Description

Auxiliary Supply: Model 20-56 V Operating Range: Power Consumption: Type Tests:

Temperature Range: Ambiente Temperature: Storage Temperature:

20-56 VDC 8W IEC 61000-4, Part 2, 3, 4, 5, Testlevel III IEC 60255, Part 5, Testlevel III IEC 60255/22, Part 1, Testlevel III

0 to +50 Degree -20 to +70 Degree

7.2. Case and Dimensions The SYN3000 has a standard 19" case with 42 U width and 3 U height and is also supplied with a panel mounting frame. Dimensions: Sub Rack Model Width x Height x Depth: 213 x 129 x 232 mm Weight: 1,5 kg Dimensions: Mounting Frame with Sub Rack Model Width x Height x Depth: 247 x 164 x 232 mm Weight: 2 kg Dimensions: Projection Mounting Model Width x Height x Depth: 247 x 164 x 266 mm Weight: 3,5 kg

7.3. Parameter Setting Ranges The following values contain the minimum and maximum values of the parameter settings. Minimum Frequency Difference df: Maximum Frequency Difference df:

0,01 Hz 0,25 Hz

Minimum Voltage Difference dV: Maximum Voltage Difference dV:

1V 30 V

Maximum Synchronizing Voltage, Adjustable for Each System , Vmax:

150 V

Minimum Synchronizing Voltage, Adjustable for Each System Vmin:

30 V

Maximum Permissible Phase Angle PHImax:15 Degree Electrical, Synchronizing Mode: 1 45 Degree Electrical, Synchronizing Mode: 2,3,4,5 Maximum Permissible Residual Voltage of a Dead System :

20 V

Maximum Adjustable CB Closing Time:

500 ms

Dwg.No.: 4-632 849 Page