O&M Forced Draft, Water, Hi Temp and Low NOx

Page 51

NOTE

G. Remove wire from Terminal '6' and connect to Terminal 'BNO'.

F. Remove wire from Terminal '5' and connect to Terminal 'BCOM'.

E. Remove wire from Terminal '4' and connect to Terminal 'BNO'.

D. Remove wire from Terminal '2' and connect to Terminal 'PNO'.

C. Remove wire from Terminal '1' and connect to Terminal 'PCOM'.

NOTE: Power wires connected to Terminals 'H' and 'N' on 150E should be from the boiler's control transformer connections which are usually designated 'L1' and 'L2'. The 150E SHOULD NOT be powered as part of any operating or safety circuit.

B. Connect 'Neutral' (L2) wire from power supply to Terminal 'N'.

A. Connect 'Hot' (L1) wire from power supply to Terminal 'H'.

Pump Terminals

Burner Terminals

Probe LED's

0-60 Second Adjustable Burner Off Delay

CUT-OFF AND ALARM SWITCH

LOW WATER CUT-OFF AND ALARM SWITCH

Š2002 ITT Industries Inc. Printed in U.S.A. 10-02 210543

3500 N. Spaulding Avenue Chicago, Illinois 60618 tel: 773 267-1600 fax: 773 267-0991 www.mcdonnellmiller.com

110 Volt Input Test from Boiler Switch Manual Reset Circuit Power (If applicable) Low Water LED Green LED Red

H

N

PNO

PNC

PCOM

BNO

BNC

BCOM

Top Middle Bottom Blue Yellow Red

Probe Connections

Electronic Relays (Series 150E and 157E)

PUMP SWITCH

ALARM LOW WATER PUMP CIRCUIT CUT-OFF CIRCUIT TERMINALS TERMINALS TERMINALS

Mercury Switches (Series 150 and 157)

30

Read and follow installation instructions included with 150E/157E control.

PUMP SWITCH

PUMP ALARM LOW WATER CUT-OFF CIRCUIT CIRCUIT TERMINALS TERMINALS TERMINALS

Snap Switches (Series 150S and 157S)

Secs.

Wiring connections for a Series 150E/157E when used as a replacement for a Series 150/157 (mercury) or 150S/157S (snap) switch unit.

Installation & Maintenance Instructions MM-416