of the parameter settings. Minimum Frequency Difference df: Maximum Frequency Difference df:
0,01 Hz 0,25 Hz
Minimum Voltage Difference dV: Maximum Voltage Difference dV:
1V 30 V
Maximum Synchronizing Voltage, Adjustable for Each System , Vmax:
150 V
Minimum Synchronizing Voltage, Adjustable for Each System Vmin:
30 V
Maximum Permissible Phase Angle PHImax:15 Degree Electrical, Synchronizing Mode: 1 45 Degree Electrical, Synchronizing Mode: 2,3,4,5 Maximum Permissible Residual Voltage of a Dead System :
20 V
Maximum Adjustable CB Closing Time:
500 ms
Dwg.No.: 4-632 849 Page
48/64
PE/SYN3BE.DOC
Edition: 08.01.2002